8.2.1.4. IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95°C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 30.0 ± 5.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minute.
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
8.2.1.5. Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor top temperature. The changes of frequency are as
below figure.
8.2.1.6. Low Pressure Prevention Control (Gas Leakage Detection)
1. When the conditions listed in below table occur, the compressor stops and restarts after three minutes.
2. If this phenomenon is continuously occurring for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
Conditions
E24DK
Cooling/Soft Dry
Heating
1. Compressor frequency (Hz)
74
68
2. Outdoor total running current (A)
3.25
3.25
3. Indoor heat exchanger temperature (°C)
20
25
Note: Conditions 1 and 2 needed to be happened continuously for 5 minutes.
32
CS-E24DKE CU-E24DKE
Содержание CS-E24DKE
Страница 9: ...4 Dimensions 4 1 Indoor Unit Remote Control 9 CS E24DKE CU E24DKE ...
Страница 10: ...4 2 Outdoor Unit 10 CS E24DKE CU E24DKE ...
Страница 11: ...5 Refrigeration Cycle Diagram 11 CS E24DKE CU E24DKE ...
Страница 12: ...6 Block Diagram 12 CS E24DKE CU E24DKE ...
Страница 13: ...7 Wiring Diagram 13 CS E24DKE CU E24DKE ...
Страница 19: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Dry 2 Heating 19 CS E24DKE CU E24DKE ...
Страница 62: ...3 For the embedded piping This can be used for left rear piping left bottom piping also 62 CS E24DKE CU E24DKE ...
Страница 77: ...13 Technical Data 77 CS E24DKE CU E24DKE ...
Страница 89: ...89 CS E24DKE CU E24DKE ...
Страница 91: ...18 3 Remote Control 91 CS E24DKE CU E24DKE ...
Страница 92: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 92 CS E24DKE CU E24DKE ...
Страница 93: ...18 5 Print Pattern Outdoor Unit Printed Circuit Board 93 CS E24DKE CU E24DKE PHAAM Printed in Malaysia ...
Страница 94: ......