IG-245-EN version 05; 13/02/2020
26
Installation
General Instructions
mb
.m
FIG_IG245 -01-014.1
1
Bolt M16 x 60 approx. 8.8 DIN-933
2
Washer 16 DIN-125
3
Washer 16 DIN-127
4
M16 Female anchor (recommended to secure it to the slab
mesh)
5
Reinforced concrete slab
6
Compacted earth
7
Access hole for medium voltage cables
8
Cable access hole (for MV/MV power transformer only)
a
1203 mm (applies in
mb
.m-3f)
b
1621 mm (applies in
mb
.m-4f)
Figure 5.4.
Recommended dimensions in millimetres of the concrete slab to support the
mb
.m
with transformer ≥ 2500 kVA
Make sure the supporting slab is correctly levelled
before placing the
mb
.m on it
This drawing and the dimensions shown are merely
for the purposes of illustration. The project's detailed
drawings will take precedence. For further information,
please contact
Ormazabal
.
Содержание velatia mb.m Series