Section 2.0 - PRE-INSTALLATION REQUIREMENTS 

 

2.1.  MASONRY & ZERO CLEARANCE REQUIREMENTS 

 
The masonry fireplace must meet the minimum code requirements, or NFPA 211 or the 
equivalent for a safe installation.  Contact your local Building Inspector for requirements in your 
area.  An inspection of the fireplace should include the following: 
 

1.  CONDITION OF THE FIREPLACE AND CHIMNEY:  Examine the masonry fireplace and 

chimney  prior  to  installation  to  determine  that  they  are  free  from  cracks,  loose  mortar, 
creosote deposits, blockage, or other signs of deterioration.  If evidence of deterioration is 
noted, the fireplace or chimney should be upgraded prior to installation. 

 
2.  INSTALLATION 

INTO 

AN 

EXISTING  FACTORY-BUILT 

ZERO-CLEARANCE   

FIREPLACE:    It  is  possible  to  install  a  wood  insert  into  an  existing  factory-built  zero-
clearance fireplace.  However, there currently exists no UL or ULC standard specific to that 
type  of  installation.    The  first  thing  that  must  be  verified  is  that  the  factory-built  zero 
clearance fireplace is listed (it must be certified by a competent certification body such as 
Omni or Warnock Hersey).  It must be suitable for use with solid fuel and nothing in the 
owner’s  manual  must  specifically  prohibit  the  installation  of  a  fireplace  insert.  When  in 
doubt,  check  with  the  fireplace  manufacturer.    The  installation  of  the  zero-clearance 
fireplace MUST be thoroughly inspected by a professional in order to ensure that it still 
meets the manufacturer’s specs and code conformity. The chimney must be of at least 1" 
(25 mm) larger in diameter to accommodate a required continuous stainless steel liner 
running from the flue collar to the top of the chimney termination. 

 

 Never remove parts that serve to insulate the zero-clearance fireplace from combustible 
material. Only readily detachable parts that are easily replaced, such as damper parts, 
screens, and doors, are to be removed from the fireplace.  These parts must be stored 
nearby and available for retrofit if the insert is ever removed.  Removal of any parts which 
render the fireplace unfit for use with solid fuel requires the fireplace to be permanently 
labelled by the installer as being no longer suitable for solid fuel until the removed parts are 
replaced and the fireplace is restored to its original certified condition. Furthermore, any air 
vents, grilles, or louvers that serve to create an air circulation pattern around and outside 
the zero-clearance fireplace shall never be removed. 

 
3.  CHIMNEY CAPS:  Mesh type chimney caps must have provision for regular cleaning, or the 

mesh should be removed to eliminate the potential of plugging. 

 

4.  LINER:  The chimney must have an acceptable masonry liner suitable for solid fuel, 

otherwise a continuous stainless steel liner must be installed. 

 

5.  ADJACENT COMBUSTIBLES:  The fireplace should be inspected to make sure that 

there is adequate clearance to combustibles, both exposed combustibles to the top, 
side, and front as well as concealed combustibles, in the chimney and mantel area.  
Your local inspector should have information on whether older fireplaces are of 
adequate construction. 

 
 

Содержание 2000-I E.P.A.

Страница 1: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 2: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 3: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 4: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 5: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 6: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 7: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 8: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 9: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 10: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 11: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 12: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 13: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 14: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 15: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 16: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 17: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 18: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 19: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 20: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 21: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 22: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 23: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 24: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 25: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 26: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 27: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 28: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 29: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 30: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 31: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 32: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 33: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 34: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 35: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 36: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 37: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 38: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 39: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 40: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 41: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 42: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 43: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 44: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 45: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 46: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 47: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 48: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 49: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 50: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 51: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 52: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 53: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 54: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 55: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 56: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 57: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 58: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 59: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 60: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 61: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 62: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 63: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 64: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 65: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 66: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 67: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 68: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 69: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 70: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 71: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 72: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 73: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 74: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 75: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 76: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 77: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 78: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 79: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 80: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 81: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 82: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 83: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 84: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 85: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 86: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 87: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 88: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 89: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 90: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 91: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 92: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 93: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 94: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 95: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 96: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 97: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 98: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 99: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 100: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 101: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 102: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 103: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 104: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 105: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 106: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 107: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 108: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 109: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 110: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 111: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 112: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 113: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 114: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 115: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 116: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 117: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 118: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 119: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 120: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 121: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 122: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 123: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 124: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 125: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 126: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 127: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 128: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 129: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 130: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 131: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 132: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 133: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 134: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 135: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 136: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 137: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 138: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 139: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 140: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Отзывы: