Elements of SFC
Section 2-3
48
Controlling a Step in an SFC Program from an Action Ladder Program within
the Same SFC Program
SA
Activate
SFC Program
Controlling an SFC Step from an Action Ladder Program within Another SFC
Program
SA
SFC Program
SFC Program
Activate
Note:
If the SA step control instruction is used to activate another step in the same
SFC program from an action ladder program in the SFC program, the activated
step’s action will be executed in the next cycle.
If the SA step control instruction is used to activate a step in a different SFC program
from an action ladder program in the SFC program, the activated step’s action will be
executed in the current or in the next cycle, depending on the order of the SFC
program execution task numbers.
•
If the SFC program containing the step activated with the SA step control
instruction has already been executed, the activated step will be executed in the
next cycle.
•
If the SFC program containing the step activated with the SA step control
instruction has not yet been executed, the activated step will be executed in the
same cycle.
Step timer value read/set instructions can be used in the same way as step
activation/deactivation instructions.
•
A step can have a step timer to maintain the time, which has elapsed since the step
became active. For each step, the time unit on the step timer can be set to either
of the following:
Содержание SYSMAC CX-Programmer 8.1
Страница 1: ...Operation Manual SFC Programming SYSMAC WS02 CXPC1 V8 CX Programmer Ver 8 1 Cat No W469 E1 04...
Страница 2: ...ii CX Programmer Ver 8 1 WS02 CXPC1 V8 Operation Manual SFC Programming Revised February 2009...
Страница 16: ......
Страница 56: ...Precautions When Creating SFC Programs Section 1 5 40...
Страница 117: ...Monitoring Section 4 5 101 For details refer to 3 2 3 Adding an Action to a Step or to the Initial Step...
Страница 118: ...Monitoring Section 4 5 102...
Страница 150: ...Index 134...
Страница 152: ...Revision History 136...
Страница 153: ......
Страница 154: ......