Remove the gas control valve rod by removing the cotter pin. Disconnect both 
piezoelectric igniter cables from their connections to the heat exchanger. Remove the 
electrode ceramic. Remove the two (2) gas lines connecting the gas control valve to the 
pilot and main burner from both ends. Remove the thermocouple from both ends. 
Remove the gas control valve grip (one (1) screw) and remove the valve. Remove the gas 
control valve support (two (2) screws). Remove the sheet metal valve protector 
(two (2) screws). Remove the main burner fixing nut on the left of the heat exchanger. 
Remove the main burner support (four (4) screws). Take the main burner assembly (with 
pilot attached) out of the heat exchanger. Clean the pilot and main burner completely as 
necessary with a soft bristled brush. 

Check the main burner gasket , If it is damaged or worn replace with a new gasket 
available from your dealer. (the gasket part number can be found in the exploded parts 
view at the end of this manual)  After cleaning, reinstall the main burner module in the 
reverse order of the directions above.  

Step 7  Replace the heater on the wall mounting plate. Take extreme care to ensure that 
the EXHAUST pipe is firmly engaged with the vent outlet at the rear of the heater.  
Be sure that the pipe remains engaged in its position in the vent cap. The air inlet pipe 
must slide over its appropriate opening. Use the hexagonal nuts of step 3 above to firmly 
re-attach the unit back on the wall mounting plate.

Step 8  Reconnect the gas supply. Perform the leak test procedure found in the section of 
this manual titled "Check for Gas Leaks"
 on page 14.

Step 9  Verify Proper Operation After Servicing: Place the unit back into operation 
following the procedures found on the hanging tag behind the unit and/or  in Figure 10 
in this manual. Check all connections from the Gas Control Assembly to the pilot and main 
burner with soapy water solution.  Bubbles on any of the joints indicate a leak is present 
and must be repaired. Turn OFF the gas to the unit when performing repairs to the gas 
piping system. Check to make sure that the spark ignition (piezoelectric igniter) lights 
the pilot.

Step 10  While the main burner is ON, check the flames to see that they are burning a 
clean blue color. 
Note: After cleaning, the first few minutes of heater operation will probably have some 
yellowish flying traces in the flame due to the burning of particles left behind during the 
cleaning operation.
Liquid propane has some evidence of yellowing in the tips of the flame. The main burner 
and pilot flames can be observed through the heat exchanger front glass on 
Comfort View units or through the pilot viewing window located at the top right front of 
the heat exchanger on Calorama units. See Figure 11 below for an approximation of the 
correct flame patterns. If your unit is not burning cleanly, turn it OFF. Clean or change 
injectors following the directions below.

CONDUCT ALL LEAK TESTING ONLY IN A WELL VENTILATED AREA.

THE AREA MUST BE FREE OF ACCUMULATED GAS. BE SURE YOU DO NOT SMELL ANY 

GAS BEFORE PROCEDING TO OPERATE THE UNIT.

Содержание CALORAMA

Страница 1: ...ORTED BY The Gas Appliance Company Inc FLORIDA US of A www orbisheat com WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage person...

Страница 2: ...Installation Figure 6 Exploded Side View of Vent Installation Vent and Wall Plate Installation Figure 7 Vent Kit Assembly Figure 8 Vent Cap as seen from the Outside Connect Gas Piping Gas Supply Press...

Страница 3: ...rect Vent Wall Furnace Standard CAN 2 32M98 to provide safe trouble free operation throughout the expected life of the unit Any alteration modification or adjustment not specifically mentioned in this...

Страница 4: ...the vent assembly supplied with the unit so that harmful gases will not gather inside of the building The vent kit part number for your unit can be found in the exploded parts view at the end of this...

Страница 5: ...e immediate action in order to reduce or eliminate the risk of injury and or property damage KNOW AND MAKE SURE OTHERS IN YOUR HOUSEHOLD KNOW THE FOLLOWING PROCEDURES TO TAKE IN THE EVENT OF A PROPANE...

Страница 6: ...mm wc 7 178 mm wc 10 254 mm wc 10 254 mm wc 10 254 mm wc 11 279 mm wc 11 279 mm wc 11 279 mm wc 13 330 mm wc 13 330 mm wc 13 330 mm wc 3 8 NPT 3 8 NPT 3 8 NPT 2 51 mm 2 51 mm 2 51 mm 12 305 mm 12 305...

Страница 7: ...osing a location for your ORBIS Calorama Comfort View Series Direct Vent Wall Furnace please remember that the Vent Kit supplied with the unit must be installed WITHOUT alteration with the exception o...

Страница 8: ...sure regulator provided with this unit C 12 in minimum 12 in minimum 4 ft minimum 4 ft minimum 12 in minimum 3 ft minimum Grade Forced air inlet Mechanical draft vent terminal see 7 8 b Mechanical dra...

Страница 9: ...3 The template illustrates all of the openings and mounting holes and their correct location for EACH UNIT The illustration Figure 3 gives you the required dimensional information for mounting the uni...

Страница 10: ...shed unit to adjacent combustible materials Figure 3 ALL MODELS Unit Mounting Instructions 8 35 212 mm 1 65 42 mm 11 89 302 mm 12 09 307 mm 10 85 275 5 mm 14 78 375 5mm 7 89 200 5 mm 4 8 121 9 mm 5 12...

Страница 11: ...10 Figure 4 Unit Mounting Template Position Figure 5 Wall Mounting Plate ALL MODELS Unit mounting positions Wall mounting positions TEMPLATE...

Страница 12: ...ombustion and ventilation air must NEVER be obstructed Prepare for Installation After ensuring that the location you have selected for the installation complies with the requirements outlined in this...

Страница 13: ...rotection pipe to pass through without bending In addition make sure that the holes in the inside and outside wall are concentric to one another NOTE Cut the outside hole slightly lower not more than...

Страница 14: ...he vent cap is securely engaged with the similar sized opening in the rear of the unit Make sure the exhaust vent pipe remains engaged in its position in the vent cap The air inlet pipe must also slid...

Страница 15: ...ust be installed in accordance with all applicable building and plumbing codes For Propane Units Gas supply Line Pressure MUST NOT EXCEED 13 IN W C It is recommended that a gas shut off valve be insta...

Страница 16: ...e bubbles to form Note any leaks in the piping system Shut off the gas at the shut off valve if installed or at the gas meter of the Propane LP tank serving the structure Fix the leaking joint and re...

Страница 17: ...in or turn by hand don t try to repair it call qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Im...

Страница 18: ...the most comfort for you Excessively high temperature settings can cause you to constantly readjust the thermostat and lose valuable efficiency WARNING DO NOT OPERATE THIS APPLIANCE WITH THE PILOT MA...

Страница 19: ...he back cover Step 4 Carefully examine the interior of the vent pipe If you notice any blockage or obstruction that was not part of the unit when it was installed clean the pipes and prepare them for...

Страница 20: ...k on the wall mounting plate Step 8 Reconnect the gas supply Perform the leak test procedure found in the section of this manual titled Check for Gas Leaks on page 14 Step 9 Verify Proper Operation Af...

Страница 21: ...d of the front cover leaning about an inch forward push the front cover in and down until the bolts lock into place Slide the overhangs at the upper end of the front cover under the back cover and fix...

Страница 22: ...is damaged or wire lead is loose 3 Pilot orifice is clogged 4 Gas Control knob not set properly 5 Improper gas supply SOLUTION 1 No action required will stop after a short period of operation 2 Apply...

Страница 23: ...that position is in the center of the pilot flame tip Replace as necessary 3 Wait 5 minutes to allow the heater to cool down then relight 1 Review correct lighting procedures see Figure 10 on page 15...

Страница 24: ...as supply SOLUTION 7 Call your gas supplier 1 Adjust thermostat to HI position and modulate down until a proper room temperature rate is attained 2 Average room size heating capacity UNIT Ave Floor Ar...

Страница 25: ...24 SECTION VI REPLACEMENT PARTS GUIDE Orbis Calorama Comfort View Series Gas System 2 15 1 3 6 7 8 4 5 9 10 11 12 14 1 A B C D E F 13...

Страница 26: ...n Burner Injector CCV III L P 1 35mm CCV 3004P 5 Main Burner Injector Adaptor CCV 5005 6 A Pilot Injector CCV N G 0 25mm 2x CCV 5006N 6 B Pilot Injector CCV L P 0 20mm CCV 5006P 7 Electrode Ceramic CC...

Страница 27: ...costs must be borne by the Purchaser Exceptions This warranty will not apply 1 to defects or malfunctioning resulting from failure to properly install operate or maintain the unit in accordance with...

Страница 28: ...CE TECHNICIAN OR APPLIANCES SERVICES AND PARTS COMPANY INC ASAP INFORMATION BELOW MANUFACTURED BY ORBIS MERTIG SAIC YERBAL 1200 1607 VILLA ADELINA PROVINCIA DE BUENOS AIRES ARGENTINA IMPORTED BY THE G...

Страница 29: ...ide of the unit above the gas valve See figure 13 With the cover still off mount blower into the wall directly under and centered on the unit using the two fastening screws provided See figure 12 for...

Страница 30: ...ESCRIPTION PART NUMBER OF PART NUMBER 1 A Blower kit Calorama Comfort View I BK 1 1 B Blower kit Calorama Comfort View II BK 2 1 C Blower kit Calorama Comfort View III BK 3 1 D Blower Fan All Units BK...

Отзывы: