If the spring charging status indicator shows DISCHARGED.
Slide the access interlocking cover to the left and insert the
spring charging lever.
Move vertically, up and down, several times until the
indication changes to springs CHARGED.
Figure 7.20.
Spring charging sequence
Figure 7.21.
Springs charged indication
Press the “I” pushbutton to close the vacuum interrupter.
The vacuum interrupter status indicator shows CLOSED.
Figure 7.22.
Vacuum interrupter closed indication
IG-196-US version 03; 13/04/2021
34
Operation and commissioning sequence
General instructions
cpg
.0 NEW MODEL: Medium-voltage
metal-enclosed switchgear with full insulation in gas,
up to 38 kV in accordance with IEEE Standards
Содержание cpg.0-c
Страница 59: ......