background image

MNL940-677-000  

 

 

 

REV - B   

 

 

 

3/20/2017 

 

11

 

3.2 

OPERATION (continued) 

 

The A1 bypass function can be verified by removing the AC line input. This will cause the 
AC IN LED to turn red and the AC IN alarm contacts to change state. During this time the 
INVERTER and DC IN LEDs should remain green. Confirm an AC output from the output 
terminals or outlets. When the AC is re-applied the unit will switch back to bypass after a 
short delay period.  

 

Units provided with the D1 bypass option are DC preferred. This means that the inverter is 
routed to the output terminals (or outlets) whenever DC is available. If the DC is lost or the 
inverter malfunctions, the incoming AC line will be routed to the output terminals.  When 
the DC has recovered, the unit will switch back to DC operation after a short delay period. 

 

The D1  bypass function can be verified by removing the DC input (leave front panel 
breaker on). Confirm that the DC IN and INVERTER LEDs turn red and the corresponding 
rear panel alarm contacts change state. The AC IN LED will remain green and the AC IN 
contacts do not change state  (a quick flash of the LED or relay trip may be encountered 
during the switch over). Use a voltmeter to confirm that the input AC line is now routed to 
the unit’s output terminals or outlets. 

 

3.3 

OPERATIONAL CONSIDERATIONS

 

 

 

LOADING LIMITATIONS:

 

 

The INV series are designed to produce a power level of 1200 watts (real power) under 
continuous operating conditions. In addition, they can supply bursts of over 1500 watts for several 
seconds. Peak repetitive currents on the order of 30 amps may also be supplied continuously as 
long as they do not exceed the RMS value of 10 amps.  

 

This high peak current capability allows the INV-1200 series to start most high in-rush loads in its 
power range. It must be understood that the DC power source suppling the inverter must also 
have this capability in order to derive these benefits. A poorly regulated or high internal resistance 
DC power source will adversely affect operation of the inverter.  

 
 

POWERING REACTIVE LOADS

 

 

Capacitors and inductors are reactive in nature. With capacitors, if the load is applied during the 
peak of the AC cycle there may be a considerable in-rush  of current several magnitudes larger 
than the steady state current. This current is only limited by any series resistance that may be 
present in the load circuit. Under the right conditions, this could trip the overload protection 
circuits in the inverter. Certain transformers and solenoids (inductance) present the same 
problem due to magnetizing currents. 

 

 
Several methods can be used to prevent tripping the protection circuits in the power source. One 
common method is to insert a limiting impedance in series with the load. This could be in the form 
of a fixed resistor or NTC (negative temperature coefficient) thermistor. Also, zero crossing 
switching can be employed. Most commercial DC power supplies present a capacitive in-rush 
characteristic. Line filters with large shunt capacitance may also cause considerable in-rush 
current “spikes”. If not accounted for these loads can trip protective circuits in the inverter.  

 

 

POWERING LAMPS

   

 

Tungsten filaments lamps, when cold, present a very low resistance. Once they are energized, 
their resistance quickly climbs to its steady state value. This characteristic must be accounted for 
when driving tungsten filament lamps. Like incandescent lamps, certain  Ni-Chrome based 
heaters will present a 2:1 or 3:1 in-rush when cold. The same methods for limiting in-rush current 
for reactive loads can be applied to tungsten or Ni-Chrome based elements. 

 

 

 

Содержание Behlman INV-1200 Series

Страница 1: ...T BEHLMAN CUSTOMER SERVICE DEPARTMENT PHONE TOLL FREE 1 800 874 6727 EMAIL SERVICE BEHLMAN COM WEB WWW BEHLMAN COM OR WRITE BEHLMAN CUSTOMER SERVICE DEPARTMENT 80 CABOT COURT HAUPPAUGE NY 11788 PHONE...

Страница 2: ...the presence of flammable gases or fumes Operation of any electrical instrument in such an environment constitutes a definite safety hazard KEEP AWAY FROM LIVE CIRCUITS Operating personnel must not re...

Страница 3: ...us conditions due to the exposure of hazardous voltage that can be lethal if contacted Neither Behlman Electronics Hauppauge NY USA nor any of the subsidiary sales organizations can accept any respons...

Страница 4: ...be refused the customer being liable for all shipping handling and repair costs When packing for reshipment use the original shock absorbent material and shipping container to preclude damage to the...

Страница 5: ...ial Authorization RMA number This number must be attached to the equipment sent back for warranty repair Equipment must be shipped back to Behlman prepaid No collect shipments will be accepted Behlman...

Страница 6: ...arm Contacts 2 4 Optional Step up Transformer 3 0 OPERATING INSTRUCTIONS 3 1 Controls and Indicators 3 2 Optional Alarm Contacts 3 3 Operational Considerations Load Limitations Powering Reactive Loads...

Страница 7: ...gged steel enclosure making them well suited to operation in industrial applications Available options include an AC input bypass and signaling contacts The AC bypass option is available in two config...

Страница 8: ...protected Thermal Thermal cut out that monitors temperature Shuts down during over temp conditions Automatic Reset MECHANICAL WIDTH 17 in 43 2cm 19 standard EIA rack panel LENGTH 17in 48 3cm HEIGHT 3...

Страница 9: ...nt the inverter by the mounting ears only If the unit is intended for use in a mobile or other high vibration application the use of additional support for the rear of the chassis is highly recommende...

Страница 10: ...with respect to earth This situation does not meet the requirements of NEC section 250 regarding separately derived AC source To allow compliance with NEC rules an additional common terminal is provi...

Страница 11: ...MNL940 677 000 REV B 3 20 2017 6 FIGURE 2 2 INV1200 WIRING WITH BYPASS OPTION FIGURE 2 3 INV1200 WIRING WITH BYPASS AND TB OPTIONS...

Страница 12: ...t Each function provides one set of dry form C contacts which accommodates any logic required The internal relays will change state if any of the three voltages are outside of limits required to provi...

Страница 13: ...standard 120VAC output to the higher value In addition the bypass option can also be included with the external transformer A block diagram of the optional transformer configurations is provided in fi...

Страница 14: ...ion provides a terminal block 6 AC LINE INPUT TERMINALS Screw type terminal block provided with alarm bypass option For connection to bypass source 7 FAN EXHAUST Heated air exhaust Minimum 4 inch clea...

Страница 15: ...e sound of the cooling fans should be evident 3 The appropriate front panel LEDs should be illuminated 4 To test the inverter use a True RMS type meter to confirm the output voltage is as specified 5...

Страница 16: ...s the INV 1200 series to start most high in rush loads in its power range It must be understood that the DC power source suppling the inverter must also have this capability in order to derive these b...

Страница 17: ...bridge rectifier followed by a capacitive filter the current waveform associated with this circuit is illustrated below in figure 3 3 The input current to this type of circuit is drawn in large gulps...

Страница 18: ...at the output that contains the original sine wave information The 20 KHz carrier frequency is removed by a low pass LC filter This provides an amplified version of the original modulation signal to...

Страница 19: ...in inverter Check polarity if ok the unit may have an internal fault Return for service WARNING Service of this device requires specialized equipment and trained personnel There are no internal user...

Страница 20: ...MNL940 677 000 REV B 3 20 2017 15 5 0 MECHANICAL OUTLINE ALL DIMENSIONS ARE IN INCHES UNLESS OTHERWISE NOTED...

Страница 21: ...EV B 3 20 2017 16 REVISION HISTORY Rev ECO DESCRIPTION DATE N A INV 1200 Gen 2 Initial Release 9 16 2016 A 17 030 Revised specification figure 2 1 to 2 3 redrawn 2 28 17 B 17 032 Corrected text figure...

Отзывы: