ZENIT
TYPE TUBE RADIANT HEATER
User’s Manual
21
Model:
ZENIT 9m „L”
Gas-fired overhead radiant tube heaters Linear shape
Type of heating: Radiant tube
Fuel: Gaseous
Type of fuel: Natural Gas
Propane
Butane
Propane-Butane
Space heating emission NOx
129.7
mg/kWh
input
(GCV)
Characteristics when operating with the preferred fuel only
Item
Symbol Value
Unit
Item
Symbol Value
Unit
Heat output
Useful efficiency - GCV
Nominal
heat output
P
nom
31.3
kW
Useful efficiency at nominal
heat output
h
th.nom
82.72
%
Minimum
heat output
P
min
19.2
kW
Useful efficiency at minimum
heat output
h
th.min
81.39
%
Minimum heat
output -
as percentage
of nominal heat output
--
61.3
%
Radiant factor
Envelop losses
Radiant factor at
nominal
heat output
RF
nom
51.2
%
Envelope insulation class
U
0.0
W/m
2
K
Radiant factor at
minimum
heat output
RF
min
49.4
%
Envelope loss factor
F
env
0.0
%
Regulation (EU) 2015/1188
Heat generator to be installed
outside the heated area
Yes
No
Possible
Auxiliary electricity consumption
Heat output control type
At Nominal heat
output
el
max
0.10
kW
- Single stage (ON-OFF)
Yes
No
At minimum heat
output
el
min
0.06
kW
- Two stage (100%-60%-OFF)
Yes
No
In standby
mode
el
sb
0.0
kW
- Modulated
Yes
No
Permanent pilot flame power requirement
Pilot flame power
requirement (if
applicable)
P
pilot
0.0
kW
Contact