SECTION 4
OPERATION
69
4.6.3.1.1.1 PROGRAMMABLE OUTPUT IMPEDANCE CALIBRATION MENU (cont’d)
Ø
column:
indicates the Power Form of operation (1, 2 or 3 phase).
Z direct column:
accepts the Direct coupled impedance of the power source (per phase) for
each Power Form listed on the far left. During DIRECT coupled operation, the
proper Z direct value is used to calibrate the PROG.Zo function based upon the
Power Form selected in the Program being executed.
XFMR ratio column:
accepts up to 3 separate XFMR ratios. Typically only one will be entered.
Z xfmr column:
accepts the impedances of the XFMR listed in the XFMR ratio column.
During XFMR coupled operation, the proper Z xfmr value is used to calibrate
the PROG.Zo function based upon the XFMR ratio selected in the Program
being executed.
The Z direct and Z xfmr values calibrated at the factory are compensated for the power source
impedance at the output terminal of the power source. To compensate for additional wiring, fixtures,
magnetics, etc., follow the calibration procedure; include the external devices in the measurements.
Calibration values for Direct coupled operation may be established via the following procedure.
1. Turn CSC OFF. Disable PROG.Zo. Execute a program in Direct coupled mode.
A. Establish the difference in output voltage between no-load and full-load voltage.
B. Divide the Voltage difference by the full-load current. The net result is the inherent direct
coupled impedance of the power source.
C. Use the result to enter in as Z-Direct for the power form used to perform this test.
V_no_load - V_full_load
Z =
I_full_load
2. Calibration values for XFMR coupled operation may be determined in the same manner, except the Z
direct value must be subtracted from the Z XFMR calculation prior to entering the Z XFMR value into
the UPC.
A good approximation of transformer impedance can be estimated by measuring the DC resistance
of each XFMR secondary tap. That value may be entered for Z XFMR as an alternative to using the
above procedure for measuring XFMR impedance.
NOTE:
XFMR impedances may vary greatly with temperature.
Содержание UPC-1
Страница 1: ...UPC 3 UPC 1 PROGRAMMABLE CONTROLLERS FIRMWARE V4 25 AND LATER OPERATION MANUAL PACIFIC POWER SOURCE δ ...
Страница 2: ......
Страница 12: ...SECTION 1 GENERAL viii THIS PAGE INTENTIONALLY BLANK ...
Страница 17: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 3 Figure 1 3b UPC 3 Figure 1 3c UPC 1 ...
Страница 43: ...SECTION 4 OPERATION 31 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL ...
Страница 74: ...SECTION 4 OPERATION 62 90 0 100 0 85 95 100 90 FIGURE 4 6 2 1 EDITED WAVEFORM ...
Страница 134: ...NOTES 122 NOTES ...
Страница 135: ...MODIFCATIONS 123 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made ...