If the spring charging status indicator on the circuit breaker
shows DISCHARGED: move the access interlock cover to the
right and insert the spring charging lever.
Turn COUNTERCLOCKWISE approximately one and a half
turns until the indication changes to springs CHARGED.
Figure 7.11.
Spring charging sequence
Figure 7.12.
Springs charged indication
Press the “I” pushbutton to close the vacuum interrupter.
The vacuum interrupter status indicator shows CLOSED.
Figure 7.13.
Vacuum interrupter closed indication
IG-196-US version 03; 13/04/2021
31
General instructions
cpg
.0 NEW MODEL: Medium-voltage
metal-enclosed switchgear with full insulation in gas,
up to 38 kV in accordance with IEEE Standards
Operation and commissioning sequence