3.3.  SAFETY INFORMATION 

 

NOTE: 

This appliance is not recommended for use in a home if an occupant has any 
respiratory or any other related problems. 

 

1.  It is important to follow the installation and operation instructions.  An improperly installed or 

operated insert could result in a safety hazard or fire, or damage to the unit, which would 
not be covered by the warranty.  Contact local building or fire officials about restrictions and 
installation requirements in your area.  You should be familiar with the installation and be 
sure that the work is done in accordance with this manual.   

 

 

WARNING:  DO NOT INSTALL THIS INSERT IN A SLEEPING ROOM. 

 

2.  Where lesser clearances are desired, consult your local authority as regulations may vary 

regarding the use of clearance reducing devices.  Listed wall and floor shields are available 
to reduce clearances, and most building codes provide information on materials which may 
be used to reduce clearances. 

 
3.  Maintain at least the minimum clearances to combustible material as specified in this manual.  
Clearances are measured to the nearest part of the insert (i.e. top edge on the side).  Clearances 
to  any  combustibles,  when  measured  directly  out  from  the  front,  must  be  a  minimum  of  48" 
(1219mm). 
 

4.  Maintain at least the minimum floor protection for combustible floor materials as specified in 

this manual.  Floor protection to the front is to be measured from the fuel loading door 
opening. 

 

5.  Osburn recommends that you install a listed smoke detector or alarm in your home.  Normal 

operation of the insert will have no effect on the detector or alarm. 

 

6.  The insert is to be connected only to a lined masonry chimney and masonry fireplace 

conforming to building codes for use with solid fuel.  Do not remove bricks or mortar 
from the existing fireplace when installing the insert.  This insert must be connected to a 
code-approved masonry chimney or listed factory-built fireplace chimney with a direct 
flue connector into the first chimney liner section.  The chimney size should not be less 
than or more than three times greater than the cross-sectional area of the flue collar 
 

7.  Minimum chimney size is 6" (152mm) diameter.  Maintain a 15' (4.5m) minimum overall 

height measured from the base of the appliance.  Chimneys should be inspected to 
check for deterioration and to determine if they meet the minimum requirements, and be 
upgraded if necessary.  The chimney must extend at least 3' (914mm) above the roof 
and at least 2' (610mm) above the highest point within an area of 10' (3m) of the 
chimney. 

 

8.  Do not use makeshift compromises during installation as they could create a safety hazard 

and a fire could result. 

 

9.  DO  NOT  CONNECT  THIS  APPLIANCE  TO  THE  CHIMNEY  OR  FLUE  SERVING 

ANOTHER APPLIANCE. 

Содержание 2000-I E.P.A.

Страница 1: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 2: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 3: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 4: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 5: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 6: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 7: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 8: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 9: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 10: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 11: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 12: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 13: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 14: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 15: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 16: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 17: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 18: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 19: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 20: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 21: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 22: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 23: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 24: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 25: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 26: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 27: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 28: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 29: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 30: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 31: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 32: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 33: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 34: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 35: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 36: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 37: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 38: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 39: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 40: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 41: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 42: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 43: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 44: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 45: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 46: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 47: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 48: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 49: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 50: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 51: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 52: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 53: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 54: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 55: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 56: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 57: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 58: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 59: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 60: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 61: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 62: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 63: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 64: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 65: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 66: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 67: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 68: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 69: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 70: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 71: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 72: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 73: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 74: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 75: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 76: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 77: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 78: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 79: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 80: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 81: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 82: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 83: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 84: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 85: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 86: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 87: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 88: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 89: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 90: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 91: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 92: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 93: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 94: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 95: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 96: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 97: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 98: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 99: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 100: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 101: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 102: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 103: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 104: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 105: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 106: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 107: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 108: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 109: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 110: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 111: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 112: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Страница 113: ...NUAL US ENVIRONMENTAL PROTECTION AGENCY PHASE II CERTIFIED WOOD INSERT Verified and tested following ULC S628 and UL 1482 Standards by Stove Builder International Inc 250 rue de Copenhague St Augustin...

Страница 114: ...mage bodily injury or even death Consult your municipal building department or fire officials about restrictions and installations requirements in your area and the need to obtain a permit Keep and sa...

Страница 115: ...INSTALLATION INSTRUCTIONS OPTIONAL 12 3 8 BAFFLE INSTALLATION 13 3 9 SECONDARY AIR TUBE REPLACEMENT 14 3 10 REMOVAL INSTRUCTIONS 15 Section 4 0 OPERATION 16 4 1 SAFETY INFORMATION 16 4 2 CORDWOOD FUEL...

Страница 116: ...3 Section 1 0 DIMENSIONS Faceplate fully extended toward the back Faceplate fully extended toward the front...

Страница 117: ...manufacturer s specs and code conformity The chimney must be of at least 1 25 mm larger in diameter to accommodate a required continuous stainless steel liner running from the flue collar to the top o...

Страница 118: ...mpensate for poor draft situations caused by large cross sectional chimneys The insert will not work without a positive seal in the chimney Chimneys constructed outside of the home on an exterior wall...

Страница 119: ...to any combustibles as mentioned on your insert certification label See figure 3 1 and table 3 1 Figure 3 1 CLEARANCES MINIMUM MASONRY OPENING A 13 330 mm F 24 610 mm B 22 559 mm G 29 737 mm C 10 254...

Страница 120: ...front of the insert is included in the calculation of the floor protector s dimensions Convert specification to R value k factor is given with a required thickness T in inches R 1 k x T C factor is g...

Страница 121: ...um floor protection for combustible floor materials as specified in this manual Floor protection to the front is to be measured from the fuel loading door opening 5 Osburn recommends that you install...

Страница 122: ...he room This creates a potential health hazard 3 CONNECTOR INSTALLATION A flue connector may provide acceptable performance however we recommend the use of a chimney liner to ensure satisfactory perfo...

Страница 123: ...inished side down on a flat soft non abrasive surface 2 Assemble the faceplate trim attaching the mitered corners with the corner brackets see Figure 3 5 3 Line up the holes of the side and top panels...

Страница 124: ...lay see Figure 3 7 Figure 3 7 2 Flip over both parts with the finished side on a plane and smooth surface free from dirt to avoid any scratches Align the holes of the door to those of the overlay Fix...

Страница 125: ...Open the rectangular outlet on the side of the unit by gently removing the material held in place by micro joints Use pliers Note The fresh air intake may be installed on the right or left end side o...

Страница 126: ...any damaged firebricks replaced Check the firebricks annually for damage and replace if they are broken or damaged See Figure 3 8 and 3 9 for the firebrick layout Install the side back firebricks firs...

Страница 127: ...r using a new cotter pin The cotter pin is a hammerlock style and locks into place by hitting the head sharply with a hammer 5 Note that any tube can be replaced without disturbing the baffle Importan...

Страница 128: ...ur insert Unscrew the faceplate fastener holding the faceplate to the faceplate extension Remove faceplate by pulling on it Remove faceplate extension Unclip the blower assembly Remove the three screw...

Страница 129: ...spillage or a back draft causing flame or smoke to spill into the room 5 Never use gasoline type lantern fuel kerosene solvents charcoal lighter fluid or inflammable liquids to start or freshen a fire...

Страница 130: ...this is not done it could cause poor air quality in the home poor and incomplete combustion and poor efficiency in the insert Adequate ventilation is required to reduce effects from room air starvatio...

Страница 131: ...moisture content of 20 or less are ideal Dry seasoned wood can be distinguished from green wood by the checks or cracks in the ends 4 Wet or green wood will tend to cause the fire to smoulder produci...

Страница 132: ...ight fume with an unpleasant odour Open windows Leave the room if the smell is too intense The fume is non toxic and will disappear completely after the unit will have been used a few times at higher...

Страница 133: ...ble 4 2 to adjust the draft control to the desired burn rate Draft Settings Burn Rate Draft Setting Low Push Control to end of travel Medium Low Pull Control by 3 8 from closed position Medium High Pu...

Страница 134: ...burn cleanly without smouldering If the fire smoulders without flame re establish a hotter fire before moving the air control to the lower setting A yellow flame burning in the top of the firebox is a...

Страница 135: ...This may take up to one hour depending on how hot the fire is NOTE ENSURE THE FAN CORD IS NOT IN CONTACT WITH ANY SURFACE OF THE INSERT TO PREVENT ELECTRICAL SHOCK OR FIRE DAMAGE DO NOT RUN CORD BENE...

Страница 136: ...quired when burning damp wood and or when burning slow fires Generally if the glass is not staying clean then the unit is being under fired Dirty glass may be self cleaned by burning a hot fire i e dr...

Страница 137: ...ground well away from all combustible materials pending final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in the closed container unt...

Страница 138: ...e the amount of creosote produced Even so the chimney connector pipe and chimney should be inspected at least once every two months during the heating season to determine if a creosote build up has oc...

Страница 139: ...inside the firebox The EPA output on the other hand is what has been obtained during emissions testing The EPA test procedure requires that a special type of wood be used and positioned inside the fir...

Страница 140: ...ent part All parts and labour costs covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspecti...

Отзывы: