Overview

Modular & Non-Modular VAV/Zone Controllers

There are two variations of the VAV/Zone Controller Actuator Packages. 

One is referred to as the Modular VAV/Zone Controller Actuator Pack-

age and the other as the Non-Modular VAV/Zone Controller Actuator 

Package. This manual is written for the Non-Modular Actuator Package. 

If you have the Modular Actuator Package you will need to refer to the 

Modular VAV/Zone Controller Actuator Package Technical Guide, Form 

No: OR-MZCAP-TGD. Below is information regarding the differences 

between the Modular & Non-Modular products.

Modular VAV/Zone Controller Act. Pkg.

The Modular VAV/Zone Controller Actuator Packages utilize modular 

connectors on the VAV/Zone Controller board which connect to a Power/

Comm Board via pre-fabricated cables that have mating modular con-

nectors to provide power & communications to the VAV/Zone Controller 

Actuator Package. The following Orion products use this type of com-

munications & power wiring architecture.

OE742-31-VAVZ    

VAV/Zone Controller 

     Actuator 

Package 

Pressure 

Dependent

OE744-31-VAVZ    

VAV/Zone Controller Actuator Package 

     Pressure 

Independent

OE520-XX   

 

VAV/Zone Round Damper 

     Assembly 

Pressure 

Dependent

OE521-XX   

 

VAV/Zone Round Damper Assembly 

     Pressure 

Independent

OE736-01 

 

 

VAV/Zone Rectangular Damper Kit

Non-Modular VAV/Zone Controller

The Non-Modular VAV/Zone Controller Actuator Packages all utilize 

wiring terminals instead of modular connectors on the VAV/Zone Con-

troller board. The 24 VAC power is supplied from a transformer wired 

to the VAV/Zone Controller using standard stranded wire and 2 pole 

terminal blocks. The communications wiring is connected between the 

other VAV/Zone Controllers, CommLink, MiniLink, HVAC unit control-

ler  or other controllers on the local loop by using 2 conductor twisted 

pair with shield wire which is connected to the VAV/Zone controllers 

via a standard 3 pole terminal block. The following Orion products use 

this type of communications & power wiring architecture.

OE742-32-VAVZ    

N.M. VAV/Zone Controller 

     Actuator 

Package 

Pressure 

Dependent

OE744-32-VAVZ    

N.M. VAV/Zone Controller 

     Actuator 

Package 

     Pressure 

Independent

OE520N-XX   

 

N.M. VAV/Zone Round Damper 

     Assembly 

Pressure 

Dependent

OE521N-XX   

 

N.M. .VAV/Zone Round Damper 

     Assembly 

Pressure 

Independent

OE736N-01   

 

N.M VAV/Zone Rectangular Damper 

     Kit 

Controller Features

Features

Non-Modular VAV/Zone Controller Act. Pkg.

The Non-Modular VAV/Zone Controller Actuator Package is used for 

controlling airflow and operation of VAV or Zoning terminal units. The 

package contains the VAV/Zone Controller and Actuator mounted and 

housed in a plastic enclosure. The VAV/Zone Controller is a program-

mable digital controller which allows for program setpoints to be stored 

in non-volatile memory. The controller is connected to a room sensor 

via a modular cable assembly which monitors space temperature al-

lowing the VAV/Zone Controller to modulate a damper in response to 

space temperature, duct temperature, and airflow requirements in the 

controlled space.

The  Non-Modular VAV/Zone Controller Actuator Package has four 

integral modular jacks for connection to the actuator, the airflow sen

-

sor (for pressure independent applications), the room sensor, and the 

VAV/Zone Controller Expansion Module via modular cables. Wire 

terminal connections are provided for the 24 VDC power and system 

communications. A quick connect terminal connector is also supplied 

for connection of the Modular Service Tool to facilitate programming 

of the controller. The controller has an on-board dip switch provided 

for board addressing. 

The VAV/Zone Controller is provided with two relays for tri-state control 

of the damper actuator. All outputs and the relay common are electri-

cally isolated from all other circuitry on the board. All relay outputs are 

supplied with transient suppression devices across each set of contacts 

to reduce EMI and arcing. The relay output contacts are rated for pilot 

duty control of a maximum of 1 Amps @ 24 VAC or 24 VDC. The 

actuator connects via a modular cable to the board and provides the 

VAV/Zone Controller with feedback monitoring for precise positioning 

of the actuator. 

OE325-01 Zone Controller Expansion Module

The OE325-01 Zone Controller Expansion Module is used in conjunction 

with the Non-Modular VAV/Zone Controller Actuator Package to allow 

for control of VAV and Zone terminal units, including series and parallel 

fan terminal units with 1, 2 or 3 stages of electric heat, modulating hot 

water heat, 2 position hot water heat, SCR electric heat, and/or auxiliary 

heat devices. 

The OE325-01 Zone Controller Expansion Module connects to the 

VAV/Zone Controller board by means of a modular cable provided with 

the expansion module. Power is supplied to the board by means of this 

modular cable. Screw terminals are provided for connection of field 

wiring to the relay and analog outputs.  

The relay outputs are N.O. contacts with one common terminal. All 

outputs and the relay common are electrically isolated from all other 

circuitry on the board. All relay outputs are supplied with transient 

suppression devices across each set of contacts to reduce EMI and arcing. 

The relay output contacts are rated for pilot duty control of a maximum 

of 1 Amps @ 24 VAC or 24 VDC. The analog output provides a 0-10 

VDC modulating signal output into a 1K Ohm minimum load.

3

Non-Modular ZCAP Technical Guide

                                    Overview 

Содержание OE742-32-VAVZ

Страница 1: ...Non Modular VAV Zone Controller Actuator Package www orioncontrols com...

Страница 2: ...16 Addressing Powering Up 17 General 17 Controller Addressing 17 Power Wiring 17 Initialization and Programming 18 Initialization 18 Programming the Controller 18 VAV Zone Configuration 19 VAV Zone C...

Страница 3: ...oused in a plastic enclosure The VAV Zone Controller is a program mable digital controller which allows for program setpoints to be stored in non volatile memory The controller is connected to a room...

Страница 4: ...Figure 1 OE742 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P D Non Modular VAV Zone Controller Actuator Package Dim P D 4 Non Modular ZCAP Technical Guide Overview...

Страница 5: ...Non Modular VAV Zone Controller Actuator Pkg P I Figure 2 OE744 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P I 5 Non Modular ZCAP Technical Guide Overview...

Страница 6: ...ar VAV Zone Controller Actuator Pkg Components Non Modular VAV Zone Controller Actuator Package Components Figure 4 OE744 32 Pressure Independent Non Modular VAV Zone Controller Actuator Pkg Component...

Страница 7: ...5 01 Zone Controller Expansion Module Dimensions Figure 6 OE325 01 Zone Controller Expansion Module Components Zone Controller Expansion Module Dimensions and Components 7 Non Modular ZCAP Technical G...

Страница 8: ...is used for connecting the communica tions wiring between each Non Modular VAV Zone ControllerActuator Package and or to the MiniLink Polling Device CommLink HVAC Unit Controller or other controller...

Страница 9: ...mounting bracket nuts on the ends of the universal mounting clamp enough to slide the entire actuator and plastic enclosure assembly over the terminal unit damper shaft Rotate the enclosure base actu...

Страница 10: ...onents when mounting the controller Remove the controller from its snap track mount Mark the control enclosure base using the snap track as a template Drill pilot holes in the enclosure base and secur...

Страница 11: ...Zone Controller Expansion Module Wiring Figure 8 Zone Controller Expansion Module Wiring Fan Terminals And Or Staged Electric Heat 11 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 12: ...igure 10 Zone Controller Expansion Module Wiring Fan Terminals And Or 2 Position HW Heat Figure 9 Zone Controller Expansion Module Wiring Fan Terminals And Or Modulating Hot Water Heat 12 Non Modular...

Страница 13: ...Figure 12 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary Electric Heat Figure 11 Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 13 Non Modular Z...

Страница 14: ...munications Wiring Figure 13 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary 2 Position HW Heat Figure 14 Communication Power Wiring Diagram 14 Non Modular ZCAP Technical Guide...

Страница 15: ...Non Modular Devices Transformer Sizing Figure 15 Non Modular VAV Zone Controller Actuator Package Transformer Sizing 15 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 16: ...slave wiring inter face card and modular cable are supplied with the OE523 Round Slaved Zone Damper OE738 Slaved VAV Zone Rectangular Damper Kit and the OE282 03 Slaved VAV Zone Damper Kit These are r...

Страница 17: ...d information regarding communication wiring and connec tion for Interconnected and Networked systems please see the Orion System Installation Troubleshooting Guide Power Wiring One of the most import...

Страница 18: ...ntroller The next step is programming the controller for your specific require ments In order to configure and program the Non Modular VAV Zone ControllerActuator Package you must have a central opera...

Страница 19: ...ional hot water valve this must be set for 0 Options available are 0 No Staging 1 1 Stage of Reheat 2 2 Stages of Reheat 3 3 Stages of Reheat Proportional Heating Signal If the box has hot water rehea...

Страница 20: ...ain fan and provide cooling or heating if so configured It will re main on until the override broadcast has not been detected for at least 2 consecutive minutes Modes of Operation There are 7 possible...

Страница 21: ...VAV Zone Controller detects that the HVAC unit is in Supply Air Heating mode indicating that the air handler has activated its heat the heating airflow minimum will be substituted for the vent minimum...

Страница 22: ...ing This prevents stages from activating at the same time Once a heating stage has been activated it must remain on for at least one minute Once it has been deactivated it must remain off for at least...

Страница 23: ...nal window starting 0 5 F below the cooling setpoint to 1 5 F above the cooling setpoint The damper airflow is never allowed to modulate outside the user adjusted minimum and the maximum setpoints The...

Страница 24: ...ng setpoints The Auxiliary Heat Relay energizes at 0 5 F below the Auxiliary Heat Setpoint and de energizes 0 5 F above the Auxiliary Heat Setpoint The Auxiliary Heat will continue to function regardl...

Страница 25: ...all amount of damper error On pressure independent terminal units the airflow is maintained to within roughly 3 of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal u...

Страница 26: ...clared Maverick by the MiniLink Polling Device The zone has been configured as a VOTING zone If all the above tests are passed the zone temperature and setpoints are then included in the HVAC Mode dec...

Страница 27: ...ime so that the VAV Zone Controllers can read it and use it in their tenant and trend logs Caution These logs are subject to loss if a power outage occurs because there is no battery backed memory on...

Страница 28: ...light up the board is probably defective STAT LED Operations As previously described when the board is first powered up the LED will do the following Flashes Once Off for 5 seconds STAT LED blinks th...

Страница 29: ...entered in the configuration screen or the airflow through the box will be incorrect If none of the aforementioned procedures solves the problem remove power from the VAV Zone Controller Shut down the...

Страница 30: ...33 4 620 5 80531 4 550 0 69822 4 474 5 60552 4 390 10 52500 4 297 15 45902 4 200 20 40147 4 095 25 35165 3 982 30 30805 3 862 35 27140 3 737 40 23874 3 605 45 21094 3 470 50 18655 3 330 52 17799 3 275...

Страница 31: ...Modular and Digital Room Sensor Testing Figure 20 Testing Resistance Voltage On Modular Digital Room Sensors 31 Non Modular ZCAP Technical Guide Troubleshooting...

Страница 32: ...Method 19 C C1 8 C2 8 C3 8 CFM Factor 19 Clockwise to Open Damper 19 Components Pressure Dependent VAV Zone Controller Actuator Package 6 Pressure Independent VAV Zone Controller Actuator Package 6 Zo...

Страница 33: ...25 Connecting to Power Comm Board 15 Modes of Operation 20 Modular Connectors Actuator 8 Power Comm 8 Modular Devices Transformer Sizing 15 Modular Room Sensor Override Button 20 Modular Service Tool...

Страница 34: ...pplications 8 Analog Output 8 Auxiliary Heat 8 Fan Enable 8 Heating Stage 1 8 Heating Stage 2 8 Relay Sequencing 8 Relay Staging 22 Resistance Testing Digital Room Sensor 31 Modular Room Sensor 31 Rev...

Страница 35: ...scribed 3 Vent Minimum 21 Voltage Testing Digital Room Sensor 31 Modular Room Sensor 31 Voting 26 Voting Zone 19 W Wiring 2 Position HW Heat 12 Auxiliary 2 Position HW Heat 14 Auxiliary Electric Heat...

Страница 36: ...NMZCAP TGD 01D Printed in the USA November 2015 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: