10.4.4.
CONNECT THE CABLE TO THE OUTDOOR UNIT
(FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT)
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 245 IEC 57 or heavier cord.
3. Secure the cable onto the control board with the holder (clamper).
4. Cable connection to the power supply (220-240V, 50Hz) through knife switch (Disconnecting means).
• Connect the approved polychloroprene sheathed power supply cable 3 × 4.0 mm
2
(V28EK), type designation 245 IEC 57 or
heavier cord to the terminal board, and connect the other end of the cable to knife switch (Disconnecting means).
Note
: Knife switch (Disconnecting means) should have minimum 3.5 mm contact gap.
●
Secure the cable onto the control board with the holder (clamper).
Содержание CS-V28EKE CU-V28EKE
Страница 8: ...8 4 Location of Controls and Components Indoor Unit Outdoor Unit Remote Control ...
Страница 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 10: ...10 5 2 Outdoor Unit ...
Страница 11: ...11 6 Refrigeration Cycle Diagram ...
Страница 12: ...12 7 Block Diagram ...
Страница 13: ...13 8 Wiring Connection Diagram ...
Страница 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit BOTTOM VIEW ...
Страница 15: ...15 TOP VIEW ...
Страница 16: ...16 9 2 Indicator And Receiver BOTTOM VIEW TOP VIEW ...
Страница 20: ...20 This can be used for left rear piping and left bottom piping also ...
Страница 43: ...43 15 Technical Data 15 1 Thermostat Characteristics ...
Страница 45: ...45 15 3 Operation Characteristics 15 3 1 CS V28EKE CU V28EKE ...
Страница 46: ...46 ...