After closing the door, the time “Et” elapses and the Economic Set 

Point  “SE”  is  activated;  Setting  in  the  parameter  "tt"  the  maximum 
time that you want to allow operation in Economy mode with the door 
closed (switching from Economy to Normal mode). 

 

 

 
Example of automatic ECONOMIC-NORMAL mode operation.  
During  working  hours,  the  door  is  opened  frequently  and  the  B4U 
remains in NORMAL mode.  
After the "Et" time has elapsed and the door has been closed for that 
time, the B4U switches to ECONOMY mode. As soon as the door is 
reopened, the B4U returns to normal mode. 
 

For  this  automatic  change  function  you  must  use  a  digital  input 
configured as

"1F / 2F / 3F / 4F" = 1, 2 or 3 (door open input). 

If "Et" = oF, 

the change from ECONOMIC mode to NORMAL through 

digital input (configured as open door) will be disabled

If "tt" = oF, 

the change from ECONOMIC mode to NORMAL for the 

maximum time allowed in ECONOMIC mode with the door closed will 
be disabled

 

 

 

(

1) - The time Et is reset every time the door is opened. In the case 

of the example, the door is always closed. 
(2) - Time tt stops when the door is opened and the B4U immediately 
switches to NORMAL mode. In the case of the example, the door is 
always closed. 
 

When entering ECONOMY mode, the initials "Ec" will be shown on 
the display. 
In the event that the cabinet light is also used (output configured as 
“L1”), the ECONOMIC mode selection is always associated with the 
function of deactivating the auxiliary output.

 

 

“TURBO-NORMAL-ECONOMIC” MODE OPERATION:

  

The TURBO mode can be used manually when a rapid decrease in 
product temperature is needed after the refrigerator is open. 
Instead,  it  can  be  used  automatically  to  allow  product  temperature 
recovery at the end of ECONOMY operation. 
 
TURBO mode can be switched manually: 
- Through digital input if parameter "1F / 2F / 3F / 4F" = 8 
 
 
TURBO mode can be switched automatically: 
- Exiting ECONOMIC mode (only if "HC" = C3) 
-  Every  time  the  B4U is started  (only  if "HC"  =  C3  and  Pr1 greater 
than SE + Ed). 
In order for the TURBO mode to be automatically switched off, the 
"tC"  time  must  be  expired  or,  if  not,  manually  through  the 
programmed key  or  digital input,  and  the  B4U will  return  to normal 
mode. 
When  entering  TURBO 

mode,  the  initials  “tr”  will  appear  on  the 

display alternating, every 10 seconds, with the normal screen. 
 
Setting "HC" = C3 the operating cycle is as follows: 
When turned on, the B4U automatically goes into the mode it was in 
before  shutting  down  (Normal  or  ECO)  unless  the  start-up 

temperature is higher than SE + Ed. In this case, a TURBO cycle is 
automatically started. 
After  the  time  “tC”,  the  B4U  automatically  switches  to  NORMAL 
mode. 
If  the  door  is  opened  frequently,  the  B4U  will  switch  to  NORMAL 
mode,  if  instead  the  door  is  not  opened  during  the  "Et"  time,  it  will 
automatically switch to ECONOMY mode. 
The B4U remains in ECONOMY mode until the door is reopened or, 
if configured, until the "tt" timeout. 
When  it  exits  the  ECONOMY  mode,  the  B4U  performs  a  TURBO 
cycle to recover the temperature of the products, then returns to the 
NORMAL operating mode, and so on. 
 

 

 

(

1) - The time Et is reset every time the door is opened. In the case 

of the example, the door is always closed. 
(2) - Time tt stops when the door is opened and the B4U immediately 
switches  to  TURBO  mode. In the  case  of  the  example,  the door  is 
always closed. 

 
 

5.3 - PROBE INPUTS CONFIGURATION AND DISPLAY 

The  parameters  related  to  the  configuration  of  the  measurement 
inputs  are  found  in  the  group  "-In".  Using  the  parameter  "uP"  it  is 
possible to select the temperature measurement unit and the desired 
measurement resolution (C0 = ° C / 1 °; C1 = ° C / 0.1 °; F0 = ° F / 1 
°; F1 = ° F / 0.1 °). 
The  B4U  allows  the  measurement  to  be  calibrated,  which  can  be 
used  to  re-calibrate  the  equipment,  according  to  the  needs  of  the 
application, by means of the parameter "C1" (input Pr1), "C2" (input 
Pr2) and "C3" (input Pr3 ).  
Parameters "P2" and "P3" allow selecting the use of the inputs by the 
B4U according to the following possibilities:  
= EP - Evaporator probe: the probe functions to control defrosts and 
evaporator fans.  
= Au - Auxiliary probe: It can be used as a display probe although it 
is also possible to associate it with temperature alarms (Possibility of 
using: product probe, anti-freeze probe, etc.) 
= cd - Condenser probe: It can be used as a display probe although 
it is also possible to associate it with temperature alarms, so that it 
signals alarms related to condenser malfunction (eg dirty / plugged 
condenser). 
= dG - Digital input (see digital input functions) 
If the input is not used, set "P2 and P3" = oF in the In folder. 
It is not possible to configure the two inputs for the same function. If 
the two inputs were configured for the same function, only the input 
with the lower value will act. 
Through  the  "Ft"  parameter  it  is  possible  to  set  a  software  filter 
relative to the measurement of the input value, so that we can reduce 
the sensitivity and the rapid variation in temperature (increasing the 
sampling time). 
In addition to this filter, there are 2 other similar filters, but they are 
used  only  to  show  the  measurement  of  the  Pr1  probe  both  for  the 
increase (parameter "du") and for the decrease (parameter "dd") and 
thus avoid showing a rapid change in temperature. 
The filter blocks the maximum reduction displayed at 0.1 ° every "dd" 
second and the maximum increase displayed every "du" second. 
At each connection, the filters are reset naturally. 
In order to visualize the filtered measurement of Pr1, we will use the 
parameter "dS" = F1, otherwise we will program "dS" = P1. 
With  the  parameter  "dS"  it  is  possible  to  establish  the  standard 
display of the screen between these options:  

P1

: Measurement of the Pr1 probe. 

P2

: Measurement of the Pr2 probe.  

P3

: Measurement of the Pr3 probe.  

Содержание B4U

Страница 1: ...ONNECTION 5 FUNCTIONING 5 1 ON STAND BY FUNCTION 5 2 NORMAL ECONOMIC AND TURBO OPERATING MODES 5 3 PROBE INPUTS AND DISPLAY CONFIGURATION 5 4 DIGITAL INPUTS CONFIGURATION 5 5 CONFIGURATION OF THE OUTPUTS AND BUZZER 5 6 TEMPERATURE REGULATION 5 7 COMPRESSOR PROTECTION AND START DELAY FUNCTION 5 8 DEFROST CONTROL 5 8 1 AUTOMATIC DEFROST 5 8 2 MANUAL DEFROST 5 8 3 DEFROST END 5 8 4 INTERVAL AND DURAT...

Страница 2: ...be configured 3 DOWN AUX 2 key In normal operating mode pressing and releasing allows quick access to the Set Point selection and modification mode Pressing for 3 seconds allows activating deactivating the configured output configured as A2 anti fog heating elements In the programming and display modes of the temperature measured by the room probe the evaporator temperature P1 and P2 and in additi...

Страница 3: ...the PP parameter within the tS group To have this protection available we will program the desired password number in the PP parameter Once the protection is activated to access the parameter menu press the ON OFF LIGHT keys simultaneously for 5 seconds and the display will show rP press the LIGHT key and the display will show 0 At this point using the UP and DOWN keys we will establish the passwo...

Страница 4: ...hat instant To exit the variables display mode we will not press any of the 4 keys for approximately 10 seconds 3 WARNINGS FOR USE 3 1 PERMITTED USE The B4U has been designed as a measuring and regulating device in accordance with EN 60730 1 for operation at altitudes up to 2000m The use of the B4U in applications not expressly provided for in the aforementioned standard must include all appropria...

Страница 5: ...eople things or animals 4 2 1 ELECTRICAL WIRING DIAGRAM Color legend Cable Strip 1 Brown 2 White 3 Green 4 Blue 5 Red 6 Black 5 OPERATION 5 1 ON STAND BY FUNCTION The B4U once turned on can take 2 different conditions ON It means that it works with the normal control functions STAND BY It means that the controller does not operate with any control function and the display turns off the Stand by LE...

Страница 6: ...g the Et time it will automatically switch to ECONOMY mode The B4U remains in ECONOMY mode until the door is reopened or if configured until the tt timeout When it exits the ECONOMY mode the B4U performs a TURBO cycle to recover the temperature of the products then returns to the NORMAL operating mode and so on 1 The time Et is reset every time the door is opened In the case of the example the doo...

Страница 7: ...ATION OF THE OUTPUTS AND BUZZER The parameters related to the configuration of the outputs are contained in the group Ou The outputs of the B4U can be configured through the parameters o1 o2 o3 and o4 with the following functions ot Compressor Solenoid Control or Cooling Element dF Control of defrost heaters Fn Evaporator fans control Au Auxiliary output control En Allows the Control of a silencea...

Страница 8: ...with Heating action In this case the regulation Set point for the ot output will be SP SE SH while for the HE output it is through the Set SH The regulation differential for the ot output is the active one between d or Ed or Hd is assumed automatically by the B4U to have positive values in the cooling action while for the HE output the differential will be Hd considered with negative values during...

Страница 9: ...counts the time since the B4U was started This mode is the one currently used in refrigeration systems ct At intervals of compressor operation time The interval di is counted as the sum of the operating times of the output ot output on This mode is normally used in refrigeration systems with compressor stop in defrost cS Defrost cycle at each compressor stop The regulator starts a defrost cycle ev...

Страница 10: ...be set as EP exceeds the temperature set in parameter tE If this temperature is not reached within the time set in parameter dE the defrost will be interrupted To avoid unnecessary defrosting when the evaporator temperature is high the tS parameter allows setting the temperature referring to the evaporator probe below which the defrosts will be activated Therefore in the indicated modes if the tem...

Страница 11: ...nfigured with the o1 o2 o3 o4 parameters The buzzer can be configured to signal alarms by setting the parameter Bu 1 or 3 or 4 and always functions as an alarm that can be silenced This means that when activated it can be deactivated by briefly pressing any key Alarms can be configured to signal them by configuring the outputs The possible alarms that can be configured are the following On When yo...

Страница 12: ...e to show the initials oP on the display When the door open alarm intervenes the normally activated outputs fans or fans compressor are also deactivated 5 10 4 VOLTAGE CONTROL ALARM The parameters related to the voltage control alarm functions are found in the UA folder The B4U can automatically deactivate the control outputs when the mains voltage measured by the B4U through its power supply is l...

Страница 13: ...e SP S Parameters Relative to the Set Point 1 SH Turbo Set Point or Minimum Set point and Superheat Set point in HC mode 99 HS 4 0 2 SE Economic Set Point maximum set point LS 99 8 0 3 S1 Set Point SE SH 4 0 In i Parameters related to inputs 4 uP Measurement unit and resolution decimal point C0 C with resolution 1 F0 F with 1 resolution C1 C with 0 1 resolution F1 F with 0 1 resolution C0 F0 C1 F1...

Страница 14: ... 0 29 Ei Interval between defrosts in case of evaporator probe error oF 01 59 min 01 99 hrs 4 30 EE Defrost duration in case of evaporator probe error oF 01 59 sec 01 99 min 20 31 tS Temperature from which the defrost starts 99 9 9 9 9 10 99 C F 2 0 32 tF Temperature that forces the start of the evaporator defrost 99 9 9 9 9 10 99 C F 99 33 St Defrost start delay due to evaporator temperature oF 0...

Страница 15: ...1 2Y Temperature alarm type 2 see 1y 1 2 3 4 5 6 7 8 9 10 3 62 2H High temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 63 2L Low temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 64 2d 2H and 2L alarm hysteresis 0 0 9 9 30 C F 1 0 65 2t Alarm delay 2H and 2L oF 01 59 sec 01 99 min oF 66 2P Temperature alarm delay time 2 on connection oF 01 59 min 01 99 hrs 2 67 2A Action of alarms 2 on the...

Страница 16: ...ify the correct functioning of the probe it is useful to have the ohm values of the probes EP Possible anomaly in the EEPROM memory Press the SET key Turn the device off and on Err Fatal Device Memory Error Replace the device or send it in for possible repair 7 2 CLEANING It is recommended to clean the B4U only with a cloth slightly dampened with water or a non abrasive detergent and that does not...

Страница 17: ...MATE N LOK 250 removable connector Connection Display B4U Power Unit B4U 3 m MAX Through the cable with removable mini connectors Pollution degree 2 Ambient operating temperature 0 60 C Operating ambient humidity less than 95 RH non condensing Transport and storage temperature 25 60 C 8 3 FUNCTIONAL CHARACTERISTICS Temperature control ON OFF Defrost control by intervals or by temperature with elec...

Отзывы: