23
3. Pull the
rotary knob (5)
and the
plug (4)
off the
hollow shaft (7).
4. Turn the
indicator disc (6)
by 180° so that the
red
zone points upwards
(illustr. 14).
5. Refi t the
rotary knob (5)
and the
plug (4)
to the
hollow shaft (7).
The rotary knob can only be easily engaged
in
one snap-in position.
It is now pointing to
the red zone. Please do not apply excessive
force on the hollow shaft.
Illustr. 16
6
6
6. Turn the
rotary knob (5)
back
to the blue zone of the
indicator disc (6)
(illustr. 15).
Illustr. 17
7. Set the
operating switch (1)
back to
automatic
operation
by turning it anticlockwise by 90° with the
help of a screwdriver so that the slot is in a vertical
position and the tip of the arrows points to
“A”
(illustr.
16).
u
The actuator can now be mounted onto the three-
way mixing valve.
Damage to property caused by wrong handling!
NOTICE
•
Always switch to manual operation before
actuating the rotary knob by hand.
If the rotary knob is actuated with excessive force
during automatic operation, this will cause damage
to the gear mechanism.
5
1
1
Illustr. 18