SETTING DATA CLEAR(Parameter P42)
The set data can be changed to the factory setting data in a batch.
Also, the data of the monitor mode n10(No. of door switching) can be cleared.
Data setting
value
Details
Data value that indicates normal state.
0
1
Changes all data to the factory settings.
Note) Press SET button when the display value changes to "1" or "2" , then the data
will be cleared. The set data will return to "0" automatically.
2
3
Data of the monitor mode n10(
No. of door switching
)
is cleared to "0". (Other data will not be changed.)
INPUT SIGNAL LOGIC SETTING (Parameter P43)
It can be selected to detect the input signal by "A contact input" or "B contact input".
Note) The logics of the OPEN signal and CLOSE signal cannot be changed. "A contact
input" is a fixed value.
Data setting range
0
to
31
Signal
name
CLOSE
speed change
OPEN
speed change
Safety
sensor
CLOSE
Arrival
OPEN
Arrival
Terminal No.
7
5
4
3
bit
4
2
1
0
Setting value
0/1
0/1
0/1
0/1
Additional value
16
8
4
2
1
䃂
Setting value
䊶
A contact input="0": When SW(switch) signal is closed (terminal level is "L"), ON is detected.
䊶
B contact input="1": When SW(switch) signal is opened (terminal level is "H"), ON is detected.
䃂
Setting method
䊶
Convert 0 to 4 bits to decimal numbers and input.
䊶
Input the total value of the setting value
h
the additional value for the setting data.
(Example) When CLOSE speed change signal (4bits) and OPEN speed
change signal (3bits) is B contact input.
Setting data=(1
h
16)
ˇ
(1
h
8)
ˇ
(0
h
4)
ˇ
(0
h
2)
ˇ
(0
h
1)
˙
24
4bit
3bit
2bit
1bit
0bit
55
0/1
6
3
Modify function assignment of self-defining mode to be
ex-factory setting state.