2.
Close the right grounding disconnector.
Figure 7.33.
Left busbar grounding sequence (ii)
3.
Connect the vacuum interrupter.
Figure 7.34.
Left busbar grounding disconnection sequence (iii)
To open the grounding connection of the left busbar,
reverse the sequence of operation.
IG-196-US version 03; 13/04/2021
40
Operation and commissioning sequence
General instructions
cpg
.0 NEW MODEL: Medium-voltage
metal-enclosed switchgear with full insulation in gas,
up to 38 kV in accordance with IEEE Standards