Patrol Sensor Control
o
First 2 minutes from Patrol function activates is stabilization time, during stabilization time, no air dirtiness
level is monitored. The Air Dirtiness level is set to Clean, Patrol LED turns blue color.
o
After that, Patrol sensor starts to record the resistance value at fixed interval. Higher resistance value
indicates cleaner air.
o
The air dirtiness level is monitored by comparing the current resistance value with maximum resistance value
from time to time to get the Air Dirtiness Value.
o
There are 3 air dirtiness level, based on the Air Dirtiness Value:
Air Dirtiness level 0: Clean
– Patrol LED = blue color
Air Dirtiness level 1: Moderate
– Patrol LED = orange color
Air Dirtiness level 2: Contaminated – Patrol LED = red color
Air Dirtiness Level 0
Air Quality Worsen
G1
Air Dirtiness Level 1
G3
G2
G4
Air Dirtiness Level 2
Air Quality Improve
•
Dirtiness level sensitivity adjustment
It is possible to change the Patrol sensor sensitivity, where the Threshold value (G1 ~ G4) will be shifted
accordingly:
1 Press and release “SET” button.
2 Press
Timer
▲
/ Timer
▼
button to select sensitivity.
(Air 1 “Low Sensitivity”
↔
Air 2 “Standard” (Default)
↔
Air 3 “High Sensitivity”)
3 Confirm setting by pressing “Timer Set” button. LCD returned to original display after 2 seconds.
4 LCD returned to original display if remote control does not operate for 30 seconds
•
e-ion
Control
o
e-ion operation starts condition
When dirtiness at level 2 (Patrol LED turns red).
2 minutes after stabilization time (Patrol LED turns red).
4 hours at level 0 (Patrol LED turns red).
o
e-ion operation time
If dirtiness level improves from level 2 to level 1 (Patrol LED from red to orange), the unit carries out level
change after 60 seconds.
When dirtiness level returns to level 0 (Patrol LED turns blue) continuously for 11 minutes or more, e-ion
operation stops.
•
Dirtiness Level and fan speed
o
When e-ion operation starts, the fan speed increases based on dirtiness level:
rpm shift
Dirtiness level
Patrol individual
operation
Combine operation
Dirtiness level 0
No change
No change
Auto
Manual
Dirtiness level 1
+ 20
+1 fan tap (max - Hi)
e-ion ON
Dirtiness level 2
+ 40
No change
Me -
Me
+2 fan tap (max - Hi)
o
Indoor Fan Control
During any operation mode combines with Patrol operation, fan speed follows respective operation mode.
During Patrol individual operation if e-ion starts, only Auto Fan Speed and no Powerful operation is
allowed. Even if “Fan Speed” button is pressed, no signal is sent to air conditioner, and no change on
LCD display.
During Patrol individual operation if e-ion stops, Indoor Fan stop operation.
Air Dirtine
ss Value
Dirty
Moderate
Clean
Содержание CS-S12MKQ
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 15: ...15 4 2 3 CU S18MKQ CU S24MKQ ...
Страница 16: ...16 4 2 4 CU S28MKQ ...
Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9MKQ CU S9MKQ CS S12MKQ CU S12MKQ ...
Страница 18: ...18 5 2 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ CS S28MKQ CU S28MKQ ...
Страница 19: ...19 6 Block Diagram 6 1 CS S9MKQ CU S9MKQ ...
Страница 20: ...20 6 2 CS S12MKQ CU S12MKQ ...
Страница 21: ...21 6 3 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ ...
Страница 22: ...22 6 4 CS S28MKQ CU S28MKQ ...
Страница 33: ...33 8 2 Outdoor Unit 8 2 1 CU S9MKQ ...
Страница 37: ...37 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 38: ...38 9 1 2 Power Printed Circuit Board 9 1 2 1 CS S9MK CS S12MK 9 1 2 2 CS S18MK CS S24MK ...
Страница 40: ...40 9 1 6 Comparator Printed Circuit Board 9 1 7 Human Activity Sensor Printed Circuit Board ...
Страница 41: ...41 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9MK ...
Страница 42: ...42 9 2 1 2 CU S12MK ...
Страница 43: ...43 9 2 1 3 CU S18MK CU S24MK ...
Страница 44: ...44 9 2 1 4 CU S28MK ...
Страница 45: ...45 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9MKQ ...
Страница 115: ...115 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 116: ...116 16 1 1 4 To remove control board Figure 7 16 1 1 5 To remove cross flow fan and indoor fan motor Figure 8 Figure 9 ...
Страница 117: ...117 Figure 10 Figure 11 ...
Страница 119: ...119 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 121: ...121 Figure 21 Figure 22 Figure 23 ...