SECTION 4
OPERATION
73
4.6.3.5 RANGE CONTROL (cont’d)
SELECT OUTPUT RANGE
:
1
,
2
,
3
,
4
. The following ranges are applicable.
PROGRAMMED OUTPUT AC VOLTS RANGE
#
< 110
1
110 - 120.9
2
121 - 130.9
3
> 131
4
NOTE:
The above Output voltages are for Single phase operation. If split (2) phase operation is used,
the listed Output voltage ranges are doubled.
Press
EXECUTE
to save the parameter entries.
4.6.3.6 SLEW RATE SETUP
Selecting SLEW RATE SETUP from the General Setup menu (
fn
,
3
,
6
) allows the slewing functions to
transition at a predetermined rate
From any METER display (V/I, AMPS or POWER), press the
fn
key to enter SETUP MODE.
From the SETUP display, press
3
to enter GENERAL SETUP.
From the GENERAL SETUP 1 display, press
6
to enter SLEW RATE SETUP.
SLEW RATE SETUP:
VOLTS / SEC. = 1
HERTZ / SEC. = 1.00
Default values are 1 volt/second and 1.00 Hz./second.
Press EXECUTE to save the parameter entries.
NOTE:
Slew rates are approximate.
Содержание UPC-1
Страница 1: ...UPC 3 UPC 1 PROGRAMMABLE CONTROLLERS FIRMWARE V4 25 AND LATER OPERATION MANUAL PACIFIC POWER SOURCE δ ...
Страница 2: ......
Страница 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Страница 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 3 Figure 1 3b UPC 3 Figure 1 3c UPC 1 ...
Страница 43: ...SECTION 4 OPERATION 31 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Страница 74: ...SECTION 4 OPERATION 62 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Страница 134: ...NOTES 122 NOTES ...
Страница 135: ...MODIFCATIONS 123 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made ...