![Oracle Tekelec 1200 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/oracle/tekelec-1200/tekelec-1200_installation-manual_1646178023.webp)
Warning: Before drilling holes in any flooring, verify with facilities personnel that the
area is free of gas or water pipes, ventilation plenum, and electrical wiring conduits.
Warning: Finger-tighten nuts on threaded rods inside the frames above the raised floor
before finger tightening the nuts below the raised floor.
Caution: Frame ground. Do not “double lug”: The practice of using one bolt through a
lug and the ground bar, and through another lug on the other side of the ground bar,
held in place by one nut.
Caution: After the frame has been shipped or moved, remove all cards prior to applying
power. Carefully reset cards to avoid possible faulty connections.
Power
Danger: Strictly observe all grounding requirements to reduce the risk of electric shock.
Danger: Do not use or place commercially AC-powered equipment within 7 ft. of –48V
equipment. Close proximity can create a shock or current loop that is severely hazardous
to personnel and equipment.
Warning: The intra-building port(s) of the equipment or subassembly is suitable for
connection to intra-building or unexposed wiring or cabling only. The intra-building
port(s) of the equipment or subassembly MUST NOT be metallically connected to
interfaces that connect to the Outside Plant (OSP) or its wiring. These interfaces are
designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described
in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The
addition of Primary Protectors is not sufficient protection in order to connect these
interfaces metallically to OSP wiring.
Warning: Before testing -48VDC power source:
• Ensure that no power is being provided to the system from the –48VDC power source,
such as a power board
• Ensure that no circuit cards are installed in the shelves
• Open all circuit breakers in the PDP
• Recheck wiring and connections for proper polarity
23
910-5681-001 Revision E, February 2014
Safety and Pre-Installation Requirements
Installation