background image

Unoccupied Mode Sequences

Series Flow Fan Terminals

I

f the VAV/Zone Controller has been configured as a Series Fan Powered 

terminal unit, the series fan relay will activate and run the series box fan 

continuously anytime the HVAC unit fan is running.

In all cases, before the series box fan can be activated, the air damper 

is driven fully closed and held that way for 30 seconds to make sure 

the series box fan hasn’t inadvertently started to spin backwards. Once 

the series box fan starts, it waits an additional 10 seconds to allow the 

fan to spin up before it starts to open the damper and introduce airflow 

from the HVAC unit fan.

Parallel Flow Fan Terminals

On parallel fan powered terminal units, the fan will run whenever Space 

Heating mode is active. At all other times, the fan will only activate if the 

damper/airflow is below a user defined low limit setting. This causes it 

to be used as a make-up air source. When the damper/airflow rises 15% 

above the low limit setpoint, the fan will be deactivated if there are no 

heating stages active, and no space demand exists. 

The check for main fan status setting has no effect on the Parallel Fan 

box when in the occupied mode. The Parallel Fan will only be energized 

when in the Space Heating mode.

Unoccupied Mode Sequences

Space Vent Mode

This mode only applies to the Occupied Mode of operation. If the 

equipment is in the Unoccupied Mode, then a lack of heating or cooling 

demand would generate the Off Mode.

Off Mode

This mode only applies to the Unoccupied Mode of operation. If the 

equipment is in the Unoccupied Mode, then a lack of heating or cooling 

demand would generate this mode. The VAV/Zone Controller will put 

the damper into the Night Minimum Position if check main fan status 

has been selected. If check main fan status has not been selected, the 

damper will be in the fully closed position.

Space Cooling Mode

During unoccupied mode, the HVAC unit is normally off. Unoccupied 

Space Cooling mode is initiated by the temperature in the space rising 

to within 0.5 ºF of the Unoccupied Cooling Setpoint. 

If the HVAC unit is in the Unoccupied Supply Air Heating mode because 

one or more of the VAV/Zone Controllers has a heating demand and 

another VAV/Zone Controller has a cooling demand, the damper/airflow 

for the VAV/Zone Controller requiring cooling will position itself to 

provide the heating minimum setpoint amount of air into the space. No 

modulation open will occur because the space does not want the warm 

air currently being supplied by the air handler. 

When the HVAC unit is in the Unoccupied Supply Air Cooling mode, 

the damper will be held at the Night Minimum Position until the space 

temperature begins to rise above the cooling setpoint. As the space tem-

perature rises to within 0.5 ºF of the Unoccupied Cooling Setpoint, the 

damper/airflow calculation causes the air valve to open proportionally 

until the maximum setpoint is achieved at 1.5 ºF above the setpoint. This 

is a 2 ºF proportional window starting 0.5 ºF below the cooling setpoint 

to 1.5 ºF above the cooling setpoint. 

The  damper/airflow  is  never  allowed  to  modulate  outside  the  user-

adjusted minimum and the maximum setpoints. The maximum damper/

airflow setpoint applies to heating and cooling modes of operation only. 

All of the modes have their own individual minimum setting.

Series Flow Fan Terminals

I

f the VAV/Zone Controller has been configured as a Series Fan Powered 

terminal unit and check for main status has been selected, the series 

fan relay will activate and run the series box fan continuously anytime 

the HVAC unit fan is running. The damper will be held at the Night 

Minimum Position until the space temperature begins to rise above 

the cooling setpoint. If check for main fan status has not been selected, 

the series fan relay will activate and run the series box fan when in the 

Space Cooling mode. The damper will  be in the fully closed position 

until the space temperature begins to rise above the cooling setpoint.

In all cases, before the series box fan can be activated, the air damper 

is driven fully closed and held that way for 30 seconds to make sure 

the series box fan hasn’t inadvertently started to spin backwards. Once 

the series box fan starts, it waits an additional 10 seconds to allow the 

fan to spin up before it starts to open the damper and introduce airflow 

from the HVAC unit fan.

Parallel Flow Fan Terminals

In the Unoccupied Cooling mode, the parallel fan will be off whether 

check for main fan status has been selected or not. If check for main fan 

status has been selected, the damper will be held at the Night Minimum 

Position until the space temperature begins to rise above the cooling 

setpoint. If check for main fan status has not been selected, the damper 

will be held in the fully closed position until the space temperature begins 

to rise above the cooling setpoint.

Space Heating Mode

During unoccupied mode, the HVAC unit is normally off. Unoccupied 

Space Heating mode is initiated by the temperature in the space falling 

to within 0.5 ºF of the Unoccupied Space Heating Setpoint. 

If the HVAC unit is in the Unoccupied Supply Air Cooling mode be-

cause one or more of the VAV/Zone Controllers has a cooling demand 

and another VAV/Zone Controller has a heating demand, the damper/

airflow for the VAV/Zone Controller requiring heating will position itself 

to provide the Night Minimum Position setpoint amount of air into the 

space. No modulation open will occur because the space does not want 

the cold air currently being supplied by the air handler. 

When the HVAC unit is in the Unoccupied Supply Air Heating mode, 

the damper will be held at the Night Minimum Position until the space 

temperature begins to fall below the Unoccupied Heating Setpoint.  As 

the space temperature falls to 0.5 ºF below the Unoccupied Heating  

Setpoint, the damper/airflow calculation causes the air valve to open 

proportionally until the maximum setpoint is achieved at 1.5 ºF below 

the setpoint. This is a 2 ºF proportional window starting 0.5 ºF above 

the heating setpoint to 1.5 ºF below the heating setpoint. 

23

Non-Modular ZCAP Technical Guide

            Sequence of Operations

Содержание OE742-32-VAVZ

Страница 1: ...Non Modular VAV Zone Controller Actuator Package www orioncontrols com...

Страница 2: ...16 Addressing Powering Up 17 General 17 Controller Addressing 17 Power Wiring 17 Initialization and Programming 18 Initialization 18 Programming the Controller 18 VAV Zone Configuration 19 VAV Zone C...

Страница 3: ...oused in a plastic enclosure The VAV Zone Controller is a program mable digital controller which allows for program setpoints to be stored in non volatile memory The controller is connected to a room...

Страница 4: ...Figure 1 OE742 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P D Non Modular VAV Zone Controller Actuator Package Dim P D 4 Non Modular ZCAP Technical Guide Overview...

Страница 5: ...Non Modular VAV Zone Controller Actuator Pkg P I Figure 2 OE744 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P I 5 Non Modular ZCAP Technical Guide Overview...

Страница 6: ...ar VAV Zone Controller Actuator Pkg Components Non Modular VAV Zone Controller Actuator Package Components Figure 4 OE744 32 Pressure Independent Non Modular VAV Zone Controller Actuator Pkg Component...

Страница 7: ...5 01 Zone Controller Expansion Module Dimensions Figure 6 OE325 01 Zone Controller Expansion Module Components Zone Controller Expansion Module Dimensions and Components 7 Non Modular ZCAP Technical G...

Страница 8: ...is used for connecting the communica tions wiring between each Non Modular VAV Zone ControllerActuator Package and or to the MiniLink Polling Device CommLink HVAC Unit Controller or other controller...

Страница 9: ...mounting bracket nuts on the ends of the universal mounting clamp enough to slide the entire actuator and plastic enclosure assembly over the terminal unit damper shaft Rotate the enclosure base actu...

Страница 10: ...onents when mounting the controller Remove the controller from its snap track mount Mark the control enclosure base using the snap track as a template Drill pilot holes in the enclosure base and secur...

Страница 11: ...Zone Controller Expansion Module Wiring Figure 8 Zone Controller Expansion Module Wiring Fan Terminals And Or Staged Electric Heat 11 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 12: ...igure 10 Zone Controller Expansion Module Wiring Fan Terminals And Or 2 Position HW Heat Figure 9 Zone Controller Expansion Module Wiring Fan Terminals And Or Modulating Hot Water Heat 12 Non Modular...

Страница 13: ...Figure 12 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary Electric Heat Figure 11 Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 13 Non Modular Z...

Страница 14: ...munications Wiring Figure 13 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary 2 Position HW Heat Figure 14 Communication Power Wiring Diagram 14 Non Modular ZCAP Technical Guide...

Страница 15: ...Non Modular Devices Transformer Sizing Figure 15 Non Modular VAV Zone Controller Actuator Package Transformer Sizing 15 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 16: ...slave wiring inter face card and modular cable are supplied with the OE523 Round Slaved Zone Damper OE738 Slaved VAV Zone Rectangular Damper Kit and the OE282 03 Slaved VAV Zone Damper Kit These are r...

Страница 17: ...d information regarding communication wiring and connec tion for Interconnected and Networked systems please see the Orion System Installation Troubleshooting Guide Power Wiring One of the most import...

Страница 18: ...ntroller The next step is programming the controller for your specific require ments In order to configure and program the Non Modular VAV Zone ControllerActuator Package you must have a central opera...

Страница 19: ...ional hot water valve this must be set for 0 Options available are 0 No Staging 1 1 Stage of Reheat 2 2 Stages of Reheat 3 3 Stages of Reheat Proportional Heating Signal If the box has hot water rehea...

Страница 20: ...ain fan and provide cooling or heating if so configured It will re main on until the override broadcast has not been detected for at least 2 consecutive minutes Modes of Operation There are 7 possible...

Страница 21: ...VAV Zone Controller detects that the HVAC unit is in Supply Air Heating mode indicating that the air handler has activated its heat the heating airflow minimum will be substituted for the vent minimum...

Страница 22: ...ing This prevents stages from activating at the same time Once a heating stage has been activated it must remain on for at least one minute Once it has been deactivated it must remain off for at least...

Страница 23: ...nal window starting 0 5 F below the cooling setpoint to 1 5 F above the cooling setpoint The damper airflow is never allowed to modulate outside the user adjusted minimum and the maximum setpoints The...

Страница 24: ...ng setpoints The Auxiliary Heat Relay energizes at 0 5 F below the Auxiliary Heat Setpoint and de energizes 0 5 F above the Auxiliary Heat Setpoint The Auxiliary Heat will continue to function regardl...

Страница 25: ...all amount of damper error On pressure independent terminal units the airflow is maintained to within roughly 3 of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal u...

Страница 26: ...clared Maverick by the MiniLink Polling Device The zone has been configured as a VOTING zone If all the above tests are passed the zone temperature and setpoints are then included in the HVAC Mode dec...

Страница 27: ...ime so that the VAV Zone Controllers can read it and use it in their tenant and trend logs Caution These logs are subject to loss if a power outage occurs because there is no battery backed memory on...

Страница 28: ...light up the board is probably defective STAT LED Operations As previously described when the board is first powered up the LED will do the following Flashes Once Off for 5 seconds STAT LED blinks th...

Страница 29: ...entered in the configuration screen or the airflow through the box will be incorrect If none of the aforementioned procedures solves the problem remove power from the VAV Zone Controller Shut down the...

Страница 30: ...33 4 620 5 80531 4 550 0 69822 4 474 5 60552 4 390 10 52500 4 297 15 45902 4 200 20 40147 4 095 25 35165 3 982 30 30805 3 862 35 27140 3 737 40 23874 3 605 45 21094 3 470 50 18655 3 330 52 17799 3 275...

Страница 31: ...Modular and Digital Room Sensor Testing Figure 20 Testing Resistance Voltage On Modular Digital Room Sensors 31 Non Modular ZCAP Technical Guide Troubleshooting...

Страница 32: ...Method 19 C C1 8 C2 8 C3 8 CFM Factor 19 Clockwise to Open Damper 19 Components Pressure Dependent VAV Zone Controller Actuator Package 6 Pressure Independent VAV Zone Controller Actuator Package 6 Zo...

Страница 33: ...25 Connecting to Power Comm Board 15 Modes of Operation 20 Modular Connectors Actuator 8 Power Comm 8 Modular Devices Transformer Sizing 15 Modular Room Sensor Override Button 20 Modular Service Tool...

Страница 34: ...pplications 8 Analog Output 8 Auxiliary Heat 8 Fan Enable 8 Heating Stage 1 8 Heating Stage 2 8 Relay Sequencing 8 Relay Staging 22 Resistance Testing Digital Room Sensor 31 Modular Room Sensor 31 Rev...

Страница 35: ...scribed 3 Vent Minimum 21 Voltage Testing Digital Room Sensor 31 Modular Room Sensor 31 Voting 26 Voting Zone 19 W Wiring 2 Position HW Heat 12 Auxiliary 2 Position HW Heat 14 Auxiliary Electric Heat...

Страница 36: ...NMZCAP TGD 01D Printed in the USA November 2015 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: