ZENIT
TYPE TUBE RADIANT HEATER
User’s Manual
8
•
SOLELY INTERIOR installation is possible�
•
The installation must comply with the valid standards�
•
For the sake of appropriate efficiency the position and the high of installation has to be carefully defined�
•
The appliance has to be placed in that way that its every part be accessible�
ATTENTION! Only a qualified person can install the appliances who participated in training which was
organised by PAKOLE Trade Kft in every year. It is forbidden to install the device as an user.
ATTENTION! The appliance can only be operated by gas defined on the data board of appliance !
The nominal values of gas-supply pressure:
• in case of natural gas: 25 mbar ( min. 20 mbar – max. 60 mbar )
• in case of Propane gas: 50 mbar
The allowed maximum pressure of gas-supply: 60 mbar!
ATTENTION! If the pressure of gas-supply is higher than 60 mbar in that case the using of pressure
regulator is indispensable because the max. allowed pressure of double-closed magnetic valve is:
Pmax = 60mbar
Appliance installation
Gas connection
•
ELECTRICAL CONNECTING SPECIFICATIONS:
•
The appliance/burner head can be connected to the mains by safety electrical connector (Fig�13) located on the fan
side of appliance head�
•
The appliance must be operated under dry circumstances�
•
At electrical installation of appliance the relevant standard must be considered�
•
The mains connection can be executed by grounded plug or fixed properly installed phase-null wires�
•
The appliance is phase-sensitive for this reason the connection always must be according to the Fig�13�
•
Fort he sake of suitable detachability of appliance from the electrical supply, double-pole – phase / null switching off – detaching main-
switch must be installed�
•
Electrical wiring: 3 x 0,75 MT cable
•
Fuse: 2A dissolving fuse
•
Before change of dissolving fuse by disconnecting of Hirschmann plug the appliance must be detached from electrical supply�
ATTENTION! Both the fan and the ignition control needs 230V/50Hz mains voltage.
Before connecting the appliance to the gas pipe line, please disconnect it from the power line and
close the gas valve front of the burner. The appliance must be connected to a grounded power supply
system!
If the above instructions are not followed that can lead to death, heavy injuries or property damages!
PLEASE CHECK THE GROUNDING!
The combustion–air supply centrifugal fan is fixed to the appliance/burner head, the automatic burner control is located in the burner
head in this way the electrical supply has to be installed just into the appliance head�
Electrical connection
15.picture: Electrical connection
CAUTION
DANGER
CAUTION
ELECTRIC
SUPPLY
ATTENTION
COMPULSORY:
EARTHING
L - phase
N - null
- ground