Zone
Zone
VCB-X STATUS
VCB-X Operator Interface SD
58
VCB-X Status Screens
Status Screen 5 - Supply Air Temperature &
Active Setpoint
VCB-X v2.00 ID 101
Supply Temp: XXX.XX
Active Spt.: XXX.XX
Line 2 Current Supply Air Temperature
The Supply Air Temperature is always required. If a
Supply Air Temperature Sensor is not installed, the VCB-X
Controller will not operate correctly and will display 0°.
Line 3
Current Active Supply Air Setpoint
This is the Supply Air Setpoint for the mode that the
unit is currently operating in. If the Supply Air Reset is
con
fi
gured, this is the calculated setpoint based on the
current Reset Source conditions.
Status Screen 6 - Cooling Enabled
VCB-X v2.00 ID 101
Cooling Enabled
YES/NO
Line 3 Cooling Enabled YES/NO
This line will display YES if Cooling is enabled and
NO if the Cooling is not enabled. Cooling is enabled if the
Outdoor Air Temperature is above the Compressor Cooling
Lockout.
Status Screen 7 - Cooling Outputs - Active
Stages and Mod Cool Position
VCB-X v2.00 ID 101
Cooling Outputs
Active Stages: XX
Mod Cool Pos.: XXX%
Line 2 Cooling Active Stages
This line will display the number of stages of Cooling
that are currently active.
Line 3 Current Modulating Cooling Output Signal Percentage
Indicates the percentage output signal to the Digital
Scroll Compressor or a Chilled Water Valve.
Status Screen 8 - Compressor Discharge
Temperature
VCB-X v2.00 ID 101
Compressor Discharge
Temp: XXX.XX
Line 3 Compressor Discharge Temperature
This line will display the current compressor discharge
temperature if your HVAC unit is using a Digital Scroll
Compressor. If this temperature rises above 268
˚
F
(131.11
˚
C), the digital compressor will be locked out.
Status Screen 9 - Heating Enabled
VCB-X v2.00 ID 101
Heating Enabled
YES/NO
If this is
not
a Heat Pump unit, the screen will appear as shown above.
Line 3 Heating Enabled YES/NO
This line will display YES if Heating is enabled and No if
Heating is not enabled. Heating is enabled if the Outdoor
Air Temperature is below the Heating Lockout.
VCB-X v2.00 ID 101
HP Heat Enabled: YES
HP Aux Enabled: YES
HP Emg Enabled: NO
If this is
a Heat Pump unit, the screen will appear as shown above.
Line 2
HP Heat Enabled
This line refers to Compressor Heating and will display
YES if the Outdoor Air Temperature is above the
Compressor Heating Lockout and below the Heating
Lockout. Otherwise, it will display NO.
Line 3 HP Aux Enabled
This line refers to Heat Pump Auxiliary Heat and will
display YES if the Outdoor Air Temperature is below
Heating Lockout. Otherwise, it will display NO.
Line 4 HP Emg Enabled
This line refers to Heat Pump Emergency Heat and will
display YES if the Outdoor Air Temperature is below the
Compressor Heating Lockout. Otherwise, it will display
NO.