10. Decommissioning

• Before carrying out this procedure, it is 

essential that the technician is completely 

familiar with the equipment and all its details.

• It is recommended good practice that all 

refrigerants are recovered safely.

• Prior to the task being carried out, an oil 

and refrigerant sample shall be taken in 

case analysis is required prior to re-use of 

reclaimed refrigerant.

• It is essential that electrical power is 

available before the task is commenced.

a)  Become familiar with the equipment and 

its operation.

b) Isolate system electrically.

c) Before attempting the procedure ensure 

that:

• mechanical handling equipment is 

available, if required, for handling 

refrigerant cylinders; 

• all personal protective equipment is 

available and being used correctly;

• the recovery process is supervised at all 

times by a competent person;

• recovery equipment and cylinders conform 

to the appropriate standards.

d)  Pump down refrigerant system, if 

possible.

e)  If a vacuum is not possible, make a 

manifold so that refrigerant can be 

removed from various parts of the system.

f)  Make sure that cylinder is situated on the 

scales before recovery takes place.

g)  Start the recovery machine and operate 

in accordance with manufacturer’s 

instructions.

h)  Do not over fill cylinders. (No more than 

80 % volume liquid charge).

i)  Do not exceed the maximum working 

pressure of the cylinder, even temporarily.

j)  When the cylinders have been filled 

correctly and the process completed, make 

sure that the cylinders and the equipment 

are removed from site promptly and all 

isolation valves on the equipment are 

closed off.

k)  Recovered refrigerant shall not be 

charged into another refrigeration system 

unless it has been cleaned and checked.

• Electrostatic charge may accumulate and 

create a hazardous condition when charging 

or discharging the refrigerant.

To avoid fire or explosion, dissipate static 

electricity during transfer by grounding and 

bonding containers and equipment before 

charging/discharging.

11. Labelling

• Equipment shall be labelled stating that it 

has been de-commissioned and emptied of 

refrigerant.

• The label shall be dated and signed.

• Ensure that there are labels on the 

equipment stating the equipment contains 

flammable refrigerant.

12. Recovery

• When removing refrigerant from a system, 

either for servicing or decommissioning, 

it is recommended good practice that all 

refrigerants are removed safely.

• When transferring refrigerant into cylinders, 

ensure that only appropriate refrigerant 

recovery cylinders are employed.

• Ensure that the correct number of cylinders 

for holding the total system charge are 

available.

• All cylinders to be used are designated for 

the recovered refrigerant and labelled for 

that refrigerant (i.e. special cylinders for the 

recovery of refrigerant).

• Cylinders shall be complete with pressure 

relief valve and associated shut-off valves in 

good working order.

• Recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

• The recovery equipment shall be in good 

working order with a set of instructions 

concerning the equipment that is at hand 

and shall be suitable for the recovery of 

flammable refrigerants.

• In addition, a set of calibrated weighing 

scales shall be available and in good 

working order.

• Hoses shall be complete with leak-free 

disconnect couplings and in good condition.

• Before using the recovery machine, check 

that it is in satisfactory working order, has 

been properly maintained and that any 

associated electrical components are 

sealed to prevent ignition in the event of a 

refrigerant release.

Consult manufacturer if in doubt.

• The recovered refrigerant shall be returned 

to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste 

Transfer Note arranged.

• Do not mix refrigerants in recovery units and 

especially not in cylinders.

• If compressors or compressor oils are to 

be removed, ensure that they have been 

evacuated to an acceptable level to make 

certain that flammable refrigerant does not 

remain within the lubricant.

• The evacuation process shall be carried 

out prior to returning the compressor to the 

suppliers.

• Only electric heating to the compressor 

body shall be employed to accelerate this 

process.

• When oil is drained from a system, it shall be 

carried out safely.

Содержание CS/CU-HU12AKY Series

Страница 1: ...then request the customer keep them for future reference Remove the remote control packed with the indoor unit Air conditioner Operating Installation Instructions Images are for Illustration purpose o...

Страница 2: ...INVERTER leverages ECONAVI sensor data and varies compressor rotation speed This helps to optimize cooling operation and reduces wasteful cooling nanoe G nanoeX Purifies the air down to the smallest p...

Страница 3: ...y FAN DRY 2 1 3 7m Accessories Remote control AAA or R03 batteries 2 Remote control holder Screws for remote control holder 2 Ag Clean PM 0 1 Filter Safety precautions 4 9 How to use 10 11 To learn mo...

Страница 4: ...e internal parts repair install remove and reinstall the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any...

Страница 5: ...the same as conventional refrigerant R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especi...

Страница 6: ...accredited assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as...

Страница 7: ...where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being co...

Страница 8: ...nd during the brazing process 8 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important...

Страница 9: ...hat it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Rec...

Страница 10: ...AU18AKYF Model FAN To operate Air Con in Fan Only mode Indoor unit temp display will show set temp for AUTO COOL DRY mode and room temp for FAN mode Only indoor unit fan operates as per remote setting...

Страница 11: ...operation stops automatically after 1 hour JETSTREAM To set the timer To turn ON and OFF the unit at a preset time To enjoy freshness and cleaner environment This is a combination operation together...

Страница 12: ...g low activity to maximise energy saving Mode Human Low activity COOL Set temperature ECONAVI take advantage of the human nature that human being takes time to feel the temperature rise during low act...

Страница 13: ...native to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug Remove the remote control batteries nanoe G Generator For better efficiency...

Страница 14: ...and some alpha numeric codes appear on IDU display Unit s Wi Fi connection with the router is activated Wi Fi LED stays ON during unit turn OFF Check unit s Wi Fi connection with router Wi Fi LED coun...

Страница 15: ...Note 15 English Troubleshooting...

Страница 16: ...condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not...

Страница 17: ...checking for gas leaks and secure with vinyl tape Vinyl tape Insulation of piping connections Remote control holder Remote control holder fixing screws Remote control Attaching the remote control hold...

Страница 18: ...ount the installation plate on the wall with 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts Always mount the installation plate horizontally b...

Страница 19: ...left piping Right Rear piping Cover for piping How to keep the cover In case of the cover is cut keep the cover at the rear of chassis as shown in the illustration for future reinstallation Left right...

Страница 20: ...ction cable Gas side piping Liquid side piping Drain hose Insert the connection cable This can be used for left rear piping and bottom piping also How to pull the piping and drain hose out in case of...

Страница 21: ...oprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP flexible cord type designation IS 694 or 60245 IEC 57 or heavier cord Bind all the indoor and outdoor connection cable with...

Страница 22: ...n this area must follow to national wiring rules Do not joint wires Wire stripping No loose strand when inserted 10 1 mm Conductor fully inserted ACCEPT Conductor over inserted PROHIBITED Conductor no...

Страница 23: ...orque wrench Spanner or Wrench Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut locate at valve onto the copper pipe Align cen...

Страница 24: ...unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP flexible cord type designation IS 694 or 60245 IEC 57 or heavier cord Do n...

Страница 25: ...as shown in the illustration 3 Then remove the 2 1 5HP or 4 2 0 2 5HP mounting screws 4 Pull the lower section of the front grille towards you to remove the front grille The below operations will be p...

Страница 26: ...aterial with a new one Heat insulating material is required for both liquid side and gas side piping Most Important Process Purpose To make the oil refrigerant mix together They are in separated condi...

Страница 27: ...or dwelling or room must be made by brazing orwelding Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a buidling or dwelling or room Flare connection ma...

Страница 28: ...b 17 C for Half Load 50 For Full Load QUIET CLEAN Open the Front Panel by lifting Intake Grille Follow the below Instructions 4 Air Swing Horizontal Airflow Set vane position to be AUTO 5 Fan speed M...

Страница 29: ...door Unit Control button while holding the indoor unit button Step b Within 5 second press once the Remote Step c After hearing a beep sound from the Indoor Unit immediately release the Auto OFF ON bu...

Страница 30: ...ed above carries warranty for 3 years from the date of purchase Product ROOM AIR CONDITIONER Panasonic Life Solutions India Pvt Ltd Model No ODU SI No IDU SI No Customer Name Address Tel No Date of Pu...

Страница 31: ...ject or living creature eg Rat lizard insect ants etc inside the Product unit f Use of harmful chemicals Improper heat load Usage of unit in an abnormally corrosive alkaline acidic atmosphere g Any ch...

Страница 32: ...m in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should b...

Отзывы: