background image

OSAKA

 - USER MANUAL - B4U - v2 - PAG. 11

 

It also allows the display of the acronym "dF" ("dL" = Lb) during the 
defrost and, after the defrost is finished, the message "Pd" will appear 
until,  after  the  defrost,  the  Pr1  temperature  has  not  returned  to  the 
set value. the last reading, or to the value ["SP" + "d"]) or when the 
time programmed in parameter "dA" expires. 
Otherwise  ("dL"  =  oF),  the  display  will  show  the  temperature 
measured by the Pr1 probe during a defrost. 
 

5.9 - EVAPORATOR FAN CONTROL 

The  evaporator fan control  works through  the  output  configured  as 
"Fn"  depending  on  certain  control  states  of  the  B4U  and  the 
temperature measured by the evaporator probe (probe configured as 
"EP"). 
The parameters related to the fan control functions are found in the 
"-Fn" folder. 
If the evaporator probe is not used or is in error, the output configured 
as "Fn" is activated only according to the parameters "tn", "tF" and 
"FE". 
With the parameters "tn" and "tF" it is possible to set the behavior of 
the  evaporator  fans  when  the  regulation  output  configured  as  "ot" 
(compressor) is deactivated. 
When the output "ot" is deactivated, it is possible to make the output 
configured  as  "Fn"  continue  to  operate  cyclically  according  to  the 
times  programmed  in  the  parameter  "tn"  (activation  time  of  the 
evaporator  fan  at  compressor  stop)  and  "  tF  "(evaporator  fan 
deactivation time at compressor stop).

 

When the compressor stops, the B4U keeps the evaporator fans on 
for time "tn", then turns them off for time "tF" and so on until the output 
"ot" remains off. 
When  programming  "tn"  =  oF,  the  “Fn”  output  will  be  deactivated 
when the “ot” output is deactivated (the evaporator fans are off when 
the compressor is stopped or the fans are running together with the 
compressor). 
By programming "tn" at any value and "tF" = oF, the "Fn" output will 
remain  activated  even  when  the  "ot"  output  is  deactivated  (the 
evaporator fans are on when the compressor is stopped). 
The  "FE"  parameter  allows setting  whether  the  fans should always 
be on regardless of the defrost status ("FE" = on) or turn off during 
defrost ("FE" = oF). 
In  the  latter  case,  by  setting  the  time  in  the  "Fd"  parameter,  it  is 
possible to delay the restart of the fans after the end of the defrost. 
When this delay is active, the FAN LED flashes to indicate the delay 
in progress. 
When the evaporator probe is used for the fan, it is conditioned by 
the parameters "tn", "tF and" FE, and acts as a temperature control. 
In  fact,  it  is  possible  to  configure  the  fans  to  deactivate  when  the 
temperature  measured  by  the  evaporator  probe  is  higher  than  the 
value programmed in the "FL" parameter (temperature too high) or 
also  when  it  is  lower  than  the  value  programmed  in  the  "LF" 
parameter. "(very low temperature). 
Associated  with  these  parameters  there  is  a  programmable 
differential in the parameter "dF" 

.

 

 
Note:  Special  attention  should  be  paid  to  the  correct  use  of  the 
temperature-based  fan  control  functions,  since  in  a  typical 
refrigeration  application,  the  evaporator  fan  stops  due  to  thermal 
change. 
Remember  that  the  operation  of  the  evaporator  fans  can  also  be 
conditioned by the "door open" function of the digital inputs. 

 

5.10 - ALARM FUNCTIONS 

The parameters related to the fan control functions are found in the 
"-AL" folder. 
The B4U alarm conditions are: 
 

- Probe error: "E1", "-E1", "E2," -E2 "," E3 "," -E3 " 
- Temperature alarm: "H1", "L1", "H2", "L2" 
- External alarms: "AL", "Pr", "HP", LP " 
- Open door alarm: "oP" 
The alarm function acts on the internal buzzer, if it is configured with 
the "Bu" parameter, and on the desired output, if it is configured with 
the "o1", "o2", "o3", "o4" parameters. 
The  buzzer  can  be  configured  to  signal  alarms  by  setting  the 
parameter "Bu" = 1 or 3 or 4 and always functions as an alarm that 
can  be  silenced.  This  means  that,  when  activated,  it  can  be 
deactivated by briefly pressing any key. 
Alarms can be configured to signal them by configuring the outputs. 
The possible alarms that can be configured are the following: 
= On - When you want the output to activate in alarm condition and 
to  be able  to deactivate  (silence) manually  by pressing any  key  on 
the B4U. 
= AL - When the output is desired to activate in alarm condition but 
cannot be manually deactivated and therefore deactivates only when 
the alarm condition is canceled (typical application for a light signal). 
= An - When you want the output to activate in alarm condition and 
to remain active even when the alarm condition has ceased (alarm 
memory).  Therefore,  deactivation  (stored  alarm  acknowledgment) 
can only be performed manually by pressing any key when the alarm 
status has been cleared (typical application for light signal). 
= -t - When the operation described as En is desired but with inverse 
operation logic (output activated in normal condition and deactivated 
in alarm condition). 
= -L - When the operation described as AL is desired but with inverse 
operation logic (output activated in normal condition and deactivated 
in alarm condition). 
= -n - When the operation described as An is desired, but with inverse 
operation logic (output activated in normal condition and deactivated 
in alarm condition). 
 

5.10.1 - TEMPERATURE ALARMS 

The  B4U  has  two  temperature  alarms,  each  with  fully  configurable 
maximum and minimum thresholds. 
The temperature alarm functions act according to the measurements 
of  the  probes,  what  is  configured  in  parameters  "1y"  and  "2y",  the 
alarm  thresholds  programmed  in  parameters  "1H"  and  "2H" 
(maximum alarms), "1L" and "2L" (minimum alarms) and the relative 
differentials "1d" and "2d". 
Through the parameters "1y" and "2y" "it is possible to program the 
alarm thresholds" 1H "," 2H "," 1L "," 2L "and they must be considered 
as absolute or relative to the Set Point. 
Depending  on  the  desired  operation,  the  parameters  "1y"  and  "2y" 
can be configured with the following values: 

= 1:

 Absolute referring to Pr1 with message display (HL).  

= 2:

 Relative to Pr1 with message display (HL). 

= 3:

 Absolute referring to Au probe with message display (HL)  

= 4:

 Relative to Au probe with message display (HL).  

= 5:

Absolute referring to cd probe with message display (HL). = 6: 

Absolute referring to Pr1 without message display. 

= 7:

 Relative to Pr1 without message display.  

= 8:

 Absolute referring to Au probe without message display.  

= 9:

 Relative to Au wave without message display. 

= 10:

 Absolute referring to cd probe without message display. 

 
By means of some parameters it is possible to delay the notification 
of these alarms. These parameters are: 
"1P" and "2P" - are the delay times of the temperature alarms at the 
start of the B4U, which if there are alarms at start-up, they will wait 
for the time programmed in these parameters to pass. 
If there are no alarm conditions at connection, the relative time "1P" 
and "2P" will not be taken into account. 
"DA" - It is the delay time of temperature alarm 1 during a defrost. 

Note: Alarm 1 during defrosts and during time "dA" after the end of 
defrosts  is  deactivated,  while  alarm  2  during  defrosts  is  always 
activated. 

"1t", "2t" - They are the delay time for the activation of temperature 
alarms 1 and 2. 
Temperature  alarms  1  and  2  are  activated  when  the  delay  times 
expire  and  after  the  times  "1t"  and  "2t",  when  the  measured 
temperature of the probe set by the alarm rises above or falls below 
the respective threshold of maximum and minimum alarm. 

Содержание B4U

Страница 1: ...ONNECTION 5 FUNCTIONING 5 1 ON STAND BY FUNCTION 5 2 NORMAL ECONOMIC AND TURBO OPERATING MODES 5 3 PROBE INPUTS AND DISPLAY CONFIGURATION 5 4 DIGITAL INPUTS CONFIGURATION 5 5 CONFIGURATION OF THE OUTPUTS AND BUZZER 5 6 TEMPERATURE REGULATION 5 7 COMPRESSOR PROTECTION AND START DELAY FUNCTION 5 8 DEFROST CONTROL 5 8 1 AUTOMATIC DEFROST 5 8 2 MANUAL DEFROST 5 8 3 DEFROST END 5 8 4 INTERVAL AND DURAT...

Страница 2: ...be configured 3 DOWN AUX 2 key In normal operating mode pressing and releasing allows quick access to the Set Point selection and modification mode Pressing for 3 seconds allows activating deactivating the configured output configured as A2 anti fog heating elements In the programming and display modes of the temperature measured by the room probe the evaporator temperature P1 and P2 and in additi...

Страница 3: ...the PP parameter within the tS group To have this protection available we will program the desired password number in the PP parameter Once the protection is activated to access the parameter menu press the ON OFF LIGHT keys simultaneously for 5 seconds and the display will show rP press the LIGHT key and the display will show 0 At this point using the UP and DOWN keys we will establish the passwo...

Страница 4: ...hat instant To exit the variables display mode we will not press any of the 4 keys for approximately 10 seconds 3 WARNINGS FOR USE 3 1 PERMITTED USE The B4U has been designed as a measuring and regulating device in accordance with EN 60730 1 for operation at altitudes up to 2000m The use of the B4U in applications not expressly provided for in the aforementioned standard must include all appropria...

Страница 5: ...eople things or animals 4 2 1 ELECTRICAL WIRING DIAGRAM Color legend Cable Strip 1 Brown 2 White 3 Green 4 Blue 5 Red 6 Black 5 OPERATION 5 1 ON STAND BY FUNCTION The B4U once turned on can take 2 different conditions ON It means that it works with the normal control functions STAND BY It means that the controller does not operate with any control function and the display turns off the Stand by LE...

Страница 6: ...g the Et time it will automatically switch to ECONOMY mode The B4U remains in ECONOMY mode until the door is reopened or if configured until the tt timeout When it exits the ECONOMY mode the B4U performs a TURBO cycle to recover the temperature of the products then returns to the NORMAL operating mode and so on 1 The time Et is reset every time the door is opened In the case of the example the doo...

Страница 7: ...ATION OF THE OUTPUTS AND BUZZER The parameters related to the configuration of the outputs are contained in the group Ou The outputs of the B4U can be configured through the parameters o1 o2 o3 and o4 with the following functions ot Compressor Solenoid Control or Cooling Element dF Control of defrost heaters Fn Evaporator fans control Au Auxiliary output control En Allows the Control of a silencea...

Страница 8: ...with Heating action In this case the regulation Set point for the ot output will be SP SE SH while for the HE output it is through the Set SH The regulation differential for the ot output is the active one between d or Ed or Hd is assumed automatically by the B4U to have positive values in the cooling action while for the HE output the differential will be Hd considered with negative values during...

Страница 9: ...counts the time since the B4U was started This mode is the one currently used in refrigeration systems ct At intervals of compressor operation time The interval di is counted as the sum of the operating times of the output ot output on This mode is normally used in refrigeration systems with compressor stop in defrost cS Defrost cycle at each compressor stop The regulator starts a defrost cycle ev...

Страница 10: ...be set as EP exceeds the temperature set in parameter tE If this temperature is not reached within the time set in parameter dE the defrost will be interrupted To avoid unnecessary defrosting when the evaporator temperature is high the tS parameter allows setting the temperature referring to the evaporator probe below which the defrosts will be activated Therefore in the indicated modes if the tem...

Страница 11: ...nfigured with the o1 o2 o3 o4 parameters The buzzer can be configured to signal alarms by setting the parameter Bu 1 or 3 or 4 and always functions as an alarm that can be silenced This means that when activated it can be deactivated by briefly pressing any key Alarms can be configured to signal them by configuring the outputs The possible alarms that can be configured are the following On When yo...

Страница 12: ...e to show the initials oP on the display When the door open alarm intervenes the normally activated outputs fans or fans compressor are also deactivated 5 10 4 VOLTAGE CONTROL ALARM The parameters related to the voltage control alarm functions are found in the UA folder The B4U can automatically deactivate the control outputs when the mains voltage measured by the B4U through its power supply is l...

Страница 13: ...e SP S Parameters Relative to the Set Point 1 SH Turbo Set Point or Minimum Set point and Superheat Set point in HC mode 99 HS 4 0 2 SE Economic Set Point maximum set point LS 99 8 0 3 S1 Set Point SE SH 4 0 In i Parameters related to inputs 4 uP Measurement unit and resolution decimal point C0 C with resolution 1 F0 F with 1 resolution C1 C with 0 1 resolution F1 F with 0 1 resolution C0 F0 C1 F1...

Страница 14: ... 0 29 Ei Interval between defrosts in case of evaporator probe error oF 01 59 min 01 99 hrs 4 30 EE Defrost duration in case of evaporator probe error oF 01 59 sec 01 99 min 20 31 tS Temperature from which the defrost starts 99 9 9 9 9 10 99 C F 2 0 32 tF Temperature that forces the start of the evaporator defrost 99 9 9 9 9 10 99 C F 99 33 St Defrost start delay due to evaporator temperature oF 0...

Страница 15: ...1 2Y Temperature alarm type 2 see 1y 1 2 3 4 5 6 7 8 9 10 3 62 2H High temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 63 2L Low temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 64 2d 2H and 2L alarm hysteresis 0 0 9 9 30 C F 1 0 65 2t Alarm delay 2H and 2L oF 01 59 sec 01 99 min oF 66 2P Temperature alarm delay time 2 on connection oF 01 59 min 01 99 hrs 2 67 2A Action of alarms 2 on the...

Страница 16: ...ify the correct functioning of the probe it is useful to have the ohm values of the probes EP Possible anomaly in the EEPROM memory Press the SET key Turn the device off and on Err Fatal Device Memory Error Replace the device or send it in for possible repair 7 2 CLEANING It is recommended to clean the B4U only with a cloth slightly dampened with water or a non abrasive detergent and that does not...

Страница 17: ...MATE N LOK 250 removable connector Connection Display B4U Power Unit B4U 3 m MAX Through the cable with removable mini connectors Pollution degree 2 Ambient operating temperature 0 60 C Operating ambient humidity less than 95 RH non condensing Transport and storage temperature 25 60 C 8 3 FUNCTIONAL CHARACTERISTICS Temperature control ON OFF Defrost control by intervals or by temperature with elec...

Отзывы: