13.2. Relationship Between The Condition Of The Air Conditioner And
Pressure And Electric Current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
13.3. Diagnosis Methods Of A Malfunction Of A Compressor And 4-way Valve
Cooling Mode
Condition of the
air conditoner
Low Pressure
High Pressure
Electric current during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or Strainer
Short circuit in the indoor unit
Heat radiation deficiency of
the outdoor unit
Inefficient compression
Nature of fault
Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90
°
C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
Содержание CS-V28EKE CU-V28EKE
Страница 8: ...8 4 Location of Controls and Components Indoor Unit Outdoor Unit Remote Control ...
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 10: ...10 5 2 Outdoor Unit ...
Страница 11: ...11 6 Refrigeration Cycle Diagram ...
Страница 12: ...12 7 Block Diagram ...
Страница 13: ...13 8 Wiring Connection Diagram ...
Страница 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit BOTTOM VIEW ...
Страница 15: ...15 TOP VIEW ...
Страница 16: ...16 9 2 Indicator And Receiver BOTTOM VIEW TOP VIEW ...
Страница 20: ...20 This can be used for left rear piping and left bottom piping also ...
Страница 43: ...43 15 Technical Data 15 1 Thermostat Characteristics ...
Страница 45: ...45 15 3 Operation Characteristics 15 3 1 CS V28EKE CU V28EKE ...
Страница 46: ...46 ...