18" [457mm]
8" [203mm]
8" [203mm]
35" [889mm]
18" [457mm]
8" [203mm]
8" [203mm]
57 5/8" [1.46m]
Canada Only
Ember
Protection
The stove must be installed with ember protection in front
of the unit, made from a non-combustible material with a
minimum K value of 23.7 btu/ft h ˚
F.
. - Equivalent to 20GA
steel. This protection must extend as follows:
U.S.A. Only
Non-combustible
floor protector
Fig. #15
Fig. #16
In Canada: 18" (457 mm) on the firing side and 8"(203mm)
to the sides. See Figure #15, below.
In U.S.A: 18" (457 mm) to the front and 8"(203mm) to the
sides of the fuel loading door opening. See Figure #16, below.
Minimum Width - 57 5/8"(1.46m)"
Minimum Overall Depth - 18"(457mm)
Non-combustible
floor protector
Minimum Width - 35"(889mm)
Minimum Overall Depth - 18"(457mm)
Safety Strip
The floor between the fireplace and the hearth extension/
ember protection must be protected with a 2"(51mm) deep
safety metal strip equal to the width of the unit.
One half of the metal strip must be under the fireplace front
and the other half must extend onto the floor and under the
hearth extension/ember protection as shown in Fig. #17.
Safety metal strip
Hearth extension
non-combustible
finish material
Floor
The space between
the fireplace and the
hearth extension must
be sealed with a
non-combustible
material such as
sand-cement grout.
Fireplace front
2”
51mm
Fig. #17
(Type 1 floor protector - approved to UL1618)
Minimum 20GA steel
19
5055.7618_210916-32
FP25.BODYA