Panasonic CS/CU-HU12AKY Series Скачать руководство пользователя страница 24

24

OPEN

CLOSE

Gas side

Liquid side

Outdoor unit

Two-way valve

Three-way valve

Indoor unit

Vacuum pump 

Close

Close

If gauge needle does not move from 0 cmHg (0 MPa) to –76 cmHg (–0.1 MPa), in step 

 above take the following measure:

- If the leak stops when the piping connections are tightened further, continue working from step 

.

- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.

4.   Close the Low side valve of the charging set and turn 
      off the vacuum pump. Make sure that the needle in the 
      gauge does not move after approximately 

fi

ve minutes. 

Note : BE SURE TO TAKE THIS PROCEDURE IN 
           ORDER TO AVOID REFRIGERANT GAS 
           LEAKAGE.

5.   Disconnect the charging hose from the vacuum pump 
      and from the service port of the 3-way valve. 
6.   Tighten the service port caps of the 3-way valve at a 
      torque of 18 N•m with a torque wrench.
7.   Remove the valve caps of both of the 2-way valve 
      and 3-way valve. Position both of the valves to 
      “OPEN” using a hexagonal wrench (4 mm).
8.   Mount valve caps onto the 2-way valve and the 
      3-way valve.

•    Be sure to check for gas leakage.     

 WARNING

This equipment must be properly earthed.

Earth wire shall be Yellow/Green (Y/G) in  colour and longer than other
AC wires for safety reason.

1.   Remove the control board cover from the unit by loosening the screw.
2.   

Connection cable 

 between indoor unit and outdoor unit shall be

      approved polychloroprene sheathed 4 x 1.0 mm2 (1.5 ~ 1.8HP),
      4 x 1.5 mm2 (2.0HP) or 4 x 2.5mm2 (2.5HP) 

fl

exible cord, type designation

      IS 694 or 60245 IEC 57 or heavier cord. Do not use joint connection cable.
      Replace the wire if the existing wire (from concealed wiring, or otherwise)
      is too short.

Terminals on the outdoor unit

1

2

3

Colour of wires

Terminals on the indoor unit

1

2

3

3.   Secure the cable onto the control board with the holder.
4.   Attach the control board cover back to the original position with screw.
5.   For wire stripping and connection requirement, refer to instruction      of 
      indoor unit.

Holder

Indoor unit

Indoor & outdoor connection cable 

Earth wire 
longer than 
others 
AC wires 
for safety 
reason

Terminal Board

Connect the cable to the Outdoor Unit

Piping Insulation

1.    Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram.
       Please wrap the insulated piping end to prevent water from going inside the piping.
2.    If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using 
       POLY-E FOAM with thickness 6 mm or above.

Installation of *Ag Clean

+

 & *PM 0.1 Filter

Open the front panel and remove air 

fi

lters.

Take out Ag Clean+ & PM 0.1 filter placed behind the installation holder.
Put the Ag Clean+ or PM 0.1 filter into place as shown in illustration at right.

(i)  There are slots at backside of Air Filter as shown.

(ii)  Put the Ag Clean+ or PM 0.1 filter in the slots as shown.

(iii) Put the Air Filter back in position.

*Filters applicable for selected models only.

Air  Filter

Ag Clean/

PM 0.1 Filter

Slots

Front

Panel

Ag Clean/

PM 0.1 Filter

Содержание CS/CU-HU12AKY Series

Страница 1: ...then request the customer keep them for future reference Remove the remote control packed with the indoor unit Air conditioner Operating Installation Instructions Images are for Illustration purpose o...

Страница 2: ...INVERTER leverages ECONAVI sensor data and varies compressor rotation speed This helps to optimize cooling operation and reduces wasteful cooling nanoe G nanoeX Purifies the air down to the smallest p...

Страница 3: ...y FAN DRY 2 1 3 7m Accessories Remote control AAA or R03 batteries 2 Remote control holder Screws for remote control holder 2 Ag Clean PM 0 1 Filter Safety precautions 4 9 How to use 10 11 To learn mo...

Страница 4: ...e internal parts repair install remove and reinstall the unit Improper installation and handling will cause leakage electric shock or fire Confirm with authorised dealer or specialist on usage of any...

Страница 5: ...the same as conventional refrigerant R410A R22 models Since the working pressure is higher than that of refrigerant R22 models some of the piping and installation and service tools are special Especi...

Страница 6: ...accredited assessment authority which authorizes their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as...

Страница 7: ...where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being co...

Страница 8: ...nd during the brazing process 8 Removal and evacuation When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However it is important...

Страница 9: ...hat it has been de commissioned and emptied of refrigerant The label shall be dated and signed Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant 12 Rec...

Страница 10: ...AU18AKYF Model FAN To operate Air Con in Fan Only mode Indoor unit temp display will show set temp for AUTO COOL DRY mode and room temp for FAN mode Only indoor unit fan operates as per remote setting...

Страница 11: ...operation stops automatically after 1 hour JETSTREAM To set the timer To turn ON and OFF the unit at a preset time To enjoy freshness and cleaner environment This is a combination operation together...

Страница 12: ...g low activity to maximise energy saving Mode Human Low activity COOL Set temperature ECONAVI take advantage of the human nature that human being takes time to feel the temperature rise during low act...

Страница 13: ...native to remove moisture left in the internal parts thoroughly to prevent mould growth Turn off the power supply and unplug Remove the remote control batteries nanoe G Generator For better efficiency...

Страница 14: ...and some alpha numeric codes appear on IDU display Unit s Wi Fi connection with the router is activated Wi Fi LED stays ON during unit turn OFF Check unit s Wi Fi connection with router Wi Fi LED coun...

Страница 15: ...Note 15 English Troubleshooting...

Страница 16: ...condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do not...

Страница 17: ...checking for gas leaks and secure with vinyl tape Vinyl tape Insulation of piping connections Remote control holder Remote control holder fixing screws Remote control Attaching the remote control hold...

Страница 18: ...ount the installation plate on the wall with 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts Always mount the installation plate horizontally b...

Страница 19: ...left piping Right Rear piping Cover for piping How to keep the cover In case of the cover is cut keep the cover at the rear of chassis as shown in the illustration for future reinstallation Left right...

Страница 20: ...ction cable Gas side piping Liquid side piping Drain hose Insert the connection cable This can be used for left rear piping and bottom piping also How to pull the piping and drain hose out in case of...

Страница 21: ...oprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP flexible cord type designation IS 694 or 60245 IEC 57 or heavier cord Bind all the indoor and outdoor connection cable with...

Страница 22: ...n this area must follow to national wiring rules Do not joint wires Wire stripping No loose strand when inserted 10 1 mm Conductor fully inserted ACCEPT Conductor over inserted PROHIBITED Conductor no...

Страница 23: ...orque wrench Spanner or Wrench Decide piping length and then cut by using pipe cutter Remove burrs from cut edge Make flare after inserting the flare nut locate at valve onto the copper pipe Align cen...

Страница 24: ...unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1 0 mm2 1 5 1 8HP 4 x 1 5 mm2 2 0HP or 4 x 2 5mm2 2 5HP flexible cord type designation IS 694 or 60245 IEC 57 or heavier cord Do n...

Страница 25: ...as shown in the illustration 3 Then remove the 2 1 5HP or 4 2 0 2 5HP mounting screws 4 Pull the lower section of the front grille towards you to remove the front grille The below operations will be p...

Страница 26: ...aterial with a new one Heat insulating material is required for both liquid side and gas side piping Most Important Process Purpose To make the oil refrigerant mix together They are in separated condi...

Страница 27: ...or dwelling or room must be made by brazing orwelding Joint connection of indoor unit by flaring method can only be made at outdoor or at outside of a buidling or dwelling or room Flare connection ma...

Страница 28: ...b 17 C for Half Load 50 For Full Load QUIET CLEAN Open the Front Panel by lifting Intake Grille Follow the below Instructions 4 Air Swing Horizontal Airflow Set vane position to be AUTO 5 Fan speed M...

Страница 29: ...door Unit Control button while holding the indoor unit button Step b Within 5 second press once the Remote Step c After hearing a beep sound from the Indoor Unit immediately release the Auto OFF ON bu...

Страница 30: ...ed above carries warranty for 3 years from the date of purchase Product ROOM AIR CONDITIONER Panasonic Life Solutions India Pvt Ltd Model No ODU SI No IDU SI No Customer Name Address Tel No Date of Pu...

Страница 31: ...ject or living creature eg Rat lizard insect ants etc inside the Product unit f Use of harmful chemicals Improper heat load Usage of unit in an abnormally corrosive alkaline acidic atmosphere g Any ch...

Страница 32: ...m in corporate sustainability panasonic india i recycle program html S No 1 All electrical and electronic products are required to be handed over only to the Authorized recycler 2 The product should b...

Отзывы: