Oilstop V anti-siphon valve
Operation
8. Operation
•
During operation, the valve does not require any action.
•
The valve can be shut off for work on the suction pipe. To do so, set
the scale to “absperren” (shut off) by turning the handwheel. After
having completed the work on the suction pipe, set the scale back to
the required protection height.
9. Troubleshooting
MALFUNCTION
CAUSE
REMEDY
Heating oil leaks
during the functional
check
The Oilstop V is set
too low or to
“entlüften” (bleed)
Set the valve to the correct
protection height
Contamination in the
valve seat
Remove the valve and
blow it out with
compressed air, then
reinstall it
The burner switches
to malfunction after
it has been in
operation for some
time (hours, days)
Check the sizing of the
suction pipe
The burner cannot
be put into operation
The Oilstop V is set to
“absperren” (shut off)
Correct the setting
The suction pressure
is too high
Redesign the suction pipe,
use fittings with a larger
flow rate
The valve is installed
the wrong way round
Install the valve the right
way round