Cable:
Belden #88760 or Alpha #55371
3.6m (12 feet) of gas & oil resistant cable to the inline ISIM
+ 1.3m (4 feet) ISIM tail.
Maximum Wiring Length*:
305 m (1,000 ft.) field wiring
Alarm Threshold Configuration:
Fully Automatic
Diagnostic Reading on Sensor Setup:
0 to 1 (normal) above 5 (in-alarm)
Multi-Drop Restriction
See Mixed Multi-Drop Installation
Connections:
Red = Power, Black = Signal, Shield = Ground
NOTE:
*This is the maximum length of wire to be used to connect all sensors on one channel.
This length includes the wire from the VSmart to each sensor board in the string.
Installation
IMPORTANT:
This Smart Sensor must ONLY be connected to an OPW Fuel Management
Systems 12V VSmart Module. This will make sure that operation conditions are safe. Smart
Sensors CANNOT be used with SS1, 2 or 3, iTouch or EECO consoles.
CAUTION:
ALWAYS obey Local and National Electrical Codes applicable
to the installation location.
Make sure that the cables (gas and oil resistant OPW Fuel Management
Systems part # 12-1030) from the field wiring to the controller are in conduit
that is dedicated to intrinsically safe wiring.
Use wire-nuts and epoxy-resin seal-packs for field connections (refer to
M00-390008 Waterproof Electrical Connections
for information).
NOTE:
The device will NOT sense hydrocarbon vapor if it is fully in water.
l
This sensor uses ONE Controller Interface I.S. Module position
l
Start with the Connections table and “Typical Installation" drawing below.
l
Do a check to make sure there are no hydrocarbon vapors before you install this sensor in a Dry
Monitoring Well.
Doc. No.: M2010-EU Rev.: 13
Page 104 of 149
Содержание M2010-EU
Страница 6: ...Warranty 147 Doc No M2010 EU Rev 13 Page 6 of 149...
Страница 20: ...Main Board Connections Jumpers and LEDs Doc No M2010 EU Rev 13 Page 20 of 149...
Страница 21: ...Conduit Installation Doc No M2010 EU Rev 13 Page 21 of 149...
Страница 22: ...Field Wiring Diagram Doc No M2010 EU Rev 13 Page 22 of 149...
Страница 32: ...Doc No M2010 EU Rev 13 Page 32 of 149...
Страница 38: ...924B Probe Installation DMP Probe Installation Doc No M2010 EU Rev 13 Page 38 of 149...
Страница 41: ...Doc No M2010 EU Rev 13 Page 41 of 149...
Страница 86: ...Typical Installation Drawings 30 0230 S Doc No M2010 EU Rev 13 Page 86 of 149...
Страница 110: ...Appendix C Declaration of Conformity Doc No M2010 EU Rev 13 Page 110 of 149...
Страница 111: ...Doc No M2010 EU Rev 13 Page 111 of 149...
Страница 112: ...Doc No M2010 EU Rev 13 Page 112 of 149...
Страница 113: ...Doc No M2010 EU Rev 13 Page 113 of 149...
Страница 142: ...Doc No M2010 EU Rev 13 Page 142 of 149...
Страница 146: ...Doc No M2010 EU Rev 13 Page 146 of 149...
Страница 149: ......