2. Auto Fan Speed
Note:
a. UP:
•
If move from Lo, the fan speed will be shifted to Maximum 1300 rpm (E24DK).
•
If move from Maximum, the fan speed no change.
•
In up zone, 10 rpm is added for every 10s until Maximum 1300 rpm (E24DK).
b. DOWN:
•
The fan speed will be decreased one step every 10 sec. until Minimum 1100 rpm.
c.
Current Output Fixed:
•
Maintain at present fan speed.
d. Instantaneous Maximum:
•
Fan speed will be increased to maximum auto fan speed.
e. Temperature in ( ) is for Powerful Mode operation.
8.2.3.2. Intake Air Temperature Control
Compressor will operate at freq 67 Hz if either one of the below conditions occur:
1. When the indoor intake air temperature is above 10°C and remote control setting fan speed is lower Me-.
2. When the indoor intake air temperature is 30°C or above.
37
CS-E24DKE CU-E24DKE
Содержание CS-E24DKE
Страница 9: ...4 Dimensions 4 1 Indoor Unit Remote Control 9 CS E24DKE CU E24DKE ...
Страница 10: ...4 2 Outdoor Unit 10 CS E24DKE CU E24DKE ...
Страница 11: ...5 Refrigeration Cycle Diagram 11 CS E24DKE CU E24DKE ...
Страница 12: ...6 Block Diagram 12 CS E24DKE CU E24DKE ...
Страница 13: ...7 Wiring Diagram 13 CS E24DKE CU E24DKE ...
Страница 19: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Dry 2 Heating 19 CS E24DKE CU E24DKE ...
Страница 62: ...3 For the embedded piping This can be used for left rear piping left bottom piping also 62 CS E24DKE CU E24DKE ...
Страница 77: ...13 Technical Data 77 CS E24DKE CU E24DKE ...
Страница 89: ...89 CS E24DKE CU E24DKE ...
Страница 91: ...18 3 Remote Control 91 CS E24DKE CU E24DKE ...
Страница 92: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 92 CS E24DKE CU E24DKE ...
Страница 93: ...18 5 Print Pattern Outdoor Unit Printed Circuit Board 93 CS E24DKE CU E24DKE PHAAM Printed in Malaysia ...
Страница 94: ......