10.2
What to DO If an Error Occurs
(For Each Communication Mode)
10-5
10.2.3 When Using General-purpose Communication Function
What to do if an error occurs
Situation
Contents to check
Confirmation method
Is a communication cassette attached?
Check if the communication block is
installed firmly.
Are wirings correct?
Check the wirings again.
Isn't there any problem in environments such as
noise?
Check the shielding.
Communication is not
possible.
(For the serial
communication unit, the
ERROR LED turns on.)
Is the communication mode set correctly?
・
Check the configuration (COM
settings) of the CPU with built-in SCU
or the serial communication unit.
・
Check the communication
parameters with PMGET instruction.
(Note)
Transmission is not
possible.
(For the serial
communication unit, the
ERROR LED turns on.)
Does an operation error occur when GPSEND
instruction is executed?
Isn't transmission prohibited by CTS signal (Y14
or Y16) when using a communication cassette
with RS-232C (5-wire type)?
Review the program.
Is the setting for the communication conditions
the same as the one for the device
communicated?
Transmission is not
possible.
Is the setting of the method for detecting
“reception done” the same as the one for the
device communicated?
・
Check the configuration (COM
settings) of the CPU with built-in SCU
or the serial communication unit.
・
Check the communication
parameters with PMGET instruction.
(Note)
Isn't reception error occurring?
Isn't the reception buffer FULL error occurring?
If the error occurs, the operation cannot be
restarted without performing channel reset.
Reception is not possible.
(For the serial
communication unit, the
ERROR LED turns on.)
Isn't the operation mode set to a mode other
than general-purpose communication with
PMSET instruction?
・
Check the communication
parameters and operation status
monitor information with PMGET
instruction. (Note)
(Note) For checking communication parameters with PMGET instruction, the CPU should be set in the RUN mode.
Set "Mode selection when self-diagnostic error occurs - A unit error occurred." to "Continue operation" in the
CPU configuration.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Содержание AFP7CPS4E
Страница 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 10: ...Table of Contents viii Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 21: ...2 Names and Functions of Parts Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 24: ...Names and Functions of Parts 2 4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 25: ...3 Wiring the COM Port Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 45: ...3 I O Allocation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 52: ...I O Allocation 4 8 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 57: ...6 PLC Link Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 97: ...9 General Purpose Communication Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 114: ...General Purpose Communication 9 18 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 115: ...4 Troubleshooting Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 124: ...Troubleshooting 10 10 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Страница 125: ...11 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...