ENGLISH
)81&7,21$/,7<
212))
The control unit is turned on/off by pressing down for a few seconds
on P1 (ON/OFF)
The OFF status is signalled by the switching on of the OFF led.
When the product is turned on, the following message sequence
is displayed:
Product code: 044
Product revision:
r1.2
KIT configuration:
CFG 10
.,7&21),*85$7,21
The thermoregulator is configured in the INSTALLER menu based
on the managed kit:
s
CFG 10 for Kit: P2
s
CFG 20 for Kit: L2
s
CFG 30 for kits: L3, P3
s
CFG 40 for kits: L1, P1
s
CFG 50 for kits: L5, P5
',63/$<
The product correctly displays the value read by probe S1.
In the configuration CFG=40 and CFG=50, pressing the P4 button
for a few seconds displays probe S2 by the dash at the lower left
the entire time the button is pressed.
$/$50)81&7,21
If the temperature detected by the PROBE exceeds the alarm
thermostat value A01 (90°C)
the acoustic and visual signalling is activated
SILENCE function: the acoustic signal can be deactivated for
5 minutes by pressing any button. After this time, if the alarm
condition remains, the acoustic signal will be reactivated.
$17,)5((=()81&7,21
If the temperature detected by the probe goes below the anti-freeze
thermostat value A03 (3°C)
s
the output P1 is activated
s
the display shows ICE
67$1'%<)81&7,21
If the device is OFF and there is an ALARM or ANTI-FREEZE
s
condition, the device will turn ON automatically.
3803$17,%/2&.,1*)81&7,21>3$1'
P2]:
If pumps P1 or P2 are inactive for a time greater than the
Antiblocking Timer t01 (one week)
s
output P1 or P2 is activated for 20 seconds
s
the display shows bLP
This function is also active in STANDBY mode.
38037(67)81&7,21>3@
Pressing down on button P2(-)
s
for a few seconds activates the output P1 the entire time the
button is pressed
s
the display shows tSt
38037(67)81&7,21>3@
Pressing down on button P3(+)
s
for a few seconds activates the output P2 the entire time the
button is pressed
s
the display shows tSt
)/2:6:,7&+
The closure of the flow switch (FLUX=ON) is signalled by the dash
to the upper left.
)81&7,21$/,7<
51