background image

Damper Control and Tenant Override Logs

Damper Control

The damper position is calculated by the mode and demand from the 

space sensor. Included in this calculation is an Integral function. This 

prevents the damper/airflow from stagnating at a position somewhere 

above the setpoint because the supply air temperature or duct pressure 

isn’t quite enough to satisfy the space at the currently calculated pro

-

portional position. The Integral causes the calculation to keep adding 

a small amount of the proportional error back into the damper/airflow 

position each time a new position is calculated. The amount the Integral 

adds back in is user adjustable. This value is presented as a number 

between 0.0 and 10.0. That means that if the integral is less than 1.0, 

you are adding a percentage from 0 to 100% of the error back into the 

calculation. If you increase the Integral above 1.0, you are adding more 

than 100% back in.

With just proportional control, a 1 ºF error would cause a 50% increase 

in damper/airflow if the Integral is not included. (1 °F is half of the 2 

ºF Proportional Window).

If you had set the Integral to 1.0, the calculation would add 2% to the 

current damper/airflow calculation each time. The calculation occurs 

once every 10 seconds, so it would take a little over 4 minutes to reach 

the programmed 100% maximum.

Example:

1.  50% Remaining / 2% Integral = 25 Moves to get to a 100%  

 Maximum

2.  25 Moves times 10 seconds = 250 seconds or a little over 4   

 

minutes to reach the 100% maximum damper/airflow  

 

 position.

Of course, different space temperature errors and different Integral values 

cause this calculation to operate slower or faster. It is up to the user to 

determine the optimum setting that provides the tightest temperature 

control without causing the damper to continue to hunt or modulate, 

causing premature wear of the actuator gears and motor.

On pressure dependent terminal units, the damper position is maintained 

to within ± 3% of the calculated position. No attempt is made to position 

the damper exactly on the calculated position. This reduces wear and tear 

on the actuator gears and motors and the amount of airflow involved is 

not affected by that small amount of damper error.

On pressure independent terminal units, the airflow is maintained to 

within roughly 3% of the terminal unit size constant but no tighter than 

16 CFM on the smallest terminal units. The actual control window is 

based on the formula:

Window = Terminal unit size X Square Root (1 / 750)

  

Where Terminal unit size refers to the total rated CFM of the 

terminal unit.

This sliding window allows the control to be much tighter on the smaller 

terminal units than can be achieved on the larger terminal units as far as 

CFM readings. On a large terminal unit, 25 CFM may not be noticeable, 

but on a small terminal unit, 25 CFM may be more than the minimum 

airflow setting for the space.

If the pressure sensor is disconnected or fails on a pressure independent 

terminal unit, the controller automatically reverts to pressure dependent 

operation and generates an alarm to alert the user that a failure has oc-

curred.

On either type of terminal unit, a space sensor failure will force the 

damper to position itself to the 50% of the maximum damper position 

setpoint, and it will not change until the sensor is repaired or replaced.

Tenant Override Logs

If you require tenant billing for push-button override usage, a 

MiniLink 

Polling Device must be installed on each local loop. The MiniLink Poll-

ing Device has the ability to track the amount of override time generated 

by each space sensor equipped with push-button override.

Storing and retrieving these logs requires a dedicated computer run

-

ning the Prism front-end software program. No other method exists for 

retrieving these logs. That means that all of your units will be connected 

together on the communications loop and the loop will be terminated at 

a CommLink device connected to an on-site computer.

Warning: 

This computer must be on 24 hours a day 7 days a  

   

 

week running the Prism software in order for tenant  

   

 

logging to be tracked.

The tenant logs are kept on the dedicated job site computer’s hard drive. 

The only limitation to the number of logs stored is the capacity of the 

hard drive on the computer to which it is being logged.

Note:

   For proper time and date stamping of the tenant log, you 

must configure the air handler to broadcast the time so 

that the VAV/Zone Controllers can read it and use it in 

their tenant and trend logs.

25

Non-Modular ZCAP Technical Guide

            Sequence of Operations

Содержание OE742-32-VAVZ

Страница 1: ...Non Modular VAV Zone Controller Actuator Package www orioncontrols com...

Страница 2: ...16 Addressing Powering Up 17 General 17 Controller Addressing 17 Power Wiring 17 Initialization and Programming 18 Initialization 18 Programming the Controller 18 VAV Zone Configuration 19 VAV Zone C...

Страница 3: ...oused in a plastic enclosure The VAV Zone Controller is a program mable digital controller which allows for program setpoints to be stored in non volatile memory The controller is connected to a room...

Страница 4: ...Figure 1 OE742 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P D Non Modular VAV Zone Controller Actuator Package Dim P D 4 Non Modular ZCAP Technical Guide Overview...

Страница 5: ...Non Modular VAV Zone Controller Actuator Pkg P I Figure 2 OE744 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P I 5 Non Modular ZCAP Technical Guide Overview...

Страница 6: ...ar VAV Zone Controller Actuator Pkg Components Non Modular VAV Zone Controller Actuator Package Components Figure 4 OE744 32 Pressure Independent Non Modular VAV Zone Controller Actuator Pkg Component...

Страница 7: ...5 01 Zone Controller Expansion Module Dimensions Figure 6 OE325 01 Zone Controller Expansion Module Components Zone Controller Expansion Module Dimensions and Components 7 Non Modular ZCAP Technical G...

Страница 8: ...is used for connecting the communica tions wiring between each Non Modular VAV Zone ControllerActuator Package and or to the MiniLink Polling Device CommLink HVAC Unit Controller or other controller...

Страница 9: ...mounting bracket nuts on the ends of the universal mounting clamp enough to slide the entire actuator and plastic enclosure assembly over the terminal unit damper shaft Rotate the enclosure base actu...

Страница 10: ...onents when mounting the controller Remove the controller from its snap track mount Mark the control enclosure base using the snap track as a template Drill pilot holes in the enclosure base and secur...

Страница 11: ...Zone Controller Expansion Module Wiring Figure 8 Zone Controller Expansion Module Wiring Fan Terminals And Or Staged Electric Heat 11 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 12: ...igure 10 Zone Controller Expansion Module Wiring Fan Terminals And Or 2 Position HW Heat Figure 9 Zone Controller Expansion Module Wiring Fan Terminals And Or Modulating Hot Water Heat 12 Non Modular...

Страница 13: ...Figure 12 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary Electric Heat Figure 11 Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 13 Non Modular Z...

Страница 14: ...munications Wiring Figure 13 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary 2 Position HW Heat Figure 14 Communication Power Wiring Diagram 14 Non Modular ZCAP Technical Guide...

Страница 15: ...Non Modular Devices Transformer Sizing Figure 15 Non Modular VAV Zone Controller Actuator Package Transformer Sizing 15 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 16: ...slave wiring inter face card and modular cable are supplied with the OE523 Round Slaved Zone Damper OE738 Slaved VAV Zone Rectangular Damper Kit and the OE282 03 Slaved VAV Zone Damper Kit These are r...

Страница 17: ...d information regarding communication wiring and connec tion for Interconnected and Networked systems please see the Orion System Installation Troubleshooting Guide Power Wiring One of the most import...

Страница 18: ...ntroller The next step is programming the controller for your specific require ments In order to configure and program the Non Modular VAV Zone ControllerActuator Package you must have a central opera...

Страница 19: ...ional hot water valve this must be set for 0 Options available are 0 No Staging 1 1 Stage of Reheat 2 2 Stages of Reheat 3 3 Stages of Reheat Proportional Heating Signal If the box has hot water rehea...

Страница 20: ...ain fan and provide cooling or heating if so configured It will re main on until the override broadcast has not been detected for at least 2 consecutive minutes Modes of Operation There are 7 possible...

Страница 21: ...VAV Zone Controller detects that the HVAC unit is in Supply Air Heating mode indicating that the air handler has activated its heat the heating airflow minimum will be substituted for the vent minimum...

Страница 22: ...ing This prevents stages from activating at the same time Once a heating stage has been activated it must remain on for at least one minute Once it has been deactivated it must remain off for at least...

Страница 23: ...nal window starting 0 5 F below the cooling setpoint to 1 5 F above the cooling setpoint The damper airflow is never allowed to modulate outside the user adjusted minimum and the maximum setpoints The...

Страница 24: ...ng setpoints The Auxiliary Heat Relay energizes at 0 5 F below the Auxiliary Heat Setpoint and de energizes 0 5 F above the Auxiliary Heat Setpoint The Auxiliary Heat will continue to function regardl...

Страница 25: ...all amount of damper error On pressure independent terminal units the airflow is maintained to within roughly 3 of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal u...

Страница 26: ...clared Maverick by the MiniLink Polling Device The zone has been configured as a VOTING zone If all the above tests are passed the zone temperature and setpoints are then included in the HVAC Mode dec...

Страница 27: ...ime so that the VAV Zone Controllers can read it and use it in their tenant and trend logs Caution These logs are subject to loss if a power outage occurs because there is no battery backed memory on...

Страница 28: ...light up the board is probably defective STAT LED Operations As previously described when the board is first powered up the LED will do the following Flashes Once Off for 5 seconds STAT LED blinks th...

Страница 29: ...entered in the configuration screen or the airflow through the box will be incorrect If none of the aforementioned procedures solves the problem remove power from the VAV Zone Controller Shut down the...

Страница 30: ...33 4 620 5 80531 4 550 0 69822 4 474 5 60552 4 390 10 52500 4 297 15 45902 4 200 20 40147 4 095 25 35165 3 982 30 30805 3 862 35 27140 3 737 40 23874 3 605 45 21094 3 470 50 18655 3 330 52 17799 3 275...

Страница 31: ...Modular and Digital Room Sensor Testing Figure 20 Testing Resistance Voltage On Modular Digital Room Sensors 31 Non Modular ZCAP Technical Guide Troubleshooting...

Страница 32: ...Method 19 C C1 8 C2 8 C3 8 CFM Factor 19 Clockwise to Open Damper 19 Components Pressure Dependent VAV Zone Controller Actuator Package 6 Pressure Independent VAV Zone Controller Actuator Package 6 Zo...

Страница 33: ...25 Connecting to Power Comm Board 15 Modes of Operation 20 Modular Connectors Actuator 8 Power Comm 8 Modular Devices Transformer Sizing 15 Modular Room Sensor Override Button 20 Modular Service Tool...

Страница 34: ...pplications 8 Analog Output 8 Auxiliary Heat 8 Fan Enable 8 Heating Stage 1 8 Heating Stage 2 8 Relay Sequencing 8 Relay Staging 22 Resistance Testing Digital Room Sensor 31 Modular Room Sensor 31 Rev...

Страница 35: ...scribed 3 Vent Minimum 21 Voltage Testing Digital Room Sensor 31 Modular Room Sensor 31 Voting 26 Voting Zone 19 W Wiring 2 Position HW Heat 12 Auxiliary 2 Position HW Heat 14 Auxiliary Electric Heat...

Страница 36: ...NMZCAP TGD 01D Printed in the USA November 2015 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: