35
Tape
Connection
cable
Terminal
Board
Control
Board
Earth wire
longer than
others
AC wires
for safety
reason
Holder
Indoor & outdoor
connection cable
Outdoor unit
a
b
d
c
Recommended
length (mm)
Recommended
length (mm)
a b c d
50 40 35 60
4
4. Secure the connection cable onto the control board with the holder.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires for safety reason.
12.2.4.3 Wire
Stripping,
Connecting Requirement
Wire stripping
5 mm
or more
Conductor
over inserted
No loose strand
when inserted
Indoor/outdoor
connection
terminal board
10
±
1
mm
Conductor
fully inserted
Conductor not
fully inserted
(gap between wires)
ACCEPT
PROHIBITED
PROHIBITED
WARNING
RISK OF FIRE
JOINING OF WIRES MAY
CAUSE O
VERHEATING
AND FIRE.
Use complete
wire without joining.
Use approved
socket and plug
with earth pin.
Wire connection
in this area must
follow to national
wiring rules.
Do not joint wires
OR
OR
OR
In case of indoor power supply
In case of outdoor power supply
OR
OR
OR