Airflow direction (Horizontal, Vertical) Control
o
During any operation mode combines with Patrol operation, airflow direction follows respective operation
mode.
o
During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is
pressed, no signal is sent to air conditioner, and no change on LCD display.
o
During Patrol individual operation if e-ion stops, Airflow direction louver closed.
•
Indicator
o
When Patrol is selected, patrol sensor indicator ON.
No Description
BLUE
ORANGE
RED
E-ION
1 When patrol function is not selected
OFF
OFF
OFF
-
2 During gas sensor error detection control
OFF
OFF
Blinking
OFF
3 During stop
OFF
OFF
OFF
OFF
4 2 minutes gas sensor initial stabilization time (Level 0)
ON
OFF
OFF
OFF
a. Dirtiness level 0*
ON
OFF
OFF
OFF
a. Dirtiness level 1
OFF
ON
OFF
OFF
b. Dirtiness level 1*
OFF
ON
OFF
ON
5
During operation
During patrol
c. Dirtiness level 2
OFF
OFF
ON
ON
•
Remote Control Receiving Sound
o
Normal
Operation
Î
Patrol Mode
: Beep
o
Patrol
Mode
Î
Stop
: Long Beep
o
Patrol
Mode
Î
Normal Operation
: Beep
o
Stop
Î
Patrol
: Beep
•
Timer
Control
o
When ON timer activates when unit stops, previous operation resumes and restored last saved Patrol
operation status.
o
When ON timer activates during any operation, no change and carry on current operation.
o
When OFF timer activates during any operation, all operation stops and the latest Patrol operation status is
saved.
•
Power Failure Control
o
During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual operation
resumes immediately.
o
During combination operation, if power failure occurs, after power resumes combination operation resume
immediately.
Содержание CS-S12MKQ
Страница 11: ...11 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control ...
Страница 15: ...15 4 2 3 CU S18MKQ CU S24MKQ ...
Страница 16: ...16 4 2 4 CU S28MKQ ...
Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9MKQ CU S9MKQ CS S12MKQ CU S12MKQ ...
Страница 18: ...18 5 2 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ CS S28MKQ CU S28MKQ ...
Страница 19: ...19 6 Block Diagram 6 1 CS S9MKQ CU S9MKQ ...
Страница 20: ...20 6 2 CS S12MKQ CU S12MKQ ...
Страница 21: ...21 6 3 CS S18MKQ CU S18MKQ CS S24MKQ CU S24MKQ ...
Страница 22: ...22 6 4 CS S28MKQ CU S28MKQ ...
Страница 33: ...33 8 2 Outdoor Unit 8 2 1 CU S9MKQ ...
Страница 37: ...37 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board ...
Страница 38: ...38 9 1 2 Power Printed Circuit Board 9 1 2 1 CS S9MK CS S12MK 9 1 2 2 CS S18MK CS S24MK ...
Страница 40: ...40 9 1 6 Comparator Printed Circuit Board 9 1 7 Human Activity Sensor Printed Circuit Board ...
Страница 41: ...41 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9MK ...
Страница 42: ...42 9 2 1 2 CU S12MK ...
Страница 43: ...43 9 2 1 3 CU S18MK CU S24MK ...
Страница 44: ...44 9 2 1 4 CU S28MK ...
Страница 45: ...45 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9MKQ ...
Страница 115: ...115 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 116: ...116 16 1 1 4 To remove control board Figure 7 16 1 1 5 To remove cross flow fan and indoor fan motor Figure 8 Figure 9 ...
Страница 117: ...117 Figure 10 Figure 11 ...
Страница 119: ...119 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 121: ...121 Figure 21 Figure 22 Figure 23 ...