Osaka B4U Скачать руководство пользователя страница 2

OSAKA

 - USER MANUAL - B4U - v2 - PAG. 2

 

The 4 outputs can be used to control the compressor or temperature 
control  device,  the  anti-fog  heater,  the  evaporator  fans  and  a 
configurable auxiliary device (light, alarm, etc.) 
The  3  temperature  probe  inputs  can  be  used  for  cell  temperature 
regulation,  for  evaporator  temperature  measurement,  for  auxiliary 
temperature  measurement  (Product  temperature,  condenser 
temperature, etc.). 
There is always a digital input available on the Power Unit B4U and, 
as an alternative to the temperature probe inputs Pr2 and Pr3, two 
other digital inputs can be configured. 
The  digital  inputs  can  be  configured  to  perform  various  functions, 
such as door signal, defrost commands, selection of a different set of 
temperature regulation, signaling of an external alarm, activation of a 
continuous cycle, activation of the auxiliary output, etc. 
In addition, the B4U is equipped with a voltage alarm that turns off 
the outputs when the voltage is too high or too low. 
The  selection  of  the  functions  and  the  programming  of  the 
parameters are carried out through the 4 capacitive keys on the B4U 
Display. 
The connection between the Display B4U and the Power Unit B4U is 
made using the LIN cable, a small three-pole cable included. 

 

1.2  -  DESCRIPTION  OF  THE  B4U  DISPLAY  AND  THE  B4U 
POWER UNIT 
 

 

 
 

1  -  ON  /  OFF  key:

  Pressing  for  1  second  turns  the  B4U  on  /  off 

(Stand-by). 
Pressing  for  5  seconds  together  with  the  LIGHT  key  (4),  allows 
access to the parameter programming mode. 
Pressing  for  5  seconds  together  with  the  DOWN  key  (3),  allows 
access to the display mode of the temperature measured by the room 
probe, the evaporator temperature (P1 and P2) and in addition to the 
maximum (Ht) and minimum (Lt) temperature recorded by the team. 
Inside  the  programming  mode  by  pressing  for  3  seconds  and 
releasing, we exit and return to normal operation. 
 

2  -  UP  /  DEFROST  key:

  In  normal  operating  mode,  pressing  and 

releasing  allows  quick  access  to  the  Set  Point  selection  and 
modification mode. 
Pressing  for  5  seconds  allows  activating  /  deactivating  a  manual 
defrost cycle. 
In the programming and display modes of the temperature measured 
by the room probe, the evaporator temperature (P1 and P2) and in 
addition  to  the  maximum  (Ht)  and  minimum  (Lt)  temperature 
registered  by  the  equipment,  is  used  to  select  the  parameters  and 
increase the values to be configured. 
 

3  -  DOWN  /  AUX  2  key:

  In  normal  operating  mode,  pressing  and 

releasing  allows  quick  access  to  the  Set  Point  selection  and 
modification mode. 
Pressing for 3 seconds allows activating / deactivating the configured 
output configured as A2 (anti-fog heating elements). 
In the programming and display modes of the temperature measured 
by the room probe, the evaporator temperature (P1 and P2) and in 
addition  to  the  maximum  (Ht)  and  minimum  (Lt)  temperature 
registered  by  the  equipment,  is  used  to  select  the  parameters  and 
decrease the values to configure. 
 
 

4  -  LIGHT  button:

  Pressing  for  2  seconds  allows  you  to  manually 

activate / deactivate the output configured as light (Auxiliary). 
Pressed for 5 seconds, together with the Stand-by key (1), it allows 
access to the parameter programming mode. 
In programming mode it is used to access parameter editing and to 
confirm values. 
In programming mode, it can be used in conjunction with the UP key 
to modify the parameter programming level. 
Pressed for 3 seconds when the keypad is locked, allows the keypad 
to be unlocked. 
 

5 - Led SET

: In normal operation mode, lights up when a button is 

pressed to indicate that it has been pressed. 
In  programming  mode  it  is  used  to  indicate  the  level  of  parameter 
programming. 
 

6  -  Led  OUT  -  COOL:

Indicates  the  status  of  the  regulation  output 

(compressor  or  temperature  control  device);  output  on  (on),  output 
off (off), or output failed (flashing). 
 

7 - Led DEF

: Indicates that a defrost is being carried out (on) or in a 

dripping state (intermittent). 
 

8 - FAN Led:

 Indicates the status of the evaporator fan output: ON, 

OFF, or failed (flashing). 
 

9 - Led AUX2:

 Indicates the activation of the output configured as A2 

(anti-fog heating elements). 
 

10  -  Led  Stand-By  /  Decimal  point:

When  the  B4U is  in  Stand-By 

mode, it is the only LED that remains lit. In normal operation it is used 
as a decimal point separator. 
 

11 - Unit of Measure Led:

 Indicates the temperature measurement 

unit in use. 

 
 

POWER UNIT B4U 

 

 

1 - Led ON

: When it is turned on, for a few seconds, the led shows 

solid red indicating that the control is starting. Once started, the LED 
starts to blink between a weak red and a more intense one, indicating 
the correct operation of the control unit. 
 

2  -  TTL  communication  port

:  Used  to  connect  to  the  following 

devices: 

USB Key

: to transfer operating parameters to and from the B4U.  

Key TTL-RS

: for MODBUS communication via RS485. 

X2

Remote display that shows the temperature measured by the Pr1 

probe.

 

 

3 - LIN communication port

: used to communicate the Display B4U 

with the Power Unit B4U. 
 
 
 
 
 
 
 
 

Содержание B4U

Страница 1: ...ONNECTION 5 FUNCTIONING 5 1 ON STAND BY FUNCTION 5 2 NORMAL ECONOMIC AND TURBO OPERATING MODES 5 3 PROBE INPUTS AND DISPLAY CONFIGURATION 5 4 DIGITAL INPUTS CONFIGURATION 5 5 CONFIGURATION OF THE OUTPUTS AND BUZZER 5 6 TEMPERATURE REGULATION 5 7 COMPRESSOR PROTECTION AND START DELAY FUNCTION 5 8 DEFROST CONTROL 5 8 1 AUTOMATIC DEFROST 5 8 2 MANUAL DEFROST 5 8 3 DEFROST END 5 8 4 INTERVAL AND DURAT...

Страница 2: ...be configured 3 DOWN AUX 2 key In normal operating mode pressing and releasing allows quick access to the Set Point selection and modification mode Pressing for 3 seconds allows activating deactivating the configured output configured as A2 anti fog heating elements In the programming and display modes of the temperature measured by the room probe the evaporator temperature P1 and P2 and in additi...

Страница 3: ...the PP parameter within the tS group To have this protection available we will program the desired password number in the PP parameter Once the protection is activated to access the parameter menu press the ON OFF LIGHT keys simultaneously for 5 seconds and the display will show rP press the LIGHT key and the display will show 0 At this point using the UP and DOWN keys we will establish the passwo...

Страница 4: ...hat instant To exit the variables display mode we will not press any of the 4 keys for approximately 10 seconds 3 WARNINGS FOR USE 3 1 PERMITTED USE The B4U has been designed as a measuring and regulating device in accordance with EN 60730 1 for operation at altitudes up to 2000m The use of the B4U in applications not expressly provided for in the aforementioned standard must include all appropria...

Страница 5: ...eople things or animals 4 2 1 ELECTRICAL WIRING DIAGRAM Color legend Cable Strip 1 Brown 2 White 3 Green 4 Blue 5 Red 6 Black 5 OPERATION 5 1 ON STAND BY FUNCTION The B4U once turned on can take 2 different conditions ON It means that it works with the normal control functions STAND BY It means that the controller does not operate with any control function and the display turns off the Stand by LE...

Страница 6: ...g the Et time it will automatically switch to ECONOMY mode The B4U remains in ECONOMY mode until the door is reopened or if configured until the tt timeout When it exits the ECONOMY mode the B4U performs a TURBO cycle to recover the temperature of the products then returns to the NORMAL operating mode and so on 1 The time Et is reset every time the door is opened In the case of the example the doo...

Страница 7: ...ATION OF THE OUTPUTS AND BUZZER The parameters related to the configuration of the outputs are contained in the group Ou The outputs of the B4U can be configured through the parameters o1 o2 o3 and o4 with the following functions ot Compressor Solenoid Control or Cooling Element dF Control of defrost heaters Fn Evaporator fans control Au Auxiliary output control En Allows the Control of a silencea...

Страница 8: ...with Heating action In this case the regulation Set point for the ot output will be SP SE SH while for the HE output it is through the Set SH The regulation differential for the ot output is the active one between d or Ed or Hd is assumed automatically by the B4U to have positive values in the cooling action while for the HE output the differential will be Hd considered with negative values during...

Страница 9: ...counts the time since the B4U was started This mode is the one currently used in refrigeration systems ct At intervals of compressor operation time The interval di is counted as the sum of the operating times of the output ot output on This mode is normally used in refrigeration systems with compressor stop in defrost cS Defrost cycle at each compressor stop The regulator starts a defrost cycle ev...

Страница 10: ...be set as EP exceeds the temperature set in parameter tE If this temperature is not reached within the time set in parameter dE the defrost will be interrupted To avoid unnecessary defrosting when the evaporator temperature is high the tS parameter allows setting the temperature referring to the evaporator probe below which the defrosts will be activated Therefore in the indicated modes if the tem...

Страница 11: ...nfigured with the o1 o2 o3 o4 parameters The buzzer can be configured to signal alarms by setting the parameter Bu 1 or 3 or 4 and always functions as an alarm that can be silenced This means that when activated it can be deactivated by briefly pressing any key Alarms can be configured to signal them by configuring the outputs The possible alarms that can be configured are the following On When yo...

Страница 12: ...e to show the initials oP on the display When the door open alarm intervenes the normally activated outputs fans or fans compressor are also deactivated 5 10 4 VOLTAGE CONTROL ALARM The parameters related to the voltage control alarm functions are found in the UA folder The B4U can automatically deactivate the control outputs when the mains voltage measured by the B4U through its power supply is l...

Страница 13: ...e SP S Parameters Relative to the Set Point 1 SH Turbo Set Point or Minimum Set point and Superheat Set point in HC mode 99 HS 4 0 2 SE Economic Set Point maximum set point LS 99 8 0 3 S1 Set Point SE SH 4 0 In i Parameters related to inputs 4 uP Measurement unit and resolution decimal point C0 C with resolution 1 F0 F with 1 resolution C1 C with 0 1 resolution F1 F with 0 1 resolution C0 F0 C1 F1...

Страница 14: ... 0 29 Ei Interval between defrosts in case of evaporator probe error oF 01 59 min 01 99 hrs 4 30 EE Defrost duration in case of evaporator probe error oF 01 59 sec 01 99 min 20 31 tS Temperature from which the defrost starts 99 9 9 9 9 10 99 C F 2 0 32 tF Temperature that forces the start of the evaporator defrost 99 9 9 9 9 10 99 C F 99 33 St Defrost start delay due to evaporator temperature oF 0...

Страница 15: ...1 2Y Temperature alarm type 2 see 1y 1 2 3 4 5 6 7 8 9 10 3 62 2H High temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 63 2L Low temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 64 2d 2H and 2L alarm hysteresis 0 0 9 9 30 C F 1 0 65 2t Alarm delay 2H and 2L oF 01 59 sec 01 99 min oF 66 2P Temperature alarm delay time 2 on connection oF 01 59 min 01 99 hrs 2 67 2A Action of alarms 2 on the...

Страница 16: ...ify the correct functioning of the probe it is useful to have the ohm values of the probes EP Possible anomaly in the EEPROM memory Press the SET key Turn the device off and on Err Fatal Device Memory Error Replace the device or send it in for possible repair 7 2 CLEANING It is recommended to clean the B4U only with a cloth slightly dampened with water or a non abrasive detergent and that does not...

Страница 17: ...MATE N LOK 250 removable connector Connection Display B4U Power Unit B4U 3 m MAX Through the cable with removable mini connectors Pollution degree 2 Ambient operating temperature 0 60 C Operating ambient humidity less than 95 RH non condensing Transport and storage temperature 25 60 C 8 3 FUNCTIONAL CHARACTERISTICS Temperature control ON OFF Defrost control by intervals or by temperature with elec...