29
Rear view for left piping installation
Drain cap
Drain hose
•
How to pull the piping and drain hose out, in case
of the embeddedpiping
.
PVC tube
for drain
hose
Indoor unit
72 mm
Piping
Cable
Apply putty or
caulking material
to seal the wall
opening.
Connection
cable
Piping
More
tha
n
470 m
m
Mo
re t
han
115
0 m
m
PVC tube (VP-65) for piping
and connection cable
PVC tubefor drain hose (VP-30)
PVC tube for
drain hose (VP-20)
Mor
e
than 700
mm
•
In case of left piping how to insert
the connection cable and drain hose.
Drain hose
from main unit
Cable
Drain
hose
Piping
(For the right piping, follow the
same procedure)
Sleeve for piping hole
Drain hose
Piping
Connection cable
More than 1150 mm
Replace the d rain hose
45°
11.2.4 Connect the Cable to the Indoor Unit
The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.
1 Install the indoor unit on the installing holder that mounted on the wall.
2 Open the front panel and grille door by loosening the screw.
3 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o
Connect the approved polychloroprene sheathed
power supply cord
3 × 1.5 mm
2
, type designation
245 IEC 57 or heavier cord to the terminal board, and connect the other end of the cable to Isolating
Devices (Disconnecting means).
o
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done by using approved socket and plug with earth pin rated 15/16A. Wiring work to
both socket and plug must follow to national wiring standard.
4 Bind all the power supply cord lead wire with tape and route the power supply cord via the left escapement.
5
Connection cable
between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 ×
1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.
6 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the right
escapement.