13. Protection
Control
13.1 Restart Control (Time Delay Safety Control)
•
The compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
•
This control is not applicable if the power supply is cut off and on again.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2 30 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, force stop by pressing the
OFF/ON button at the remote control is permitted or the Auto OFF/ON button at indoor unit.
•
The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
13.3 Total Running Current Control
•
When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
•
If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
•
However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3
minutes.
Model S9*** S12*** S18*** S24*** S28***
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Cooling / Soft Dry (A)
5.5
15.0
6.8
15.0
9.3
14.8
12.0
19.0
13.3
19.3
Cooling / Soft Dry (B)
5.0
15.0
6.3
15.0
8.8
14.8
11.5
19.0
12.3
19.3
•
The first 30 minutes of cooling operation, (A) will be applied.
13.4 IPM (Power Transistor) Prevention Control
13.4.1 S9MK,
S12MK
•
Overheating Prevention Control
o
When the IPM temperature rises to 100°C, compressor operation will stop immediately.
o
Compressor operation restarts after 3 minutes the temperature decreases to 95°C.
•
DC Peak Current Control
o
When electric current to IPM exceeds set value of 18.5A, the compressor will stop operate. Then, operation
will restart after 3 minutes.
o
If the set value exceeds again more than 30 seconds after the compressor starts, the operation will restart
after 2 minutes.
o
If the set value exceeds again within 30 seconds after the compressor starts, the operation will restart after 1
minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off.
(B)
(A)
Outdoor air temperature
38.5°C
37.5°C
Содержание CS-S12MKQ
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 15: ...15 4 2 3 CU S18MKQ CU S24MKQ ...
Страница 16: ...16 4 2 4 CU S28MKQ ...
Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9MKQ CU S9MKQ CS S12MKQ CU S12MKQ ...
Страница 18: ...18 5 2 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ CS S28MKQ CU S28MKQ ...
Страница 19: ...19 6 Block Diagram 6 1 CS S9MKQ CU S9MKQ ...
Страница 20: ...20 6 2 CS S12MKQ CU S12MKQ ...
Страница 21: ...21 6 3 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ ...
Страница 22: ...22 6 4 CS S28MKQ CU S28MKQ ...
Страница 33: ...33 8 2 Outdoor Unit 8 2 1 CU S9MKQ ...
Страница 37: ...37 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 38: ...38 9 1 2 Power Printed Circuit Board 9 1 2 1 CS S9MK CS S12MK 9 1 2 2 CS S18MK CS S24MK ...
Страница 40: ...40 9 1 6 Comparator Printed Circuit Board 9 1 7 Human Activity Sensor Printed Circuit Board ...
Страница 41: ...41 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9MK ...
Страница 42: ...42 9 2 1 2 CU S12MK ...
Страница 43: ...43 9 2 1 3 CU S18MK CU S24MK ...
Страница 44: ...44 9 2 1 4 CU S28MK ...
Страница 45: ...45 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9MKQ ...
Страница 115: ...115 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 116: ...116 16 1 1 4 To remove control board Figure 7 16 1 1 5 To remove cross flow fan and indoor fan motor Figure 8 Figure 9 ...
Страница 117: ...117 Figure 10 Figure 11 ...
Страница 119: ...119 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 121: ...121 Figure 21 Figure 22 Figure 23 ...