D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON
1
→
2
→
3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
→
5
→
4
←→
5
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
Odor Status
1
2
3
4
5
4
5
4.5.4...
1
Status Shift
according to COMP
ON
OFF
ON
Status Shift
according
Cooling
zone
40
50
—
20
90
20
90
.......
to time (s)
Dry zone
ON
Fan Speed
Cooling
zone
OFF
SLo
Auto Fan Speed
SLo
OFF
SLo
OFF
.......
Dry zone
OFF
SLo
OFF
8.1.8. Outdoor Fan Motor Operation
Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation.
22
CS-E24DKE CU-E24DKE
Содержание CS-E24DKE
Страница 9: ...4 Dimensions 4 1 Indoor Unit Remote Control 9 CS E24DKE CU E24DKE ...
Страница 10: ...4 2 Outdoor Unit 10 CS E24DKE CU E24DKE ...
Страница 11: ...5 Refrigeration Cycle Diagram 11 CS E24DKE CU E24DKE ...
Страница 12: ...6 Block Diagram 12 CS E24DKE CU E24DKE ...
Страница 13: ...7 Wiring Diagram 13 CS E24DKE CU E24DKE ...
Страница 19: ...B Indoor Fan Control i Indoor fan control operation outline 1 Cooling Dry 2 Heating 19 CS E24DKE CU E24DKE ...
Страница 62: ...3 For the embedded piping This can be used for left rear piping left bottom piping also 62 CS E24DKE CU E24DKE ...
Страница 77: ...13 Technical Data 77 CS E24DKE CU E24DKE ...
Страница 89: ...89 CS E24DKE CU E24DKE ...
Страница 91: ...18 3 Remote Control 91 CS E24DKE CU E24DKE ...
Страница 92: ...18 4 Print Pattern Indoor Unit Printed Circuit Board 92 CS E24DKE CU E24DKE ...
Страница 93: ...18 5 Print Pattern Outdoor Unit Printed Circuit Board 93 CS E24DKE CU E24DKE PHAAM Printed in Malaysia ...
Страница 94: ......