32
11.8. Horizontal Airflow Direction Control
11.8.1.
Auto Control
• When the horizontal airflow direction is set to Auto using the
remote control, the vanes swings left and right for Cooling
and Soft Dry (0
°
-44
°
) as shown in the diagram.
• When stop operation using the remote control, the vanes is
reset, and stop at the reset position.
• During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that condition,
the vanes will stop swinging and rest at 22
°
.
• During dew prevention control, Airflow Direction Auto-control
angle change from 0
°
-44
°
to 14
°
-30
°
under Cooling and Soft
Dry operation mode.
11.8.2.
Manual Control
• When the horizontal airflow direction is set to Manual using
the remote control, the automatic airflow is released and the
airflow direction vane move left and right in the range shown
in the diagram.
The louver can be adjusted by pressing the button to the
desired vane position.
• When stop operation using the remote control, the vanes is reset, and stopped at reset position.
• During dew prevention control, Airflow Direction Manual control angle change from 0
°
, 11
°
, 22
°
, 33
°
, 44
°
to 14
°
, 18
°
, 22
°
, 26
°
,
30
°
under Cooling and Soft Dry operation mode.
11.9. Powerful Operation
• The Powerful operation is to achieve the setting temperature quickly.
(Cooling and Soft Dry Operation condition)
• When Powerful operation is set, the setting temperature will be automatically decreased 3
°
C internally against the present set-
ting temperature (Lower temperature limit: 16
°
C).
• This operation automatically will be running under SHi Fan Speed (Cooling).
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10
°
lower than previous.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10
°
downward.
• Powerful operation stops when:-
- Powerful operation has operate for 15 minutes.
- Powerful button is pressed again.
- Quiet button is pressed.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Operating mode is changed.
11.10. Quiet Operation
• The Quiet operation is to provide quiet cooling/heating operation condition compare to normal operation.
(Cooling and Soft Dry Operation condition)
• Once the Quiet Mode is set at the remote control, Quiet Mode LED illuminates. The sound level will reduce either around 2 dB(A)
for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present sound level operation.
• Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo + 100
rpm). After that, it goes back to QLo+180rpm (However Quiet LED remains on).
Содержание CS-V28EKE CU-V28EKE
Страница 8: ...8 4 Location of Controls and Components Indoor Unit Outdoor Unit Remote Control ...
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 10: ...10 5 2 Outdoor Unit ...
Страница 11: ...11 6 Refrigeration Cycle Diagram ...
Страница 12: ...12 7 Block Diagram ...
Страница 13: ...13 8 Wiring Connection Diagram ...
Страница 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit BOTTOM VIEW ...
Страница 15: ...15 TOP VIEW ...
Страница 16: ...16 9 2 Indicator And Receiver BOTTOM VIEW TOP VIEW ...
Страница 20: ...20 This can be used for left rear piping and left bottom piping also ...
Страница 43: ...43 15 Technical Data 15 1 Thermostat Characteristics ...
Страница 45: ...45 15 3 Operation Characteristics 15 3 1 CS V28EKE CU V28EKE ...
Страница 46: ...46 ...