background image

MNL940-677-000  

 

 

 

REV - B   

 

 

 

3/20/2017 

 

13

 

 

SECTION 4 
TROUBLESHOOTING 
 

 

 

4.1 

THEORY OF OPERATION

 

 

The INV-1200 series utilizes high frequency, switched mode, power conversion to convert the 
incoming DC to an AC output. The first stage is a DC to DC converter which “steps - up” the input 
voltage to a reg/- 200 VDC. This voltage is applied to a second high frequency 
“housekeeping” supply and the output inverter. The housekeeping supply provides operating 
voltages for the output inverter and alarm circuits. The output section consists of a crystal 
controlled sine wave oscillator and class “D” power amplifier. The crystal derived clock frequency 
is divided down and applied to a counter, PROM, D/A converter combination. The resulting sine 
wave at the output frequency is applied to the power amplifier and boosted to the 120 VAC level 
required on the output.  

 

The power amplifier consists of a pulse width modulated (PWM) “half bridge” circuit utilizing IGBT 
output devices. The devices are switched at a rate of 20 KHZ and modulated with the sine wave 
information. The result is a 400V p/p pulse train at the output that contains the original sine wave 
information. The 20 KHz “carrier” frequency is removed by a low pass LC filter. This provides an 
amplified version of the original modulation signal to the output terminals. The control circuitry on 
the output inverter assembly also provides output regulation and protective functions. The output 
voltage RMS value is monitored and used to keep the output regulated. Output current is 
measured and used to provide fold back type limiting in the event of an overload. Output short 
circuits will disable the inverter stage, requiring the input power to be recycled to return proper 
operation.  

 

The alarm and bypass circuits (if provided) allow for external monitoring of input and output 
status. The AC input/ bypass feature allows the AC power line to be applied to the model INV-
1200 and sent directly to the output terminals. In the event the AC is interrupted, a relay will 
switch the output to the inverter. Units supplied with the D1 option will switch the line through 
when the DC is not available or the inverter has a fault. The AC input is fused at 10 amps.  
 

HOUSE

OSC. &

POWER

DC /DC

LINE FUSE

AC 

DC

AC

SYSTEM BLOCK DIAGRAM

BYPASS RELAY

CONVERTER

KEEPING

CONTROL

AMP

OUTPUT

INPUT

IN

 

FIGURE 4-1 INV-1200 BLOCK DIAGRAM (WITH BYPASS OPTION) 

 
 
 
 
 
 

Содержание Behlman INV-1200 Series

Страница 1: ...T BEHLMAN CUSTOMER SERVICE DEPARTMENT PHONE TOLL FREE 1 800 874 6727 EMAIL SERVICE BEHLMAN COM WEB WWW BEHLMAN COM OR WRITE BEHLMAN CUSTOMER SERVICE DEPARTMENT 80 CABOT COURT HAUPPAUGE NY 11788 PHONE...

Страница 2: ...the presence of flammable gases or fumes Operation of any electrical instrument in such an environment constitutes a definite safety hazard KEEP AWAY FROM LIVE CIRCUITS Operating personnel must not re...

Страница 3: ...us conditions due to the exposure of hazardous voltage that can be lethal if contacted Neither Behlman Electronics Hauppauge NY USA nor any of the subsidiary sales organizations can accept any respons...

Страница 4: ...be refused the customer being liable for all shipping handling and repair costs When packing for reshipment use the original shock absorbent material and shipping container to preclude damage to the...

Страница 5: ...ial Authorization RMA number This number must be attached to the equipment sent back for warranty repair Equipment must be shipped back to Behlman prepaid No collect shipments will be accepted Behlman...

Страница 6: ...arm Contacts 2 4 Optional Step up Transformer 3 0 OPERATING INSTRUCTIONS 3 1 Controls and Indicators 3 2 Optional Alarm Contacts 3 3 Operational Considerations Load Limitations Powering Reactive Loads...

Страница 7: ...gged steel enclosure making them well suited to operation in industrial applications Available options include an AC input bypass and signaling contacts The AC bypass option is available in two config...

Страница 8: ...protected Thermal Thermal cut out that monitors temperature Shuts down during over temp conditions Automatic Reset MECHANICAL WIDTH 17 in 43 2cm 19 standard EIA rack panel LENGTH 17in 48 3cm HEIGHT 3...

Страница 9: ...nt the inverter by the mounting ears only If the unit is intended for use in a mobile or other high vibration application the use of additional support for the rear of the chassis is highly recommende...

Страница 10: ...with respect to earth This situation does not meet the requirements of NEC section 250 regarding separately derived AC source To allow compliance with NEC rules an additional common terminal is provi...

Страница 11: ...MNL940 677 000 REV B 3 20 2017 6 FIGURE 2 2 INV1200 WIRING WITH BYPASS OPTION FIGURE 2 3 INV1200 WIRING WITH BYPASS AND TB OPTIONS...

Страница 12: ...t Each function provides one set of dry form C contacts which accommodates any logic required The internal relays will change state if any of the three voltages are outside of limits required to provi...

Страница 13: ...standard 120VAC output to the higher value In addition the bypass option can also be included with the external transformer A block diagram of the optional transformer configurations is provided in fi...

Страница 14: ...ion provides a terminal block 6 AC LINE INPUT TERMINALS Screw type terminal block provided with alarm bypass option For connection to bypass source 7 FAN EXHAUST Heated air exhaust Minimum 4 inch clea...

Страница 15: ...e sound of the cooling fans should be evident 3 The appropriate front panel LEDs should be illuminated 4 To test the inverter use a True RMS type meter to confirm the output voltage is as specified 5...

Страница 16: ...s the INV 1200 series to start most high in rush loads in its power range It must be understood that the DC power source suppling the inverter must also have this capability in order to derive these b...

Страница 17: ...bridge rectifier followed by a capacitive filter the current waveform associated with this circuit is illustrated below in figure 3 3 The input current to this type of circuit is drawn in large gulps...

Страница 18: ...at the output that contains the original sine wave information The 20 KHz carrier frequency is removed by a low pass LC filter This provides an amplified version of the original modulation signal to...

Страница 19: ...in inverter Check polarity if ok the unit may have an internal fault Return for service WARNING Service of this device requires specialized equipment and trained personnel There are no internal user...

Страница 20: ...MNL940 677 000 REV B 3 20 2017 15 5 0 MECHANICAL OUTLINE ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE NOTED...

Страница 21: ...EV B 3 20 2017 16 REVISION HISTORY Rev ECO DESCRIPTION DATE N A INV 1200 Gen 2 Initial Release 9 16 2016 A 17 030 Revised specification figure 2 1 to 2 3 redrawn 2 28 17 B 17 032 Corrected text figure...

Отзывы: