Zone

Zone

VCB-X CONFIGURATION

    VCB-X Operator Interface SD

42

Description

Minimum

Default

Maximum

Unoccupied Offsets 
Cooling

0ºF

(0

º

C)

30ºF 

(16.6ºC)

30ºF

(16.6ºC)

Unoccupied Offsets 
Heating

0ºF

(0

º

C)

30ºF 

(16.6ºC)

30ºF

(16.6ºC)

Setpoint Screen #4 -      Mode Deadband

VCBX Spts ID 101

Mode Deadband

Setpt: 1.0

º

F

This Setpoint is added to and subtracted from the HVAC Mode Setpoints 
to determine when the unit enters and leaves a mode of operation.

Description

Minimum

Default

Maximum

HVAC Mode Select 
Deadband

1ºF

(.6ºC)

1ºF

(.6ºC)

10ºF

(5.5ºC)

Setpoint Screen #5 -      Space Sensor Slide 

Adjust

VCBX Spts ID 101

Space Sensor 

Slide Adj: 0

If the VCB-X has a Space Temperature Sensor with the Slide Adjust 
option installed, the HVAC Mode Enable Heating and Cooling Setpoints 
can be offset by the HVAC Mode Sensor Slide Offset Setpoint value.  
When the Slide Adjust bar is in the middle, no offset will occur. If the 
Slide Adjust bar is moved all the way to the top of the Sensor, the Heat-
ing and Cooling Setpoints will be raised by the Setpoint value you have 
entered. If the Slide Adjust bar is moved all the way down to the bottom 
of the Sensor, the Heating and Cooling Setpoints will be lowered by the 
Setpoint value you have entered.

If the Space Temperature is the SAT Reset Source, then the Slide Adjust 
will adjust the HVAC Mode Enable Setpoints and the SAT Reset Source 
Setpoints simultaneously.

Description

Minimum

Default

Maximum

Space Sensor
Slide Adjust

 0ºF

(0

º

C)

0ºF

(0

º

C)

10ºF

(5.5ºC)

Space Temperature Control of High Percentage Outside Air Units

This option allows for Space Temperature control of 100% Outside Air 
MUA Units or units with a high percentage of Outdoor Air (normally 
50% or greater).  For this application you would con

fi

 gure “Space Tem-

perature w/High OA %” for the Controlling Sensor option. The intent 
of this sequence is to allow Space Temperature control of the unit while 
preventing the dumping of hot or cold outside air into the space during 
the Space Vent Mode of operation.

Once the Space Temperature is satis

fi

 ed, before switching to Vent Mode, 

the controller compares the Outside Air Temperature to these Hood On 
HVAC setpoints to determine if a continued demand for heating or cool-
ing is required to prevent dumping.  If there is no demand, the VCB-X 
Controller switches to Vent Mode.  If the Outside Air Temperature is 
greater than the Hood On HVAC Cooling Setpoint or less than the Hood 
On HVAC Heating Setpoint, plus the Occupied Deadband, the VCB-X 
Controller will continue mechanical cooling or heating operation and 
stage it as necessary to maintain the Vent Mode Supply Air Setpoint 
(Calculated to be halfway between the Mode Enable Setpoints). A call 
for Heating or Cooling from the Space Sensor will cancel this temper-
ing operation.

Supply Air Tempering

—In the VAV Supply Air Tempering application 

(see the 

VCB-X Controller Technical Guide

 for full details), the unit will 

enter the Cooling and Heating Modes based on the outdoor temperature.  
The outdoor Heating and Cooling Setpoints are con

fi

 gured using the 

Hood On OAT Cooling and Heating Setpoints on this screen.  In this 
application, the economizer can operate in any mode, if necessary, to 
achieve the supply air setpoint. Night Setback Heating and Morning 
Warm Up are both controlled to the Warm Up Supply Air Setpoint.

NOTE:

  For this Supply Air Tempering application, the Heating Supply 

Air Setpoint on 

Setpoint Screen #21

 should be set at least 2°F 

below

 the 

Cooling Supply Air Setpoint. 

Description

Minimum

Default

Maximum

 Hood On OAT Cool

1ºF 

(-17.2ºC)

75ºF 

(24ºC)

110ºF

(43.3ºC)

 Hood On OAT Heat

1ºF

(-17.2ºC)

70ºF 

(21ºC) 

110ºF

(43.3ºC)

Setpoint Screen #3 -      Unoccupied Offsets - 

 Cooling &  Heating

VCBX Spts ID 101

Unoccupied Offsets

Cooling: 30.0

º

F

Heating: 30.0

º

F

During the Unoccupied Mode of Operation, these Setpoints spread the 
HVAC Mode Setpoints out by this user-adjustable amount. Use only 
positive numbers for these Setpoints. If you do not want Cooling or 
Heating to operate during the Unoccupied Mode, use the default setting 
of 30°F for these setpoints. 

VCB-X Setpoint Screens

Содержание OE335-26B-VCBZ

Страница 1: ...ersion 2 00 up VAV Zone Controller Code SS1001 SS1005 SS1025 Requires Modular Service Tool SD Code SS1063 Requires Modular System Manager SD Code SS1064 VCB X Controller Operator Interface SD Technica...

Страница 2: ...orioncontrols com AAON is a registered trademark of AAON Inc Tulsa OK WattMaster Controls Inc assumes no responsibility for errors or omissions This document is subject to change without notice Form O...

Страница 3: ...op Search and System Alarm Search 20 Unit Alarm Search Override Search 21 Schedules Holidays 22 Schedule Override 23 PROGRAMMING 24 VCB X Configuration Screen Index 24 Configuring VCB X Controllers 25...

Страница 4: ...nglish language messages Menu driven programming allows for easy setup and operation without the need for specialized training The Modular Service Tool is supplied with a programmable 4 Gigabyte SD me...

Страница 5: ...ular Service Tool Be sure that the Modular Service Tool has fresh batteries installed or that it is connected to a power source using the supplied power pack before attempting any programming of the c...

Страница 6: ...system alarm conditions and override initiations Protection from unauthorized users is provided by the System Manager s integral multi level passcode authorization programming On a Networked System t...

Страница 7: ...ications and power wiring to the Modular System Manager from a 24 VAC power source and to the HVAC unit controller communication wiring terminals See Figure 6 on page 9 for wiring details If the suppl...

Страница 8: ...Power Comm Board From The Unit Controller MiniLink PD Or Another Power Comm Board Line Voltage 24VAC R SH T R SH T R SH T R SH T All Comm Loop Wiring Is Straight Thru Local Loop RS 485 9600 Baud Local...

Страница 9: ...s Modular System Manager SD Back View NOTE For Stand Alone Installations No CommLink or MiniLink All TERM Jumpers Must Be ON For All Applications With CommLink s Or MiniLink s All Jumpers Must Be OFF...

Страница 10: ...a entry field and start over This key also turns off the power to the Service Tool when on the Main Screen Minus If a setpoint with a negative value is required press this key for the minus sign DEC P...

Страница 11: ...amming the Time From the Setup Screen shown below press 1 on your keypad to access the Set Time Date Screens You may have to press NEXT to access this screen 1 Set Time Date 2 Communications NEXT More...

Страница 12: ...lection press ENTER The following screen will appear You Have Changed The System Mode Press Any Key To Continue Press any key to continue The Setup Screen will appear as shown below 1 Set Time Date 2...

Страница 13: ...etermine and report any controllers that are currently operating in an override condition on a specific Loop by entering a Loop ID number and then doing a search NOTE When you press the OVERRIDES butt...

Страница 14: ...the holiday starts and the day the holiday ends If your holiday only lasts one day simply set both the Start Day and the Stop Day to the same value Remember to combine the month and day into a single...

Страница 15: ...ride VCB X Ovrd Schedule Override Enter Override X 0 Auto 1 ON 2 OFF If you want to force the unit to operate in a continuous Occupied or Unoccupied mode select this menu item to activate the desired...

Страница 16: ...ear the data entry field and start over Minus If a setpoint with a negative value is required press this key for the minus sign DEC Press this key when entering data that re quires a decimal point Use...

Страница 17: ...light savings you will need to manually adjust the time twice a year Initialization Setting the Time Date Programming the Time From the Setup Screen shown below press 1 on your keypad to ac cess the S...

Страница 18: ...n you need to operate in Multiple MGRS Mode If your display indicates a different mode than the one you need press 2 at the Setup Screen shown below You will have to cycle power to get to this screen...

Страница 19: ...asscode is 2222 If you wish to change either Level 1 or Level 2 passcodes please see the instructions that follow From the Main Status Screen press ESC and then press PREV The following screen will ap...

Страница 20: ...oop Search Finished Loops Found XX Press ESC to Exit The screen will display the number of loops found on your system The information will be saved into the System Manager s memory No further loop sea...

Страница 21: ...clear any alarms that are found you must fix the problem indicated in the alarm Once the problem is fixed the alarm will clear from the screen the next time the unit is polled System Manager Override...

Страница 22: ...oth the Start and Stop Times are ZERO the schedule is in a continu ous OFF mode Use for Remote Signal Contact If both the Start and Stop Times are 2359 the schedule is in a continu ous ON mode NOTE Th...

Страница 23: ...must enter the time in 24 hour military format the same as a regular week schedule Normally the holidays will operate in an unoccupied mode or a reduced schedule mode There are two start stop events a...

Страница 24: ...n 25 Economizer Control Type Screen 26 Title 24 Economizer Screen 27 Economizer in Unoccupied Mode Screen 28 Outdoor Air Sensor Installed Screen 29 E BUS Outdoor Air RH Sensor Screen 30 Economizer Ena...

Страница 25: ...Press Enter Selected Unit XXXX No Communication Enter the Unit ID of the controller you wish to change schedules for and press ENTER Once communication is established No Com munication will be replac...

Страница 26: ...Zone VAV Recirculating unit using the Space Temperature Sensor to determine the mode of operation Heating and Cooling are controlled to a Leaving Air Setpoint Space Temperature resets the Supply Fan V...

Страница 27: ...Source was set Single Zone VAV in Configuration Screen 5 then line 3 on this screen will read No SAT Rst Allowed and the line 4 will be blank Configuration Screen 10 Reset Rate Interval VCBX Cnfg ID...

Страница 28: ...fan to delay starting This is the Supply Fan Starting Delay initiated whenever the VCB X initiates Supply Fan operation upon going occupied or after power up This is useful when you are using multiple...

Страница 29: ...Cooling as the 2nd form of Cooling VCB X Configuration Screens Configuration Screen 22 Digital Compressor For Modulating Cooling VCBX Cnfg ID 101 Digital Comp For Mod Cool NO Use Or To Change SelectYE...

Страница 30: ...s OAT RH Sensor NO Use Or To Change If the Outdoor Air Sensor installed is an E BUS Outdoor Air Tempera ture and Humidity Sensor press 0 to select YES Default is NO Configuration Screen 30 Economizer...

Страница 31: ...Or To Change Building Pressure Control is available if expansion module EM1 has been installed and configured Default is None Available options are None No Building Pressure Control by this controlle...

Страница 32: ...eversing Valve during Heating operation VCB X Configuration Screens Configuration Screen 38 WSHP Glycol Percentage VCBX Cnfg ID 101 WSHP Glycol Percentage 0 Use Or To Change If this is a Water Source...

Страница 33: ...Select YES if you have an E BUS Space and Humidity Sensor installed Set this to NO if receiving a Space Humidity Broadcast from a GPC XP Controller Default is NO VCB X Configuration Screens Configura...

Страница 34: ...g ID 101 Control Outdoor Air CFM NO Use Or To Change Select YES if you have anAirflow Monitoring station and are controlling the Outdoor Air Damper to an airflow CFM Setpoint Default is NO Configurati...

Страница 35: ...ou need to enter the inside area in square feet of the Exhaust Air duct damper When measuring the Exhaust Air damper area be sure to measure the inside dimensions of the damper The duct size needs to...

Страница 36: ...be accessed with Prism 2 software Default is 15 minutes Description Minimum Default Maximum Trend Log Rate 1 Min 15 Min 120 Min Configuration Screen 63 Emergency Shutdown VCBX Cnfg ID 101 Emergency Sh...

Страница 37: ...Controller Technical Guide for information on how these Delays and Run Times are used Description Minimum Default Maximum Cooling Stage Up 3 Min 3 Min 15 Min Cooling Stage Down 1 Min 1 Min 15 Min Cool...

Страница 38: ...is configured in the VAV Box Controller Configuration Screens 77 81 VCB X Relay Configuration Screens VCBX Cnfg ID 101 On Board Relay 2 6 Not Used Use Or To Change Relay 1 is not configurable as it i...

Страница 39: ...nfigured this relay will energize if unit is in Economizer mode and the damper has moved 5 above its Economizer Minimum Setpoint position 19 Heat Wheel Configure 1 Relay that turns heat wheel on when...

Страница 40: ...roller are listed on the next few pages by sequential screen number When each VCB X Controller is configured for the first time it is best to start with screen 1 and proceed to each Setpoint Screen in...

Страница 41: ...be displayed Change Setpoints Configure Unit Save Copy Restore Scroll to the Change Setpoints option and press ENTER This will take you to the first Setpoints Screen shown below Setpoint Screen 1 Occu...

Страница 42: ...into the space during the Space Vent Mode of operation Once the Space Temperature is satisfied before switching to Vent Mode the controller compares the Outside Air Temperature to these Hood On HVAC...

Страница 43: ...VAC unit will initiate Override Mode any time the Override Button is pressed and held for less than 3 seconds This puts the unit into Occupied operation The Push Button Override Duration Setpoint allo...

Страница 44: ...between the Coil Temperature High Reset Limit down to the Coil Temperature Low Reset Limit On MUA units where the Outdoor Dewpoint Setpoint is used to initiate Dehumidification this screen is only use...

Страница 45: ...It can then modulate up to the Max Heat Percentage as the Space Temperature falls within the range created by the Hi Space setpoint and the Low Space Setpoint created in Setpoint Screens 22 and 23 On...

Страница 46: ...Min Cooling VFD VCB X Setpoint Screens Setpoint Screen 19 Cool Reset Source Setpoints High Space SAT VFD VCBX Spts ID 101 Cool Rst Source Spts If Hi Spc 75 0 F Then SAT 55 If no SAT Reset Source has b...

Страница 47: ...for Single Zone VAV see the last paragraph for this screen If a Reset Source has been configured in Configuration Screen 9 the third line will display If Hi Spc If Hi OAT If Hi RAT or If Hi VFD depen...

Страница 48: ...s configured for Single ZoneVAVapplication on Configura tion Screen 7 this screen will appear In the Heating Mode the Supply Fan VFD speed will proportionally modulate as the Space Temperature falls w...

Страница 49: ...ndow of 2 if you are 2 or more from setpoint the amount of signal change will be 10 per time period and at 1 from setpoint the change would be 5 per time period So a larger proportional window allows...

Страница 50: ...door Air that will be introduced to the HVAC unit in order to ensure the unit is operating within its Heating and Cooling design limitations As shown in the table that follows the Minimum setting for...

Страница 51: ...Economizer Outdoor Air Damper output signal AOUT2 Economizer Control Signal to maintain the Building Pressure Setpoint Whenever the Building Pressure falls below the Building Pressure Setpoint by the...

Страница 52: ...temperatures may be experienced a Pre Heater relay output can be activated to control a preheat coil based on the OutdoorAir Temperature to prevent freezing of Water Coils One of the VCB X Relay Outp...

Страница 53: ...up and will run until the Return Air Temperature rises above the Morning Warm up Target Temperature or until the Max Length Setpoint time expires If the ReturnAirTemperature is above the Morning Warm...

Страница 54: ...current Outdoor Air Temperature Sensor Reading Enter a positive Sensor Calibration value in Line 4 to raise the Outdoor Air Temperature Sensor reading or a negative value in Line 4 to lower the Senso...

Страница 55: ...lication Description Minimum Default Maximum Warm Up SAT Setpoint 40 100 240 Setpoint Screen 56 Cool Down Supply Air Temperature Setpoint VCBX Spts ID 101 Cooldown Supply Air Setpoint 55 0 F Cooling w...

Страница 56: ...48 59 12 Relay Expansion Module Relays Screens 60 90 Alarm Status Screens Status Screens General Procedures From any menu screen press STATUS The Unit Selection Screen shown below will appear request...

Страница 57: ...eat Remote Vent RH Remote Cool RH Remote Heat RH Status Screen 3 Controlling Temperature Cooling Heating Setpoints VCB X v2 00 ID 101 Cont Temp XX XX Cool Spt XX XX Heat Spt XX XX Line 2 Controlling T...

Страница 58: ...the Digital Scroll Compressor or a Chilled Water Valve Status Screen 8 Compressor Discharge Temperature VCB X v2 00 ID 101 Compressor Discharge Temp XXX XX Line 3 Compressor Discharge Temperature Thi...

Страница 59: ...this combination Temperature Humidity Sensor is not installed this line will display 0 Line 3 Current Indoor Relative Humidity Setpoint Percentage This is the adjustable Indoor Air Relative Humidity S...

Страница 60: ...ng Position If you do have a PREHEAT X Controller connected to the VCB X Controller and are using Modulating Heat this is the current modulating heat signal Line 4 Current PREHEAT X Active Stages If y...

Страница 61: ...conomizer Minimum Percentage This shows the current Economizer OA Minimum Damper Position If the unit is not in IAQ Mode this will be the regular configured Minimum Damper Position If the unit is in I...

Страница 62: ...reen 29 Building Pressure Exhaust Fan and Output VCB X v2 00 ID 101 Building Pressure Exhaust Fan ON OFF Output XXX Line 3 Building Pressure Exhaust Fan Status Indicates whether the Exhaust Fan Relay...

Страница 63: ...mp Module these values are read directly from hard coded information in that module The values on Lines 3 and 4 are safety setpoints that will disable compressors See the Water Source Heat Pump Module...

Страница 64: ...t relay FORCED ON or FORCED OFF will appear if this Relay is in a Force Mode Possible options are as follows ON OFF FORCED ON FORCED OFF Status Screens 43 47 EM1 Relays VCB X v1 00 ID 101 Main Exp Rly...

Страница 65: ...ms on the unit and one of the following screens will appear VCB X v2 00 ID 101 NO ALARMS SCROLL DOWN TO VIEW VCB X Status Screens Alarms VCB X v2 00 ID 101 ALARMS PRESENT SCROLL DOWN TO VIEW Line 2 Bl...

Страница 66: ...r Passcode XXXX If the correct passcode was entered the Unit Selection Screen will be displayed Enter Unit Address Then Press Enter Selected Unit XXXX No Communication Enter the Unit ID of the control...

Страница 67: ...ir Heating Mode This is used as a method to provide supplemental heat if for some reason the HVAC heat cannot satisfy the heating demand Configuration Screen 8 Main Fan Status XX Box Cnfg IDXXXX This...

Страница 68: ...AV Zone Controller board with a relay expansion board is used for this purpose No damper or actuator is used If you need to control an auxiliary heater select YES otherwise be sure it is set to NO Con...

Страница 69: ...e communication is established No Com munication will be replaced with Press Down Then press NOTE If No Communication remains it indicates a communication failure to the controller The following scree...

Страница 70: ...w calculations to continue to increase as long as the zone temperature is still above the setpoint That means it can provide 100 or Maximum CFM before the 4 F er ror is achieved bringing the zone unde...

Страница 71: ...es a Force to Fixed Position command Description Minimum Default Maximum Fixed Pos 0 or 0 CFM 0 or 0 CFM 100 or 9999 CFM Setpoint Screen 11 SAT HVAC Mode Deadband XX Box Spts IDXXXX SAT HVAC Mode Dead...

Страница 72: ...aximum Effect on SP 0 F 0 F 6 F Setpoint Screen 16 Push Button Override Duration XX Box Spts IDXXXX Push Button Override Duration X X Hr If the Flush Mount Wall Sensor has the optional Push Button Ove...

Страница 73: ...ust is installed on the Flush Mount Wall Sensor this line will display the current amount the Slide Offset is affecting the Heating and Cooling Setpoints Line 3 Current Heating or Cooling Demand in th...

Страница 74: ...Not Used Line 3 If your VAV Zone Controller has been configured to control reheat stages this line reflects the On Off Status of the first stage of Reheat If you have 3 stages of reheat this line will...

Страница 75: ...Mode setting If the unit ID you entered is for a VAV Zone Controller the Damper Force Mode setting will only apply to that VAV Zone Controller Damper Force Enter Force Mode 0 0 Auto 1 Open 2 Clsd 3 Ma...

Страница 76: ...s SETPOINTS The screen below will appear because this option requires passcode clearance Only a Level 2 passcode can change setpoints THIS ACTION REQUIRES PASSCODE CLEARANCE Enter Passcode XXXX If the...

Страница 77: ...ing Polling Unit Config Enable Alarm Polling Unit XX YES Use Or To Change Enabling Alarm Polling allows any alarm from the loop to be polled You must set this for each controller on the loop MiniLink...

Страница 78: ...n relay to be set for Auto Force On or Force Off The default setting is Auto After you complete all troubleshooting or testing procedures all relays should be changed back to this setting The Force On...

Страница 79: ...will be displayed Analog Output 5 Screen Modulating Cool Override 10 10 Auto The default setting for normal operation is 10 Percentages between 0 to 100 are valid entries Press ENTER after making a s...

Страница 80: ...quires passcode clearance Only a Level 2 passcode can change setpoints THIS ACTION REQUIRES PASSCODE CLEARANCE Enter Passcode XXXX If the correct passcode was entered the Unit Selection Screen will be...

Страница 81: ...y Setpoints Stand Alone Mode The instructions for Stand Alone Mode are exactly the same as Network Mode except that there is no need to enter a Loop number in the Unit ID number field and in the Copy...

Страница 82: ...d to save or open the file and then click OK This option will save the file to the Downloads folder on your PC 5 Open the Downloads folder in Windows Explorer You will find a folder labeled Modular_HH...

Страница 83: ...ttMaster Comm 2 E BUS Module ESC Exit Menu 7 Follow the instructions for WattMaster Controllers or E BUS Modules Updating Controller E BUS Module Software WattMaster Controllers 1 Press 1 to update a...

Страница 84: ...lder version if given to you by Technical Support Then press ENTER Software Version Enter 0 for Latest 0 Esc Exit Menu 4 The screen will display the following messages Resetting Unit Load Sys Info 5 I...

Страница 85: ...e 59 Coil Temperature Sensor 54 Coil Temperature Setpoint 44 59 Coil Temperature Setpoint Status 59 Coil Temperature Status 59 Coil Temperature Switch 33 Communications Screen 12 18 Compressor Dischar...

Страница 86: ...tage s of Heat 28 H H C Changeover Box VAV Zone 66 Head Pressure Control 25 Head Pressure Control Screen 33 Head Pressure Setpoints Cooling and Reheat 49 Head Pressure Setpoint Status 62 Head Pressure...

Страница 87: ...Setpoints 41 VCB X Status 56 Modular System Manager Connection Diagram 7 Defined 6 Dimensions 6 Network Connection 7 Stand Alone Connection 9 Modulating Chilled Water 25 29 Modulating Cooling 58 Modu...

Страница 88: ...Occupied Active 39 Override Active 39 Pre Heat 39 Reversing Valve 39 Supply Fan 64 Relay Status 64 Relay Status 12 Relay 65 Relay Status EM1 64 Remote Forced Cooling 26 Remote Forced Dehumidification...

Страница 89: ...ad Pressure Status 62 Heat Cool Changeover Delay 37 Heating Active Stages Status 59 Heating Enabled Status 58 Heat Pump Configuration 32 Heat Pump Defrost Interval 52 Heat Pump Delays 37 Heat Pump Eme...

Страница 90: ...22 Wetbulb Temperature Status 60 WSHP Glycol Percentage 32 Search For Loops 20 For Overrides 21 Selection Buttons Defined 10 16 Sensor Calibration Space Temperature 72 Supply Air Temperature 72 Senso...

Страница 91: ...r Supply Air Temperature 72 Unoccupied Setbacks 69 Zone Alarm Delay 72 Zone Alarm Offsets 71 VAV Zone Status Airflow 74 Alarm Status 74 Box Air Temperature 73 Cooling Setpoints 73 Desired CFM 74 Fan S...

Страница 92: ...VCBXOISD TGD 01Q Printed in the USA March 2017 All rights reserved Copyright 2017 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 866 918 1100 www orioncontrols com Fax 816 5...

Отзывы: