Installation
6
Sinergy S II Series Series UPS User Instruction Manual
Storage
If the UPS is to be stored prior to use, it should be stored in a clean, dry environment and away from
temperature extremes. It is recommended that the equipment be stored in a temperature controlled,
moderate humidity environment. Table 1 below provides the temperature and humidity storage limits:
NOTE:
When storing equipment, every 8°C above 25°C reduces the shelf life of the battery by 50%. More
frequent battery charging is required to maintain the batteries in storage at these greater temperatures.
Environmental
Conditions
The UPS must be installed on a level and even surface and in an area protected from extremes of
temperature, water, humidity and the presence of conductive powder or dust (See Table 2 on page 6). Do
not stack units and do not place any objects on top of a unit.
The functional temperature range of the UPS is 32°F to 104°F (0°C to 40°C).
The ideal ambient temperature range is 60°F to 77°F (15 °C to 25°C).
Expected battery runtimes and battery life is based on operational temperatures between 68°F and 77°F (20°C
and 25°C). Operation of the equipment above 77°F (25°C) reduces the service life of the batteries dramatically.
Floor Loading
Taking into consideration the weight of the UPS, extension battery packs, and any other equipment that
may be mounted in an associated rack, confirm that the floor in the chosen location be capable of
supporting the weight of the combined units.
NOTE:
Weights for the UPS and battery packs are shown in Appendix A, “Specifications”.
Ventilation
It is necessary to leave a minimum space of at least two inches (50 mm) in front and rear of the UPS to
allow a flow of air.
Electrical maintenance and servicing requires access to the front and back of the UPS. Provide the
necessary space to allow service personnel access to the UPS.
Installation
ATTENTION:
This UPS is supplied with standard power cords and receptacles suitable for its use in
your area of operation. It may be installed and operated by non-technical personnel..
Table 1. Storage Data
Temperature limits -Batteries ONLY
32°F to 104°F (0°C to +40°C)
Temperature limits - UPS without batteries
-13°F to 131°F (-25°C to +55°C)
Temperature limits – UPS with batteries
32°F to 104°F (0°C to +40°C)
Relative humidity (non-condensing)
0% to 90%
Table 2. Installation Data
Item
Specification
Ambient temperature
32°F to 104°F (0 °C to 40C°)
Relative humidity (non condensing)
90%
Environment
Controlled (i.e. Office or equivalent)
Max. altitude (w/o derating)
3300 ft. above sea level (1000 m.a.s.l.)
Derated to 82%
10000 ft. above sea level (3048 m.a.s.l.)
Input Power Connection
Rear
Output Power Connection
Rear
Battery Power Connection
Rear
Air inlet
Front
Air outlet
Rear