13.4.2 S18MK, S24MK, S28MK
•
Overheating Prevention Control
o
When the IPM temperature rises to 100°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 95°C.
•
DC Peak Current Control
o
When electric current to IPM exceeds set value of 18.5A, the compressor will stop operate.
During operation starts, if the DC peak current is detected after 30 seconds, the operation will restart
after 2 minutes.
During operation starts, if the DC peak current is detected within 30 seconds, the operation will restart
after 1 minute.
o
After compressor starts for 30 seconds, if DC peak current is detected exceeding 18.5A and this condition
repeats continuously for 7 times, all indoor and outdoor relays will be cut off. Timer LED blinks and “F99”
indicated.
13.5 Compressor Overheating Prevention Control (For S18, S24MK, S28MK
only)
•
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
•
If compressor discharge temperature exceeds 112°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. “F97” is indicated.
Compressor=OFF
Compressor Frequency
Reduced
Compressor Frequency
Maintain
Free
Comp Discharge temperature
112°C
96°C
110°C
100°C
97°C
90°C
13.6 Low Pressure Prevention Control (Gas Leakage Detection)
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
•
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
13.7 Compressor Tank Temperature Rise Protection Control
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
•
Control
contents
o
Compressor stops (and restart after 3 minutes)
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
13.8 Low Frequency Protection Control 1
•
When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
Содержание CS-S12MKQ
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 15: ...15 4 2 3 CU S18MKQ CU S24MKQ ...
Страница 16: ...16 4 2 4 CU S28MKQ ...
Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9MKQ CU S9MKQ CS S12MKQ CU S12MKQ ...
Страница 18: ...18 5 2 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ CS S28MKQ CU S28MKQ ...
Страница 19: ...19 6 Block Diagram 6 1 CS S9MKQ CU S9MKQ ...
Страница 20: ...20 6 2 CS S12MKQ CU S12MKQ ...
Страница 21: ...21 6 3 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ ...
Страница 22: ...22 6 4 CS S28MKQ CU S28MKQ ...
Страница 33: ...33 8 2 Outdoor Unit 8 2 1 CU S9MKQ ...
Страница 37: ...37 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 38: ...38 9 1 2 Power Printed Circuit Board 9 1 2 1 CS S9MK CS S12MK 9 1 2 2 CS S18MK CS S24MK ...
Страница 40: ...40 9 1 6 Comparator Printed Circuit Board 9 1 7 Human Activity Sensor Printed Circuit Board ...
Страница 41: ...41 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9MK ...
Страница 42: ...42 9 2 1 2 CU S12MK ...
Страница 43: ...43 9 2 1 3 CU S18MK CU S24MK ...
Страница 44: ...44 9 2 1 4 CU S28MK ...
Страница 45: ...45 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9MKQ ...
Страница 115: ...115 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 116: ...116 16 1 1 4 To remove control board Figure 7 16 1 1 5 To remove cross flow fan and indoor fan motor Figure 8 Figure 9 ...
Страница 117: ...117 Figure 10 Figure 11 ...
Страница 119: ...119 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 121: ...121 Figure 21 Figure 22 Figure 23 ...