4. Installation

4.1. Connections to the chimney

4.2. Hydraulic connections

Radiators

Safety

valve

Differential pressure

valve (*)

Insulation valve

Boiler

Heating

circulation

pump

Filling valve

Expansion

vessel

HYDRAULIC SCHEMA "HEATING ONLY" WITHOUT REGULATION

Insulation valve

* If all radiators are equipped with thermostatic valves, a differential pressure valve should be placed within the delivery and return

boilers.

IMPORTANT:
The start/return pipings of the installation may not in any case be from a diameter lower than 2" at least on a section of
200mm and this in order to ensure an optimal irrigation of the cast-iron elements constituting the heating body.

The boilers are designed to function in heating installations with hot water and forced circulation.

It is forbidden for the boilers to work in thermosiphon (without circulating pump).

The fitter must absolutely dimension the circulation pump to ensure a difference of temperature between the start and return
of the boiler of minimum 5°C and of maximum 35°C.

Beforeinstallingadevice,itishighlysuggestedthattheinstallerchecksthe conditionsofthechimney(boilertubecleaning
buffer,infiltratedairintake,cracks,etc.). Theboilerperformancerequiresrelativelylowfumetemperature.Particularcare
shouldbetakento theheatinsulatedand tight chimneys.Infact,anincorrecttightnessand insulationof thechimneyreduce
the fume temperature and cause the bistre event. To avoid this problem, it is possible to tube protect the ducts, i.e. heat-
insulate the draining duct. The tubing quality should be compliant with the used fuel.

Recommendationsforchimneyconnection
- keep the same section of the boiler outlet valve
- avoid sudden direction changes
- install the connecting protection sleeves with an ascending slope in the direction of the circulation (in particular, at the

nesting into the chimney)

- arrange a draining cup as near as possible to the boiler
-arrange some chimneysmadeof corrosion-proof materials
- connect the chimney from the back. The fume pipe should be properly nested (outside) and assure a perfect tightness.

Содержание Optimajor GLP S 3.0

Страница 1: ...Optimajor GLP S EXPORT OPTIMAJOR GLP S EXPORT 0111 00 OIL GASFIRED CENTRALHEATINGBOILER TECHNICALANDMAINTENANCEINSTRUCTIONS...

Страница 2: ...6 Spare parts 18 7 Maintenance 20 8 Guarantee conditions on Optimajor GLP S 20 Page Contents User s advices The boiler must be installed and commissioned by a registered installer in accordance with...

Страница 3: ...e calculated and carried out according to the standards in force the local obligations and the regulations of the manufacturer The hydraulic installations fuel or gases will be established according t...

Страница 4: ...48 1 84 7 60 3 101 9 72 5 119 84 7 136 2 96 6 153 3 109 2 Combustion circuit vol dm Water side losses mbar 1 7 0 9 2 7 1 4 3 9 2 5 3 2 7 6 9 3 5 8 7 4 4 Relative standby loss Water capacity l Packed...

Страница 5: ...edition of Clean Air Act 1993 should be observed To ensure safe operation of the boiler the chimney system shall be capable of the complete evacuation of the products of combustion at all times The e...

Страница 6: ...the thermal insulation and the mantle No leakage must occur during the water test Positioningthebottomrearfixingplate A onthecastiron block on the rear section Using2M8X10 DIN933 screw blocktherearpla...

Страница 7: ...ount the overall dimensions of the jacket Provide a coupling duct with a diameter of 200 mm Height of the axis of the duct 670 mm not including the base Place the chimney coupling duct Ensure the airt...

Страница 8: ...e filling of the heating circuit Verify and check the watertightness of all connections Rinse the installation by empying it Bring the pressure up to the level in accordance with the manometric height...

Страница 9: ...mp to ensure a difference of temperature between the start and return oftheboilerofminimum5 Cand ofmaximum35 C Beforeinstallingadevice itishighlysuggestedthattheinstallercheckstheconditionsofthechimne...

Страница 10: ...arenotpartofthescopeof our supply but are mentioned because requiredforagoodplantperformance If all the plant radiators are equipped with thermostatic valves a differential pressure valve should be pl...

Страница 11: ...f the hydraulic circuits is ensured apply the following sequence for the filling of the hot sanitary water circuit Z Z The fillingmust takeplace slowly the draincocksbeing openorunscrewed inorderto av...

Страница 12: ...age again Remark As far as Ecosets are concerned are the electrical connections of the circula tionpumpoftheheatingcircuitmadein the control box outisde the boiler control panel 4 3 Electricalconnecti...

Страница 13: ...ago range Climaticregulator delivered in option Lago Eco Lago E8 0634 In order to install this regulation it is necessary to interpose between the boiler connector block and the regulator a connection...

Страница 14: ...plug of connector A 4 Connect the 10 poles white connector on the connector block II of the regulator 5 Connect directly the following probes on the connector block I of the regulator AFS external pr...

Страница 15: ...P 12 poles plug of connector A 4 Connect the 10 poles white connector on the connector block II of the regulator 5 Connect directly the following probes on the connector block I of the regulator KFS b...

Страница 16: ...cuit USING LIGHTING put the boiler under tension via the main switch set the boiler thermostat at the desired temperature after a temperature setting of the installation make again a general purging a...

Страница 17: ...Page 17 19 6 Spare parts list Boiler Cast ironblock 20 21 26 12 11 10 13 14 15 16 17 19 18 23 24 25 22 32 37 36 38 30 34 33 31 32 31 35...

Страница 18: ...7 0 1 80 600 80940 22 4 M16 x 1060 tie bar n 8 0 1 80 600 81060 23 1 Reducing plug 1 1 4 3 4 1 60 110 10061 24 4 Plug 1 1 4 with square hole fig 596 1 60 100 30010 25 2 Eye bolt 1 80 121 10063 26 acc...

Страница 19: ...uted airincludingcorrosiveelementssuch as chlorine fluorine sulphur etc The use of water which is found to be unsuitable would also invalidate our guarantee 2 Our guarantee specified below commences o...

Отзывы: