41
13.1.4 Compressor
Overheating Prevention Control
•
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
•
If compressor discharge temperature exceeds 103°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. (“F97” is indicated.)
103°C
88°C
Comp. Discharge temperature
Compressor = OFF
99°C
87°C
Compressor Frequency
Reduce
96°C
86°C
Compressor Frequency
Maintain
Free
13.1.5 Low Pressure Prevention Control (Gas Leakage Detection)
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.6A and 1.15A.
o
During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4°C.
o
During Heating operations :
Indoor piping temperature - indoor suction is under 5°C.
•
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
Stop
operation.
Timer LED blinks and “F91” indicated.
13.1.6 Low
Frequency
Protection Control 1
•
When the compressor operate at frequency lower than 24 Hz continued for 240 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
13.1.7 Low
Frequency
Protection Control 2
•
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°C)
T < 14 or T
≥
30
T < 14 or T
≥
28
Outdoor air (°C)
T < 13 or T
≥
38
T < 4 or T
≥
24
Indoor heat exchanger (°C)
T < 30
T < 0