OSAKA

 - USER MANUAL - B4U - v2 - PAG. 7

 

SP

: the active regulation set point (SP),  

Ec

: Measurement of the Pr1 probe in normal mode with the initials 

“Ec” in the dispaly if the controller is in ECONOMIC mode.  

F1

:  Measurement  of  the  filtered  Pr1  probe  through  the  parameters 

"dd" and "du". 

oF

: Numeric display off

 

(OFF). 

If one of the measurements is displayed ("dS" = P1, P2, P3, Ec, F1) 
the "CU" parameter allows setting an offset that is applied to show 
only  the  variable  (all  regulation  controls  will  always  be  carried  out 
according to correct measurement of the calibration parameter). 
Regardless of what is set in the "dS" parameter, it is possible to view 
all the measurement and operating variables in a rotating manner, for 
this see section 2.7 - VARIABLES DISPLAY. 
Also  remember  that  the  display  related  to  the  Pr1  probe  can  be 
modified by means of the screen lock function during defrost through 
the "dL" parameter (see 5.8 - Defrost control). 
 

5.4 - DIGITAL INPUT CONFIGURATION 

The parameters related to the configuration of the digital inputs are 
found in the group "-In". 
The  B4U Display  has  1 digital  input  for  power-free  contacts  whose 
function is defined in parameter "1F" and whose action is delayed by 
the time established in parameter "1t".  
On  the  other  hand,  the  Power  Unit  B4U  can  have  a  digital  input 
whose function is defined in the "4F" parameter plus another 2 power-
free  digital  inputs  as  an  alternative  to  the  measurement  inputs  Pr2 
and Pr3. 
To use these inputs as digital, set the relative parameter to "P2" or 
"P3" = dG. 
The configured function that these digital inputs perform is defined in 
parameters "2F" and "3F". 
The  action  time  of  digital  input  2  can  be  delayed  in  parameter  "2t" 
while  the  action  of  digital  inputs  di3  and  di4  is  instantaneous  and 
cannot be delayed. 
Parameters "1F", "2F", "3F", "4F" can be configured for the following 
operations: 
= 0 - Digital input not active 
= 1 - Opening of the chamber door through normally open contact: 
when  the  input  is  closed,  the  B4U  alternately  displays  oP  and  the 
variable  set  in  the  "dS"  parameter.  With  this  operating  mode,  the 
action  of  the  digital  input  also  activates  the  time  programmed  in 
parameter "oA", after which the alarm is activated to signal that the 
door is open. 
When the door is opened, if the ECONOMIC mode is activated, the 
B4U returns to normal operation. 
=  2  -  Chamber  door  opening  with  fan  lock  through  normally  open 
contact: similar to "1F / 2F / 3F / 4F" = 1 but with evaporator fan lock. 
If open door alarms are generated (after time "oA") the output will be 
deactivated. 
=  3  -  Chamber  door  opening  with  compressor  and  fan  block  and 
through normally open contact: similar to "1F / 2F / 3F / 4F" = 2 but 
with  fan  and compressor block.  If  open  door  alarms  are generated 
(after time "oA") the output will be deactivated. 
= 4 - External alarm signaling with normally open contact: when the 
digital input is closed and the alarm is activated, the B4U alternately 
displays AL and the variable set in the "dS" parameter. 
= 5 - External alarm signaling with deactivation of the control output 
(excluding alarm and light outputs) by normally open contact: when 
the digital input is closed, all the control outputs are deactivated and 
the alarm is activated, the B4U displays alternately on the display AL 
and the variable set in the "dS" parameter. 
= 6 - Normal / Economic mode selection with normally open contact: 
When the digital input is closed, the Economic mode will be selected. 
When the input is open, Normal mode is selected. 
=  -1,  -2,  -3,  etc.  -  Identical  functions  to  the  previous  ones  but  with 
inverse  operating  logic.  Activating  when  the  digital  input  contact 
opens. 

Note: In the event that the digital input is configured for this type of 
function, the unit will consider the contacts as if they were in parallel 
(considering this result as an OR function). 

 
 
 
 
 

5.5 - CONFIGURATION OF THE OUTPUTS AND BUZZER 

The  parameters  related  to  the  configuration  of  the  outputs  are 
contained in the group "-Ou". 
The  outputs  of  the  B4U can  be  configured  through  the parameters 
"o1", "o2", "o3" and "o4", with the following functions: 

=

 ot - Compressor / Solenoid Control or Cooling Element.

 

=

 dF - Control of defrost heaters. 

=

 Fn - Evaporator fans control. 

=

 Au - Auxiliary output control. 

=

 En - 

Allows the Control of a “silenceable” Alarm device through the 

normally  open  and  closed  digital  input  during  the  alarm  (See  from 
section 5.10 - ALARM FUNCTIONS). 

=

 

AL: Allows the Control of a “non-silenceable” Alarm device through 

the normally open and closed digital input during the alarm (See from 
section 5.10 - ALARM FUNCTIONS). 

=

  An:  Allows  the  control  of  an  alarm  device  with  memory  function 

through the normally open and closed digital input during the alarm 
(See from section 5.10 - ALARM FUNCTIONS). 

=

  -t  - 

Allows  the  control  of  a  “silenceable”  alarm  device  through a 

normally closed and open contact in alarm.  

= -L 

Allows the Control of a “non-silenceable” Alarm device through 

the normally closed and open digital input during the alarm. (See from 
section 5.10 - ALARM FUNCTIONS). 

=  -n 

-  Allows  the  control  of  an  alarm  device  with  memory  function 

through the normally open and closed digital input during the alarm 
(See from section 5.10 - ALARM FUNCTIONS). 

= on 

- Allows the control of a device that must be activated whenever 

the instrument has voltage. If the equipment is in Stand-by, the output 
will remain deactivated. This control is ideal for lighting showcases, 
anti-humidity heating elements or other various functions. 

= HE 

To control a heating device in neutral zone (“r.HC” = nr). 

= L1 

- Showcase light connected to Normal / Economic mode. The 

output  will  turn  on  when  Normal  mode  is  active  and  turn  off  when 
Economy mode is chaotic. 

= L2 

- Internal camera light. The output is always off and if the digital 

input is configured as door opening "1F", "2F", "3F" = 1, 2, 3), it will 
turn on with the door opening. 

= -d 

- Defrost output with normally open contact.  

= A2 

- Auxiliary output 2 control (Anti-fog resistance).  

= oF - No function (output disabled). 
If one of the outputs is configured as an auxiliary output ("o1", "o2", 
"o3"  and  "o4"  =  Au),  its  function  must  be  configured  in  the  "Fo" 
parameter and may be conditioned by the time programmed in the 
"You" parameter. 
 
The "Fo" parameter can be configured for the following functions: 
= oF - No function 
= 1 - Delayed regulation output.  
The  auxiliary  output  is  activated  with  the  delay  programmed  in  the 
parameter  "tu"  with  respect  to  the  output  configured  as  "ot".  The 
output will deactivate as soon as the "ot" output is deactivated. This 
type of operation can be used as control of a second compressor or 
with  a  parallel  control  that  is  useful  for  the  regulation  process.  It 
prevents  two  devices  from  starting  at  the  same  time,  causing  high 
occasional electricity consumption. 
= 2 - Activation by LIGHT key or digital input. The output is activated 
by pressing the LIGHT key or by activating the digital inputs, provided 
they are configured as ("1F / 2F / 3F / 4F" = 9). The key and digital 
input functions are bistable, which means that on the first press of the 
key, the output turns on, while the second press turns off. 
The  output  configured  as  auxiliary  can  be  turned  off  automatically 
after a certain time programmable in the "tu" parameter. With "tu" = 
oF the output is activated and deactivated manually using the LIGHT 
key,  otherwise,  the  output,  once  activated,  will  automatically 
deactivate after the programmed time. This function can be used, for 
example,  to  control  the  camera  light,  anti-fog  resistance  or  other 
functions. 
= 3 - Activation by LIGHT key or digital input even when the B4U is 
in Stand-By. The output is activated in the same way as "Fo" = 2 even 
when the B4U is in Stand-By. 
If one of the outputs is configured as auxiliary output 2 ("1F / 2F / 3F 
/ 4F" = A2), its activation and deactivation can be managed with the 
DOWN key and operation can be conditioned by the time set in the 
parameter "tA "present in group "-tS". 

Содержание B4U

Страница 1: ...ONNECTION 5 FUNCTIONING 5 1 ON STAND BY FUNCTION 5 2 NORMAL ECONOMIC AND TURBO OPERATING MODES 5 3 PROBE INPUTS AND DISPLAY CONFIGURATION 5 4 DIGITAL INPUTS CONFIGURATION 5 5 CONFIGURATION OF THE OUTPUTS AND BUZZER 5 6 TEMPERATURE REGULATION 5 7 COMPRESSOR PROTECTION AND START DELAY FUNCTION 5 8 DEFROST CONTROL 5 8 1 AUTOMATIC DEFROST 5 8 2 MANUAL DEFROST 5 8 3 DEFROST END 5 8 4 INTERVAL AND DURAT...

Страница 2: ...be configured 3 DOWN AUX 2 key In normal operating mode pressing and releasing allows quick access to the Set Point selection and modification mode Pressing for 3 seconds allows activating deactivating the configured output configured as A2 anti fog heating elements In the programming and display modes of the temperature measured by the room probe the evaporator temperature P1 and P2 and in additi...

Страница 3: ...the PP parameter within the tS group To have this protection available we will program the desired password number in the PP parameter Once the protection is activated to access the parameter menu press the ON OFF LIGHT keys simultaneously for 5 seconds and the display will show rP press the LIGHT key and the display will show 0 At this point using the UP and DOWN keys we will establish the passwo...

Страница 4: ...hat instant To exit the variables display mode we will not press any of the 4 keys for approximately 10 seconds 3 WARNINGS FOR USE 3 1 PERMITTED USE The B4U has been designed as a measuring and regulating device in accordance with EN 60730 1 for operation at altitudes up to 2000m The use of the B4U in applications not expressly provided for in the aforementioned standard must include all appropria...

Страница 5: ...eople things or animals 4 2 1 ELECTRICAL WIRING DIAGRAM Color legend Cable Strip 1 Brown 2 White 3 Green 4 Blue 5 Red 6 Black 5 OPERATION 5 1 ON STAND BY FUNCTION The B4U once turned on can take 2 different conditions ON It means that it works with the normal control functions STAND BY It means that the controller does not operate with any control function and the display turns off the Stand by LE...

Страница 6: ...g the Et time it will automatically switch to ECONOMY mode The B4U remains in ECONOMY mode until the door is reopened or if configured until the tt timeout When it exits the ECONOMY mode the B4U performs a TURBO cycle to recover the temperature of the products then returns to the NORMAL operating mode and so on 1 The time Et is reset every time the door is opened In the case of the example the doo...

Страница 7: ...ATION OF THE OUTPUTS AND BUZZER The parameters related to the configuration of the outputs are contained in the group Ou The outputs of the B4U can be configured through the parameters o1 o2 o3 and o4 with the following functions ot Compressor Solenoid Control or Cooling Element dF Control of defrost heaters Fn Evaporator fans control Au Auxiliary output control En Allows the Control of a silencea...

Страница 8: ...with Heating action In this case the regulation Set point for the ot output will be SP SE SH while for the HE output it is through the Set SH The regulation differential for the ot output is the active one between d or Ed or Hd is assumed automatically by the B4U to have positive values in the cooling action while for the HE output the differential will be Hd considered with negative values during...

Страница 9: ...counts the time since the B4U was started This mode is the one currently used in refrigeration systems ct At intervals of compressor operation time The interval di is counted as the sum of the operating times of the output ot output on This mode is normally used in refrigeration systems with compressor stop in defrost cS Defrost cycle at each compressor stop The regulator starts a defrost cycle ev...

Страница 10: ...be set as EP exceeds the temperature set in parameter tE If this temperature is not reached within the time set in parameter dE the defrost will be interrupted To avoid unnecessary defrosting when the evaporator temperature is high the tS parameter allows setting the temperature referring to the evaporator probe below which the defrosts will be activated Therefore in the indicated modes if the tem...

Страница 11: ...nfigured with the o1 o2 o3 o4 parameters The buzzer can be configured to signal alarms by setting the parameter Bu 1 or 3 or 4 and always functions as an alarm that can be silenced This means that when activated it can be deactivated by briefly pressing any key Alarms can be configured to signal them by configuring the outputs The possible alarms that can be configured are the following On When yo...

Страница 12: ...e to show the initials oP on the display When the door open alarm intervenes the normally activated outputs fans or fans compressor are also deactivated 5 10 4 VOLTAGE CONTROL ALARM The parameters related to the voltage control alarm functions are found in the UA folder The B4U can automatically deactivate the control outputs when the mains voltage measured by the B4U through its power supply is l...

Страница 13: ...e SP S Parameters Relative to the Set Point 1 SH Turbo Set Point or Minimum Set point and Superheat Set point in HC mode 99 HS 4 0 2 SE Economic Set Point maximum set point LS 99 8 0 3 S1 Set Point SE SH 4 0 In i Parameters related to inputs 4 uP Measurement unit and resolution decimal point C0 C with resolution 1 F0 F with 1 resolution C1 C with 0 1 resolution F1 F with 0 1 resolution C0 F0 C1 F1...

Страница 14: ... 0 29 Ei Interval between defrosts in case of evaporator probe error oF 01 59 min 01 99 hrs 4 30 EE Defrost duration in case of evaporator probe error oF 01 59 sec 01 99 min 20 31 tS Temperature from which the defrost starts 99 9 9 9 9 10 99 C F 2 0 32 tF Temperature that forces the start of the evaporator defrost 99 9 9 9 9 10 99 C F 99 33 St Defrost start delay due to evaporator temperature oF 0...

Страница 15: ...1 2Y Temperature alarm type 2 see 1y 1 2 3 4 5 6 7 8 9 10 3 62 2H High temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 63 2L Low temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 64 2d 2H and 2L alarm hysteresis 0 0 9 9 30 C F 1 0 65 2t Alarm delay 2H and 2L oF 01 59 sec 01 99 min oF 66 2P Temperature alarm delay time 2 on connection oF 01 59 min 01 99 hrs 2 67 2A Action of alarms 2 on the...

Страница 16: ...ify the correct functioning of the probe it is useful to have the ohm values of the probes EP Possible anomaly in the EEPROM memory Press the SET key Turn the device off and on Err Fatal Device Memory Error Replace the device or send it in for possible repair 7 2 CLEANING It is recommended to clean the B4U only with a cloth slightly dampened with water or a non abrasive detergent and that does not...

Страница 17: ...MATE N LOK 250 removable connector Connection Display B4U Power Unit B4U 3 m MAX Through the cable with removable mini connectors Pollution degree 2 Ambient operating temperature 0 60 C Operating ambient humidity less than 95 RH non condensing Transport and storage temperature 25 60 C 8 3 FUNCTIONAL CHARACTERISTICS Temperature control ON OFF Defrost control by intervals or by temperature with elec...