- When the compressor is stopped by Power Switch, Remote
Control or there is a power failure, it restarts after 3 minutes when
the Power Switch, Remote Control is turned ON or the power
supply is resumed.
- When the setting temperature is reached during cooling operation,
the compressor stops and it will not start for 3 minutes.
7 minutes Time Saved Control
- The compressor will start automatically if it has stopped for 7
minutes even if the room temperature is below the compressor ON
temperature.
Anti-Freezing Control
- If the temperature of the indoor heat exchanger falls continuously
below 2°C for 4 minutes, the compressor turns off to protect the
indoor heat exchanger from freezing. The fan speed setting
remains the same. /
- Compressor recommences when the indoor heat exchanger
temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is
valid
for Cooling Operation.
Automatic Fan Speed Mode
10
PDF created with pdfFactory Pro trial version
Содержание CS-A281KR
Страница 6: ...6 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 8: ...7 Wiring Diagram 8 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 17: ...Heating Operating Time Diagram 17 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 34: ...34 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 66: ...66 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 67: ...15 Exploded View 67 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 68: ...16 Replacement Parts List Model CS A281KR 68 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 71: ...18 Replacement Parts List Model CU A281KR 71 PDF created with pdfFactory Pro trial version www pdffactory com ...
Страница 76: ...How to use electronic circuit diagram 76 PDF created with pdfFactory Pro trial version www pdffactory com ...