![Panasonic CS-E24DKE Скачать руководство пользователя страница 78](http://html.mh-extra.com/html/panasonic/cs-e24dke/cs-e24dke_service-manual_256896078.webp)
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
6.75
5.11
2.21
6.30
4.90
2.37
5.86
4.71
2.54
5.33
4.48
2.74
19.0°C
6.80
2.41
19.5°C
7.41
5.35
2.25
6.92
5.14
2.42
6.44
4.95
2.59
5.85
4.71
2.79
22.0°C
8.07
5.55
2.29
7.54
5.34
2.46
7.02
5.15
2.63
6.38
4.91
2.84
TC - Total Cooling Capacity (kW)
Indoor 27°C/19°C
SHC - Sensible Heat Capacity (kW)
Outdoor 35°C/24°C
IP - Input Power (kW)
78
CS-E24DKE CU-E24DKE
Содержание CS-E24DKE
Страница 9: ...4 Dimensions 4 1 Indoor Unit Remote Control 9 CS E24DKE CU E24DKE ...
Страница 10: ...4 2 Outdoor Unit 10 CS E24DKE CU E24DKE ...
Страница 11: ...5 Refrigeration Cycle Diagram 11 CS E24DKE CU E24DKE ...
Страница 12: ...6 Block Diagram 12 CS E24DKE CU E24DKE ...
Страница 13: ...7 Wiring Diagram 13 CS E24DKE CU E24DKE ...
Страница 19: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Dry 2 Heating 19 CS E24DKE CU E24DKE ...
Страница 62: ...3 For the embedded piping This can be used for left rear piping left bottom piping also 62 CS E24DKE CU E24DKE ...
Страница 77: ...13 Technical Data 77 CS E24DKE CU E24DKE ...
Страница 89: ...89 CS E24DKE CU E24DKE ...
Страница 91: ...18 3 Remote Control 91 CS E24DKE CU E24DKE ...
Страница 92: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 92 CS E24DKE CU E24DKE ...
Страница 93: ...18 5 Print Pattern Outdoor Unit Printed Circuit Board 93 CS E24DKE CU E24DKE PHAAM Printed in Malaysia ...
Страница 94: ......